title>GB/T 14808-2001 AC high voltage contactors and contactor-based motor starters - GB/T 14808-2001 - Chinese standardNet - bzxz.net
Home > GB > GB/T 14808-2001 AC high voltage contactors and contactor-based motor starters
GB/T 14808-2001 AC high voltage contactors and contactor-based motor starters

Basic Information

Standard ID: GB/T 14808-2001

Standard Name: AC high voltage contactors and contactor-based motor starters

Chinese Name: 交流高压接触器和基于接触器的电动机起动器

Standard category:National Standard (GB)

state:in force

Date of Release1993-01-02

Date of Implementation:2002-06-01

standard classification number

Standard ICS number:>>29.130.10 High voltage switchgear and controllers

Standard Classification Number:Electrical Engineering>>Power Transmission and Transformation Equipment>>K43 High Voltage Switchgear

associated standards

alternative situation:GB/T 14808-1993

Procurement status:eqv IEC 60470:1999

Publication information

publishing house:China Standards Press

Publication date:2002-06-01

other information

Release date:1993-12-28

Review date:2004-10-14

Drafting unit:Tianshui Great Wall Switch Factory

Focal point unit:National Technical Committee for Standardization of High Voltage Switchgear

Publishing department:General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China

competent authority:China Electrical Equipment Industry Association

Introduction to standards:

This standard applies to indoor AC contactors and/or contactor-based motor starters used in power systems with rated voltages of 3.6 kV and above but not exceeding 12 kV and frequencies of 50 Hz and below. This standard is only applicable to three-pole contactors and starters in three-phase systems, and single-pole contactors and starters used in single-phase systems. Two-pole contactors and starters used in single-phase systems should be negotiated between the manufacturer and the user. The contactors and/or starters involved in this standard are generally not used to break short-circuit currents, so appropriate short-circuit protection (see 3.4.110.12 and Note 2 below) can be part of the device, but not necessarily part of the contactor or starter. This standard sets requirements for the following devices: - Contactors associated with overload and/or short-circuit protection devices (SCPD); - Starters associated with separate short-circuit protection devices and/or separate short-circuit and overload protection devices integrated therewith; - Contactors or starters combined with their own short-circuit protection devices according to specified conditions. These combined appliances, such as integrated starters (see 3.4.110.9), are considered as a whole. This standard covers contactors used to close and open circuits and, if combined with suitable relays (see 3.6.108), to protect the circuits from possible overloads. This standard also applies to contactor operating devices and their auxiliary equipment. This standard covers motor starters used to start and accelerate motors to normal speed, ensure continuous operation of the motor, cut off the power supply to the motor and provide protection for overloads of the motor and the circuits connected to it. Types of motor starters include: - direct starters - reversing starters - bidirectional starters - reduced voltage starters - autotransformer step-down starters - varistor starters - reactor starters. Starters whose operation depends on thermal relays for protecting motors in accordance with GB/T 14598.15 or thermal protection devices for motors in accordance with GB 13232 do not need to meet the relevant requirements of this standard. Overload relays for starters, including those based on solid-state technology, are included in the scope of this standard. This standard does not apply to: - circuit breaker-based motor starters; - single-pole operation of multi-pole contactors or starters; - two-stage auto-decompression starters for continuous operation in the starting position; - asymmetric variable resistance rotor starters, that is, starters with different resistance values ​​for all phases; - equipment that can start and adjust the speed; - liquid starters and "liquid-steam" starters; - semiconductor contactors and starters using semiconductor contactors in the main circuit; - variable resistance stator starters; - contactors or starters for special purposes. This standard does not involve the components installed in contactors and contactor-based starters, as they have their own technical requirements. The purpose of this standard is to specify: a) the characteristics of contactors, starters and related equipment; b) the relevant conditions that contactors and starters should comply with; - operation and characteristics; - insulation performance; - when applicable, the degree of protection of the enclosure; - structure; - for integrated starters, the interaction between the various components, such as coordination with SCPD. c) tests used to confirm that these conditions have been met, and the methods used for these tests; d) information that should be indicated in the accompanying documents or manufacturer's documents. GB/T 14808-2001 AC high voltage contactors and contactor-based motor starters GB/T14808-2001 standard download decompression password: www.bzxz.net

