Home > GB > GB 5023.3-1997 Polyvinyl chloride insulated cables of rated voltage 450/750V and below Part 3: Unsheathed cables for fixed wiring
GB 5023.3-1997 Polyvinyl chloride insulated cables of rated voltage 450/750V and below Part 3: Unsheathed cables for fixed wiring
Basic Information
Standard ID:
GB 5023.3-1997
Standard Name: Polyvinyl chloride insulated cables of rated voltage 450/750V and below Part 3: Unsheathed cables for fixed wiring
Part 3 of this standard specifies in detail the technical requirements for PVC insulated single-core non-sheathed cables for fixed wiring with rated voltages of 450/750V and below. All cables shall comply with the corresponding requirements specified in GB 5023.1, and various types of cables shall comply with the special requirements specified in this part. GB 5023.3-1997 PVC insulated cables with rated voltages of 450/750V and below Part 3: Non-sheathed cables for fixed wiring GB5023.3-1997 Standard download decompression password: www.bzxz.net
Some standard content:
1 General 1.1 Scope National Standard of the People's Republic of China Polyvinyl chloride insulated cablesof rated voltages up to and including 450/750V Part 3:Non-sheathed cables for fixed wiringGB5023-3—1997 fdt IEc 227-3:1993 Replaces GB5023.2—85 GB 5023.3—85 Part 3 of this standard specifies in detail the technical requirements for polyvinyl chloride insulated single-core non-sheathed cables for fixed wiring of rated voltages up to and including 450/750V. All cables shall comply with the corresponding requirements specified in GB5023.1, and various types of cables shall comply with the special requirements specified in this part. 1.2 Referenced Standards The provisions contained in the following standards constitute the provisions of this standard through reference in this standard. When this standard is published, the versions shown are valid. All standards will be revised, and parties using this standard should explore the possibility of using the latest versions of the following standards. GB/T2951.1—1997 General test methods for cable insulation and sheathing materials Part 1: General test methods Section 1: Measurement of thickness and overall dimensions GB/T 2951.21997 Mechanical properties test General test methods for cable insulation and sheathing materials Part 1: General test methods Section 2: Thermal aging test methods GB/T 2951.4—1997# General test methods for cable insulation and sheathing materials Part 1: General test methods Section 1: Low temperature test General test methods for cable insulation and sheathing materials GB/T 2951.61997 Part 3: Special test methods for ethylene fluoride mixtures Section 1: High temperature pressure test - cracking resistance test General test methods for cable insulation and sheathing materials GB/T 2951.7—1997 Part 3: Special test methods for polyvinyl chloride mixtures Section 2: Weight loss test-thermal stability test GB/T3956—1997 Cable conductors GB5023.1-1997 Polyvinyl chloride insulated cables with rated voltages of 450/750V and below Part 1: General requirements Approved by the State Administration of Technical Supervision on July 30, 1997 Implemented on September 1, 1998 GB 5023. 2—1997 GB 5023. 3—1997 Polyvinyl chloride insulated cables with rated voltages up to and including 450/750V Part 2: Test methods GB/T12666.2-90 Fire test methods for wires and cables Part 2: Vertical fire test methods for single wires and cables 2 Single-core rigid conductor non-sheathed cables for general use 2.1 Model 227 IEC 01(BV). 2.2 Rated voltage 450/750V. 2.3 Structure 2.3.1 Conductor Number of cores: 1 core. The conductor shall comply with the requirements specified in GB/T3956. Type 1 is used for a solid conductor. Type 2 is used for a stranded conductor. 2.3.2 Insulation The insulation extruded on the conductor shall be a PVC/C type hydrophilic vinyl mixture. The insulation thickness shall comply with the value specified in column 3 of Table 1. The insulation resistance shall not be less than the value specified in column 5 of Table 1. Table 1227Comprehensive data of IEC 01 (BV) type cableConductor nominal cross section Conductor type Insulation thickness specified value Average outer diameter upper limit Minimum insulation resistance at 70℃ Ma·km Conductor nominal cross section 2.3.3 Outer diameter Conductor type GB 5023.3—1997 Table 1 (end) Insulation thickness specified value Average outer diameter shall not be greater than the upper limit specified in column 4 of Table 1. 2.4 Test Upper limit of average outer diameter The inspection and test specified in Table 2 shall be used to check whether it meets the requirements of 2.3. 