Machinery Industry Standard of the People's Republic of China
JB/T7435-94
CJX Series AC Contactor
Published on September 6, 1994
Ministry of Machinery Industry of the People's Republic of China
Implemented on July 1, 1995
Subject Content and Scope of Application
Cited Standards
Terms, Symbols, Codes
Structural Type, Classification, Basic Parameters and Dimensional Technical Requirements
Test Methods|| tt||Inspection rules.
Marking, packaging, transportation and storage
Appendix A Interlocking contactor (supplement)
CR.OC.OC.OOC..O..
Mechanical industry standard of the People's Republic of China
CJX series AC contactor
JB/T7435-94
This standard adopts IEC947-4-1 (1990) "Low-voltage switchgear and control equipment Part 4 Contactor and motor starter".
1 Subject content and scope of application
This standard specifies the common types, parameters, technical requirements, test methods and inspection rules of CJX series AC contactors. This standard applies to CJX series AC contactors (hereinafter referred to as contactors). The contactor is mainly used in circuits with AC 50Hz (or 60Hz), rated working voltage up to 660V, and rated working current up to 170A when the rated working voltage is 380V under AC-3 use category, for remote connection and disconnection of circuits, and can be combined with appropriate thermal overload relays to form electromagnetic starters to protect circuits that may be overloaded.
1.1 This standard applies to the following basic varieties and specifications of AC contactors: a.
CJX1 series AC contactors;
CJX2 series AC contactors;
CJX3 series AC contactors;
CJX4 series AC contactors;
CJX5 series AC contactors
Other varieties and specifications of the above series can be formulated by the manufacturer to meet the general requirements of this standard. Enterprise standards. 1.2 The basic requirements for the combination of contactor and functional module (functional electrical appliance) and interlocking contactor composed of two contactors are proposed in the form of supplementary parts, which are used together with this standard. 2
Referenced standards
GB2828
GB2900.18
GB5226
GB14048.4
GB14048.5
GB/T13384
GB/T14048.1
JB3284
Basic test methods for low voltage electrical appliances
Basic test methods for electrical and electronic products Environmental test procedures Basic environmental test procedures for electrical and electronic products Batch inspection Count sampling procedures and sampling tables Electrical terminology Low voltage electrical appliances
Low voltage electrical appliances enclosure protection level
Test A: Low temperature test method
Test Db: Alternating damp heat test method
Fire hazard test for electrical and electronic products
Glow wire test method and guidelines
General technical conditions for machine tool electrical equipment
Low voltage switchgear and control equipment Low voltage electromechanical contactors and motor starters Low voltage switchgear and control equipment
Circuit electrical appliances
General technical conditions for packaging of electromechanical products
Control circuit electrical appliances and switching elements Part 1 Electromechanical control
General rules for low voltage switchgear and control equipment
Basic environmental conditions and test methods for transportation, transportation and storage of motors and electrical products Approved by the Ministry of Machinery Industry on September 6, 1994
1995-07-01 implementation
Terms, symbols, codes
JB/T7435-94
The terms, symbols, codes used in this standard comply with the relevant provisions of Chapter 3 of GB2900.18 and GB14048.4. 4 Structural type, classification, basic parameters and dimensions Structural type
4.1.1 The contactor is open type, the contact is double breakpoint, and the action mechanism is direct-acting. 4.1.2 Number of contacts
a. Main contacts
The contactor has 3 pairs of normally open main contacts;
b. Auxiliary contacts
The contactor has a maximum of 4 pairs of normally open and 4 pairs of normally closed auxiliary contacts. 4.2 Model and meaning
Structural modification code
Z indicates DC operation
Derived code: if there is N, it indicates the number and combination of auxiliary contacts of interlock contactor
Rated working current (A) when the rated working voltage is 380V under AC-3 use category
Design serial number
-Small
AC contactor
4.3 Classification
According to the presence or absence of arc extinguishing cover
Without arc extinguishing cover:
With arc extinguishing cover.
According to the type of control circuit power supply
AC operation;
DC operation.