Some standard content:

JCS.29-130.10
National Standard of the People's Republic of China
GB/T14808—2001
eIFC 60470:1999
High-voltage alternating current contactorsand contactor-based miotor-starters2001-11-02 Issued
General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China
2002-06-01 Implementation
GB/T 148082001
IEC language
1.1 Specification
1.2 Reference standards
2 Normal use conditions
2.1 Normal use conditions
2.2 Special use conditions
3 Nomenclature
Pre-application terms
And related equipment
Components of switchgear
Components of switchgear and controlgear
Characteristic parameters
Fuse|||Rated value
Rated voltage point)
All insulation levels are studied.
Reliable frequency part ()-
Rated current and temperature rise:
Rated withstand current ()-
Agreed range current ()
Drive duration (limit)
The power supply voltage of the combined power supply and auxiliary power supply circuit is 4-10V
The rated pressure of the power supply and/or the operating pressure is less than 10V. The rated current, or rated power
Rely on 1. Manufacturing..
Rely on load and overload resistance
Position category...
Match with the protection device
Type and net size of automatic conversion device and automatic acceleration control device 14H82001
Types and characteristics of pressure reducing inductors or reactors for first 10% starting 4.110
Types and characteristics of starting resistors for variable resistance starters 4.111
Unique characteristics of variable resistance starters
. Design and structure
Requirements for liquid
Requirements for gas
Auxiliary and control equipment:
Power conversion,
Energy building operation:
Operation of dependent persons
Remote protection device
Power monitoring device
Network brand ...
Mounting bone
Position indication
Enclosure protection grade
Creep current protection
Gas and vacuum sealing
Comparison rate
Product flammability
Electromagnetic combination
Type of intermediate device or trip device
Combined starter
Interconnection test between circuit breaker and indicator or contactor
|Isolation test:
Radio interference voltage (r...5.) test
Four-way resistor test
Thermometer test
Short-circuit current test...Frequency test caused by protective measures
Pressure test
3.3 Electromagnetic combined operation test (FMC)
r-10-1
Mechanical test...
Closing and breaking capacity test
Overcurrent withstand test·
Short-circuit current closing and breaking test
GR/T14808—2001
Overload relay is the frequency limit test of the positive coordination with SP
Pre-test.
Heartbeat opening and closing test
Out! 7. 5. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59. 60. 61. 62. 63. 64. 65. 66. 67. 68. 69. 70. 71. 72. 73. 74. 75. 76. 77. 78. 79. 80. 81. 82. 83. 84. 85. 86. 87. 88. 89. 90. 91. 92. 93. 94. 95. 96. 97. 98. 99. .1 core 2 and light-limiting fuse according to SCFD when the information provided 1 transportation must be stored, installation, operation and correction of the existing rules 11 individual.
recorded A (standard appendix) related points, new and short-term performance type test records and reports 32
GH/T146CE2331
This standard is equivalent to IF; 190th edition AC high positive contactor and motor starter based on the contactor. Standard equivalent chemical difference follows the faithful three, limited and inherited like purchase: 4 standard and 1EC:riU170:1SSS blue must be described: a single fixed voltage E7C:! 11 is" ​​0 above but not more than 12:4.1 fixed voltage standard according to 2. kV3. tkV-5. kV. 7. 2k—12kV)1—Specification level: (IEC, 10/70:1999 value 1 uses TEC60694:19) Rated thermal rate: (IEC6070:1999 4.3 teaching rated frequency is 50H and %0E121; RVEe:D0 h without test circuit width RV requirement. 1.4. Figure 5: IF4:15 Figure 4 and Figure 5 in Figure 4 and Figure 5 are annual load without seat resistance. The medical test is a test force type transfer current standard test. It is not a test of the test end benefit circuit. The connection method is inconsistent with the actual working record. Therefore, its load is convenient for some parts to expand: .11.4 The discussion on the layout of the test circuit is different from Figure 4 and Figure 5 in 1:47: The quality of the RV control sensitivity of the different connections is different. The test results of the linear product are not good. This standard is modified according to 1F core 6470V box and TECA:
In order to have a wider range of applicability and compatibility. This standard follows the following regulations: This standard promotes the Chinese standard in accordance with the following original measurement and adherence, and the referenced standards in the third edition are directly quoted when there are corresponding national standards and clauses. The national standards and clauses are directly quoted when there are no national standards and clauses. The standards and clauses of this standard will be replaced from the year of implementation: GB[150%993. Appendix A of this standard is the record of the difficult standards.