2.5 Guidelines for use In normal use, the maximum temperature of the conductor is 70℃. Note: Other guidelines are under consideration. Table 2227Test item number of IEC01 (BV) type cable Electrical performance test Conductor resistance 2 500V voltage test Insulation resistance at 70 ms Structural dimension inspection Structural inspection Thickness measurement Outer diameter measurement Insulation mechanical properties Tensile test before aging Tensile test after aging Fish loss test High temperature pressure test Test items Low temperature elasticity and impact strength Insulation low temperature bending test Insulation low temperature tensile test|| tt||Continuous low-temperature impact test Thermal shock test No delay test 1) It is only applicable when the outer diameter of the cable exceeds the limit value specified in the test method. Test type Minimum insulation resistance at 70℃ MQ·km Test method GB(GB/T) 5023.1 and 5023.2 5023-1 Article number Inspection and manual test 8. 1. 3.1 3 General purpose single-core soft conductor non-sheathed cable 3.1 Model 227IEC02(RV). 3.2 Rated voltage 450/750V. 3.3 Structure 3.3.1 Conductor Number of cores: 1 core. GB 5023. 3—1997 Conductors shall comply with the requirements of the 5th conductor specified in GB/T3956. 3.3.2 Insulation The insulation extruded on the conductor shall be a PVC/C-type polyvinyl nitride mixture. The insulation thickness shall comply with the specified value in the second column of Table 3. The insulation resistance shall not be less than the specified value in the fourth column of Table 3. 3.3.3 Outer diameter The average outer diameter shall not be greater than the upper limit specified in the third column of Table 3. 3.4 Test The inspection and test specified in Table 4 shall be used to check whether the requirements of 3.3 are met. 3.5 Guidelines for use In normal use, the maximum temperature of the conductor is 70 °C. Note: Other guidelines are under consideration. Table 3227 General data of IEC02 (RV) type cable Nominal conductor cross section Specified value of insulation thickness Upper limit of average outer diameter Minimum insulation resistance at 70°C 0.004 6 Electrical performance test Conductor resistance 2500V voltage test Insulation resistance at 70°C Structural dimension inspection Structural inspection Insulation thickness measuring plate Outer diameter measurement Insulation mechanical properties Tensile test before aging Tensile test after aging Weight loss test High pressure test Low temperature elasticity GB 5023. 3--1997 Table 4227 Test items for IEC02 (RV) type cable Test items Insulation low temperature bending test Insulation low temperature tensile test\ Thermal shock test Non-flame retardation test 1) Applicable only when the cable outer diameter exceeds the limit value specified in the test method. Test type Test methodwwW.bzxz.Net GB(GB/T) Single-core solid conductor non-sheathed cable with conductor temperature of 70°C for internal wiring4 4.1 Model 227 IEC 05(BV) 4.2 Rated voltage 300/500 V. 4.3 Structure 4.3.1 Conductor Number of cores: 1 core The conductor shall meet the requirements of the first type of conductor specified in GB/T3956, 4.3.2 Insulation The insulation extruded on the conductor shall be PVC/C type polyvinyl chloride mixture. The insulation thickness shall comply with the value specified in column 2 of Table 5. The insulation resistance shall not be less than the value specified in column 4 of Table 5. 4.3.3 Outside diameter The average outside diameter shall not be greater than the upper limit value specified in column 3 of Table 5. 5023.2 5023.1 and 5023.2 Document number Inspection and manual test 8. 1. 3. 1 Conductor nominal cutting area 4.4 Test GB 5023. 3—1997 Table 5227Comprehensive data of IEC05 (BV) type cableInsulation thickness specified value Average outer diameter upper limit The inspection and test specified in Table 6 shall be used to check whether it complies with the requirements of 4.3. Guidelines for use In normal use, the maximum temperature of the conductor is 70℃. Note: Other guidelines are under consideration. 227IEC05(BV) type cable test items table 6 Electrical performance test Conductor resistance 2000V voltage test Insulation resistance at 70℃ Structural dimension inspection Structural inspection Insulation thickness measurement Outer diameter measuring plate Insulation mechanical properties Tensile test before aging Tensile test after aging Loss of mass test High temperature pressure test Low temperature elasticity Low temperature bending test of insulation Thermal shock test Non-flame retardation test 5 Single-core soft conductor non-sheathed cable with conductor temperature of 7D C for internal wiring 5.1 Type 227IEC 06(RV). 5.2 Rated voltage 300/500 V. 5.3.1 Conductor Number of cores: 1 core. Test type Minimum insulation resistance at 70 ms MQ·km Test method GB(GE/T) 5023. 1 and 5023. 2 Article number Inspection and manual test 8. 1. 3.1 GB5023.3--1997 Conductors shall comply with the requirements for the fifth type of conductors specified in GB/T 3956. 5.3.2 Insulation The insulation extruded on the conductor shall be a mixture of PVC/C-type polyvinyl chloride. The insulation thickness shall comply with the value specified in column 2 of Table 7. The insulation resistance shall not be less than the value specified in column 4 of Table 7. 