This standard is issued by the China Export Equipment Industry Association. This standard is the responsibility of the National Dongwan Guan Equipment Standardization Technical Committee and the import and export: This standard is the starting point of the chapter unit:
Responsible unit: Dashou Great Wall The switch factory is made in the original horse type, which is not long-lasting. Li Jia unit: Xi'an Gaole Electric Research Institute, Liu Qingtai Beijing Switch Factory Li Zhiya. Sa Duanshan: Jinzhou II Switch! Wu Min, Meishan, Xu Case: Shanghai Guangzhong Electric - (Frame) Co., Ltd. Year: This standard is entrusted to the International Technical Committee for Standardization of Switchgear Equipment for Standardization. GR/T14808—2001
IEC former moss
1) C (International Technical Committee) is a world standardization organization composed of national committees of various giants (1C). The purpose of IE is to promote international cooperation on all issues related to international standardization in the electrical and electronic fields. For this In addition to the relevant activities, the publication area indicates that these standards are drafted by the technical committee: the national committee responsible for this is able to participate in the drafting. International, governmental and non-international organizations that cooperate with EC are also gradually involved in the drafting. [EC and the International Organization for Standardization (ISO) work together in parallel according to their own conditions. 2) Formal decisions of the C on technical issues must be made by consensus, and all national committees concerned with this issue will have representatives of more than one technical point of view. They are free to express their technical concerns. 3) These decisions may be published in the form of standards, technical reports or guidelines for use as recommended standards and accepted by the technical committees in this sense.
4) In order to promote international unification, the various countries will agree to adopt international standards as far as possible in their national and regional standards. Any differences between national and regional standards should be clearly stated in the text of the standard.
3) IE does not carry out the issuance of conformity marks. 1. It does not assume responsibility for the establishment of a TF standard. 6 It should be noted that this standard may be the subject of a patent and will not be recognized in one or all such specialties.
IEC60470 is fully covered by 1E:IC:17-Switchgear and control equipment\SC:17A\Screening switch ... ||The content of this standard is based on the following documents: |FDIS
17A/4/FIES
Report
173/554/RVD
Report on the cost standard can be found in the voting report indicated in the table above.
1 Overview
National Standard of the People's Republic of China
AC high-voltage contactors and contactor-based motor starters
Eight-valtre alternuling airrem ranlectorsand cuntactur-bused motor starlers1.1 Specification and application
GB/T1408-2GJ
eq: IEC 60470:999
Replacement GB 113c3-592
This standard applies to AC terminals and/or motor starters based on rectifiers installed in production with rated voltage of 1000 kV or above but not exceeding 12 V and power of 5 H or below. This standard is applicable to three-pole contactors and starters in three-phase systems and single-pole contactors and starters in single-phase power systems. The use of two-pole contactors and starters in single-phase systems should be negotiated between the manufacturer and the user. The contactors and/or starters covered by this standard shall be Starter: Generally, a short-circuit protection device is not required. Therefore, when short-circuit protection is provided (3, 4.11, 3.12 and Note 2 below), it can be part of the device and must not become part of the complete device or the active device. This standard lists the following devices that exceed these requirements:
Connectors with overload and/or effective protection devices (SCP>): Starters related to overload protection devices that are integrated with separate short-circuit protection devices and/or separate short-circuit protection devices; According to the specified conditions, Contactors or starters combined with this standard: These electrical components, such as comprehensive starting energy (3.4.11C.9). The entire device is measured and used together with the main terminal of the sub-circuit, as well as the self-contained device (see 3.6.18? Combination, protection line may fall into the potential of overload,
This standard also applies to the operation of the contactor and its auxiliary equipment: This standard is used to change the starting motor and the common starter motor. The positive belt speed ensures the continuous operation of the motor, and the secondary motor power supply provides over-load protection for the motor and the commonly connected circuit. The motor starter is a motor starter with a thermal protection device that meets the requirements of GB/T 14556.15 and GB/T 3232. The motor starter does not need to meet the requirements of the standard and relevant requirements. Instructions for use
Different from [EC604 core, control network conditions, step voltage 3-kV and above but not exceeding 12V-rate below 5H General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China 2001-11-Approved 200206-01 Implementation
GR/T1480B—2001
The relay package of the actuator is within the scope of this standard: This standard is not applicable to:
: Actuator based on circuit breaker motor; ||tt| |Multi-version contactor: single-stage electric starter: ice and used in the starting value of the stomach business or graded self-reducing jade tester: asymmetric variable soft starter, that is, a device that has a load of different power and can start and adjust the speed; fluid starter and "liquid-lai" starter; semi-contactor contactor and starter using semiconductor contactor in the main station; fixed resistance stator starter:
special purpose contactor or crown contactor:
This standard does not involve the components installed in the contactor starter because they have self-draft technical requirements. Note
1 Thermoelectric rectifier should meet GD/T1528.
! The high-voltage limit switch should meet GB...6.2
pre-voltage reverse 3,6V to not exceed 10.5V when using the US and control equipment is E,: the two high-voltage switches and micro-quality switches are (let 1. Rated voltage T3.6kV and above does not exceed 72.kV high-load switch sequence meets B33C4, the purpose of this standard is to specify
a) contactors, starting tickets and related equipment characteristics; L) press the activator. The starter should comply with all relevant conditions; requirements and characteristics:
" absolute performance!
When applicable, the protection level of the external gram
joint starter;
a comprehensive starter, the interaction between various components, examples and SCPD matching:! To ensure that these conditions are sufficient, the test supervision, and the light The method adopted by the Shantou test institute:) The random 2 pieces or the manufacturer's text should show other information, 1.2 The following standard contains the clauses, which constitute the text of this standard through reference in this international standard. This standard is published, and the versions shown are valid. All standard departments have been ordered by you. The components using this standard can discuss the possibility of using the following standard to measure the latest version. 91.19 Change Part 2: Temperature rise (1E076-2.1993GB9R1-139 AC circuit breaker (EC6005617G1S85%! AC product pressure from the United States and the United States (mgC60129.198) GB/2.2-_994 Electrical terminology high-voltage equipment nTEC00041:: 19H14-1-full load 665-9
3-35 flow
5/4eb.2—95 terminal modification symbol EC617.154>GB643-19T type transformer (eF: 1982) G1102—999 common installation technology requirements for pressure switch equipment and control equipment standards 41E6064996GB-2321991 motor installation type thermal insulation expansion device health specification (eaTEC: (34-113: 194) adopts the same standard. GH7T14808—2001
[31404%. 1993 low T switch section equipment and control equipment light control circuit electrical appliances and switch elements Part 1 upgrade: machine type control circuit electrical appliances (e41565947-5 -1:1990)8-Wire electric heating relay: 0)
GB/115166.11994 AC high-voltage circuit breaker technical terms (nenFC60050:441):.984)G566.2-17 AC commercial voltage baking device current limiting fuse (e1E core 69232-1:1385) inductive load opening and closing
C6233:1931 High AC current limiting circuit breaker
1正:68121:006 2. 1. Normal and special use conditions of commercial time-limited devices
2.1 Normal use conditions
Part 1: Requirements and test methods
GB 11022-1S99 2.1 is suitable for the following static collection, when used outdoors, refer to 8.:V2.6.
2.2 2.2 of GR/T11C221993 applies, with the following modifications 2.2.1 Hella dials are divided into two levels ≥CCCm and 3UuU, see 8.102. Juice: This ratio is necessary for all types of operating parts. 3 Suggestions
Chapter 3 of GB 112221999 applies, with the following additions. 3.1 General terms
3.1.10: Control equipment
Originally refers to switches and other control, measuring, protection and regulation equipment used to control electrical equipment, and the combination of these switches and related electrical connections, enclosures and supporting components. 3.1.102 Overcurrent
Current exceeding the rated current. 16B/T2.2-1994 2.83.1.103 Short-circuit current
The short circuit current caused by faulty load or switching in the electrical circuit 4. [B/12900.20-1994 2.9] 3.1.104 Overload
Overcurrent or overcurrent. [B/T25, 2-1994 2.13.1.1057 Electrical components