5.3.3 Outer diameter The average outer diameter shall not be greater than the upper limit specified in column 3 of Table 7. Table 7227Comprehensive data of IEC 06 (RV) type cableConductor nominal surface 5.4 Tests Insulation thickness specification Average outer diameter upper limit The requirements of 5.3 shall be checked by the tests and tests specified in Table 8. 5.5 Guidelines for use In normal use, the maximum temperature of the conductor is 70°C. Note: Other guidelines are under consideration. 227Test items for IEC06 (RV) type cable Electrical performance test Conductor resistance 2000V voltage test Insulation resistance at 70'C Structural dimension inspection Structural inspection Insulation thickness measurement Outer diameter measurement Insulation mechanical properties Tensile test before aging Tensile test after aging Weight loss test High temperature pressure test Low temperature elasticity Test items Low temperature insulation bending test Thermal shock test Non-flame retardation test Test type Minimum insulation resistance at 70℃ Mn·km Test method GB(GB/T) 5023-2 5023. 1 and 5023. 2 Article number Inspection and manual test 8. 1. 3.1 GB 5023.3—1997 6 Single-core solid conductor non-sheathed cable with a conductor temperature of 90°C for internal wiring 6.1 Model 227IEC 07 (BV-90). 6.2 Rated voltage 300/500V. 6.3 Structure 6.3. 1 Conductor Number of cores: 1 core. The conductor shall comply with the requirements of the first type of conductor specified in GB/T 3956. 6.3.2 Insulation The insulation extruded on the conductor shall be PVC/E type polyvinyl chloride mixture. The insulation thickness shall comply with the specified value in the second column of Table 9. The insulation resistance shall not be less than the value specified in column 4 of Table 9. 6-3.3 Outer diameter The average outer diameter shall not be greater than the upper limit value specified in column 3 of Table 9. Table 9227Comprehensive data of IEC07 (BV-90) type cableConductor nominal cross section 6.4Test Specified value of insulation thickness Upper limit of average outer diameter The test and test specified in Table 10 shall be used to check whether it complies with the requirements of 6.3. 6.5Guidelines for use In normal use, the maximum temperature of the conductor is 90 ℃, and the minimum insulation resistance at 90 ℃ Mn·km When the cable is used in an environment that prevents thermoplastic flow and allows a reduction in insulation resistance, the PVC mixture that can be used continuously at 90 ℃ can be increased to 105 ℃ under the premise of shortening the total working time. Note: Other guidelines are under consideration. Table 10227Test items for IEC 07 (BV-90) type cableNo. Electrical performance test Conductor resistance 2 000 V voltage test Continuous resistance at 90°C Structural dimension inspection Structural inspection Insulation thickness measurement Outer diameter measurement Test items Test type GB (GB/T) 5023-1 and 5023. 2 5023-2 Article number Inspection and manual test Absolute mechanical properties Tensile test before aging Tensile test after aging Loss of mass test High temperature pressure test Test items Low elasticity Insulation low temperature bending test Thermal shock test No flame retardancy test Thermal stability test GB 5023. 3—1997 Table 10 (end) Test type 7 Single-core soft conductor non-sheathed cable with a conductor temperature of 90°C for internal wiring 7.1 Model 227IEC08 (RV-90) 7.2 Rated voltage 300/500 V. 7.3 Structure 7. 3. 1 Conductor Number of cores: 1 core. The conductor shall comply with the requirements of the 5th type of conductor in GB/T3956. 7.3.2 Insulation The insulation extruded on the conductor shall be a PVC/E type polyvinyl chloride mixture. The insulation thickness shall comply with the value specified in the second column of Table 11. The insulation resistance shall not be less than the value specified in the fourth column of Table 11. 7.3.3 Outer diameter The average outer diameter shall not be greater than the upper limit specified in column 3 of Table 11. Test method GB(GB/T) 2951-6 Table 11227Comprehensive data of IEC08(RV-90) type cableConductor nominal surface 7.4 Test Insulation thickness Specified value Average outer diameter upper limit The inspection and test specified in Table 12 shall be used to check whether the requirements of 7.3 are met. 7.5 Guidelines for use Article number 8. 1. 3. 1 Minimum insulation resistance at 90℃ In normal use, the maximum temperature of the conductor is 90℃GB5023.3—1997 When the relay is used in an environment that prevents thermoplastic flow and allows for reduced insulation resistance, PVC mixtures that can be used continuously at 90°C can have their operating temperature increased to 105°C while shortening the total operating time. Note: Other guidelines are under consideration. Table 12227IEC08 Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.