Can be clean but not necessarily can bear the current, [GB/T2900.2℃·1934 2.19] 3.1.106 Solid state air temperature
Control provisions of the meter to measure the ambient air of the entire switchgear (for enclosed switchgear, it is the average temperature of the external air>. IGB 2U0.2(s54 2.39
3.2 Switchgear microcontroller assembly
Special definitions.
3.3 Assembly components
No other definitions.
3.4 ​​Switching device
3.4.107 Switching device
A device used to close or open the current in one or more circuits. 3.4.102 Switchgear
GB/T14808—2001
A device that can be separated to close or open one or more circuits. Switch installation: The medium where the switch is located does not distinguish between air and oil. 3.4.103 The two switches
in the open position, there is a good insulation distance between the contacts that meets the requirements of the platform and an obvious new opening mark: in the closed position, it can carry the current under normal circuit conditions (such as rough circuit) within a specified time. According to GBT2900.20 994 5.24. Modify the selling
of the car: "the return port is small" or the distance between the two contacts of the normal switch is small. When the display changes before and after closing and opening, the switch is used to connect the return switch to the ground. Under the condition of the circuit breaker (such as short circuit), the abnormal current is required to be carried in the timing or period; under the condition of the circuit breaker, the current is required to be carried: [according to / T.20-1554 3.28: static discharge Note: the ability of the switch to close the switch, 3.4.105 contactor (mechanical)
manual operation, only one rest The machine should be equipped with a machine that can close, carry and break the overload current specified in the normal current position: [According to GB/2900.20199 3-32 modified notes
1 with the ability to break,
2 close the normally open main head or disconnect the normally idle main head quickly, Www.bzxZ.net
3.4.106 Magnetic contactor
The power of the normally open main head or the normally idle main head is provided by the electric contact. 3.4.107 The main contactor is more reliable in high-pressure air. 3. 4.10 The main fuse is in the closed position and the fuse is closed. 3.4.109 Locking device
When the operating mechanism is powered off, the lock is equipped with a lock to prevent the moving element from returning to the stop position. The material of the quick release and lock can be mechanical, electric, pneumatic, etc. 3.4.110 Starting
When the overload protection element is closed, all the components required for starting and stopping the motor are combined. CB/T25e0.2V-9a 5
: The motor can be controlled by a type of head and the knife is also provided. 3.4.110. Ear connection starter
Connect the line power directly to the starter on the electric Kai connection terminal. /12900.2C-1994 3.363.4.110.2 Reverse starter
A starter that can reverse the motor by controlling the reverse current when the motor is running, 3.4.1.0.3 Double starter
A starter that reverses the motor by connecting the motor only when the motor is not running. 3.4.110.4 Reduced voltage starter
A starter that reduces the starting voltage of the motor. Note: The positive starter is active and considers the characteristics of the pressure reduction: reactance drive belt: and variable resistance drive. 3.4.110.5 Reduced positive starter
From a small group of independent variables to obtain a reduced voltage for starting the electric starter 3.4.710.6 Variable resistance starter
One or more effective resistors to obtain the electric or motor when the start is about the torque and current limiting starter, H/14808-2001
Let: It is usually even composed of this part of the world cloud part of the product to provide a combination, can provide the use of the point of note! Stator power supply state of the machine storage and the United States loan device! The general energy loan has a social awareness of the device. 2 The three-way power group of the nuclear person and the rotor must be connected in series with the stator system of the fan electronic to increase the voltage of the starter 3.4.110.9 (through the starter) to increase the voltage of the starter 3.4.110.9. The normal sequence is to control the light contact energy, overload protection, external operation of the service provider and the circuit protection device, and the equipment is installed in a special casing. The entire casing should be specially designed and used. All parts of the new device should be designed in a special way. It can also contain grounding power. It can also be used in other occasions besides motors. 3.4.110.10 Electromagnetic starter
The closed earth contacts are electromagnetic starters. 3.4.110.11\ Class starters
There are several intermediate positions between the full and full positions. Note
and the blood position is changed to the medium speed position. If the starter is a throw starter (see, 1.11, 2 gradually rising and connecting the oil vertically, there is an intermediate position E plus the starting position according to the necessary first-class stop. 3 Three-resistance starters, both of which are electrically connected,
3.4.70.12 Short-circuit protection devices and 5C.1
Ensure that the circuit or circuit components are protected from damage and light damage by breaking the circuit current: 3.5 Opening and digging parts
3.5.101: Switch this pole)
Only the ten circuits that are electrically separated from the electrical paths are used, and all the accessories are not included when they are installed and operated together [6B12300, 20994 2.25
Note: If a switch device has only one, it is called a single pole. If it is under the same circumstances, only these excitation accessories are included! It is called a multi-transmission "etc.)
3.5.102 (closing equipment) Feng circuit
includes all conductive parts of the element circuit that transmits 4 energy: G2/12900.2-994 2.2-3.5.103 (lifting equipment) pad circuit
also includes all 5 parts of the control closing and opening operation circuit. "G1/2600.201932 2.25] 3.5.104 (Switch device) The auxiliary circuit is included in all conductive parts of the different circuits other than the switch circuit and the control circuit: "GB/2S214 2. 27
Juice: This circuit is used for additional requirements, with the provisions of the provisions, these national solutions can also be used for other parts of the system. 3.5.105 The contacts in the circuit can be closed by hand when in the same position. "GL/T2923.201994 4.43.5.106 The contacts are connected in the control circuit of the switch and are closed by mechanical means. GB/T3)2U14 4.5 3.5.107 Auxiliary power contact
CB/T14808-201
Connected to the auxiliary switch of the switch 1 mountain The lifting switch is operated by mechanical resistance: 1GB/T2909.201H1 4.7 3.5.108 Closing contact Normally flat contact 2! Service contact
When the switch contacts are closed and the contacts are open, the flash control melting contact or push-pull follow-up contact is disconnected. G\2CC, 20--1 4.8
3.5.109 Break [normally closed contact] contact
When the switch contacts are closed and the contacts are open, the control contact or auxiliary contact is disconnected. 1/T2900.20-14.9!
3.6 Operation
3.6101 Operation
Move from one position to another position, "GK/1290n.20-1554 5.1
For the trip device, this can be selected or operated. 2 Adding considerations is necessary, then the meaning of the part can be explained in terms of electrical equipment, so as to understand the same strategy, and then in terms of the meaning of the navigation point. 3.6.102 Operation
Change from one position to another and then return to the initial position. If there are multiple positions, you need to go through all the other positions. [12900.21S94 3.3]
: It can be used to analyze the common production methods that are needed and the slow production cycle that are not suitable: the special production methods are listed incorrectly. 3.6.103 Closing (change operation
The switch is transferred from the open position to the open position, [GB/12160.20-1904 3.3! 3.6.104 Operation (gate)
The switch is transferred from the closed position to the open position, GB/2900.2-:991 2! 3.6.105 Closing (switching position)
Ensure the continuity of the switch circuit (through 9 positions. G/2933.20-1J4 323.6.106 Open (alarm position (lower closing device) The main direction of the quick closing device is only in the specified (middle air magic position [(13/3900,201994 3. a5
3.6.10/ Stop position (contactor:
When the contactor's circuit is not energized or the compressor is not working properly, the position of the moving parts of the contactor K/1 2900.20-1!4 5.34
3.6.108 Overheating relay or release
Overcurrent relay or release used for overcurrent protection (closed, including transformer and internal connection). 3.6109 Thermal (overload) relay or release uses the reverse action (including delay) of the thermal effect generated by the current through the overcurrent release:
3.6.110 (overcurrent or overcurrent cut-off relay) setting value of the overcurrent release The action current value adjusted by the British release is also in accordance with its specified operating conditions: 3.6.111 (over-current relay or tripping) The current setting range refers to the setting current or minimum value and the maximum value. The current setting value of the output device or tripping device can be adjusted within this range. 3.6.112 Phase-failure overload release device or tripping device
According to the specified requirements, when the mountain cannot be filled with rated current, the current value is low and the gate is operated when the current is sufficient. For the over-current relay or tripping device, 3.6.113 Point battery undervoltage> Relay tripping-device E