Basic parameters
Rated voltage
The rated insulation voltage of the contactor is 660V;
The rated working voltage of the contactor is up to 660V. Rated current and control power
Contactor agreed heating current It, rated operating current I under AC-3 use category. And the maximum power P of controllable three-phase squirrel cage motor are shown in Table 1, Table 2 and Table 3.
Contactor model
CJX1-9
CJX3-9
CJX1-12
CJX3-12
CJX1-16
CJX3-16
CJX1-22
CJX3-22
CJX1-32
CJX3-32
CJX1-38
CJX3-38
CJX1-45
CJX3-45
CJX1-63
CJX3-63
CJX1-75
CJX3-75||tt| |CJX1 -85
CJX3-85
CJX1-110
CJX3-110bzxZ.net
CJX1-140
CJX3-140
CJX1-170
CJX3-170
Contactor model
CJX2-9
CJX4-9
CJX2-12
CJX4-12
Conventional thermal current
Conventional thermal current
JB/T7435-94
Rated working current 1,
Rated working current 1,
Maximum power P of controllable three-phase squirrel cage motor. kw
Maximum power P of controllable three-phase squirrel cage motor, kw
Contactor model
CJX2-16
CJX4-16
CJX2-25
CJX4-25
CJX2-32
CJX4-32
CJX2-40
CJX4-40
CJX2-50
CJX4-50
CJX2-63
CJX4-63
CJX2-80
CJX4-80
CJX2-95||tt| |CJX4-95
Contactor model
CJX5-9
CJX5-12
CJX5-16
CJX5-22
CJX5-30
CJX5-40
CJX5-50
CJX5-62
CJX5-85
CJX5-105
CJX5-120
CJX5-150
Conventional thermal current
Conventional thermal current
JB/T743594
Continued Table 2
Rated operating current 1.
Rated operating current 1.
Maximum power P of controllable three-phase squirrel cage motor, kw
Maximum power P of controllable three-phase squirrel cage motor. kw
Use category
Main circuit use category
JB/T 743594
The use category of the contactor main circuit is mainly AC3, and the control capacity can also be appropriately reduced for AC-4 use category; b.
Use category of auxiliary circuit
The use category of auxiliary circuit is AC-15 or DC-13. 4. 4. 4
Rated working system
Eight-hour working system;
Intermittent cycle working system (or intermittent working system); uninterrupted working system
The rated operating rate and load factor of contactor under intermittent cycle working system are shown in Table 4. Table 4
Contactor model
CJX-9~25
CJX-30~140
CJX-150~170
CJX-9~170
Control circuit
Use category
Rated control power supply voltage U of the contactor is: a.
AC: 36, 110, 220, 380V;
DC: 24, 110, 220V
Auxiliary circuit
4. 4. 7. 1
4. 4. 7. 2
Rated voltage
Rated insulation voltage U of auxiliary contact: 660V: Rated operating rate h-1
Rated working voltage U of auxiliary contact. AC380V and DC220V. Rated current
The conventional heating current of the auxiliary contact is 10A; the rated working current of the auxiliary contact under different rated working voltages is shown in Table 5. Table 5
Use category
Overall dimensions and installation dimensions
3600VA
Overall dimensions and installation dimensions shall comply with the provisions of Figures 1 to 8 and Tables 6 to 9. Load factor
Rated working current IA
JB/T7435--94
Figure 1CJX1-9~22, CJX3-9~22 type AC contactor appearance and installation dimensionsFigure 2CJX1-32~170, CJX3-32~
~170 type AC contactor appearance and installation dimensionsFigure 3CJX2-9~32, CJX4-9~32 type AC contactor appearance and installation dimensionsFigure 4CJX2-40~95, CJX4-40~95 type AC contactor appearance and installation dimensionsFlesh
Figure 5CJX 5-9-
JB/T 7435 94
~16 type AC contactor size and installation size Figure 6CJX5-22~40 type AC contactor size and installation size Figure 7CJX5-50~105 type AC contactor size and installation size 8
CJX1-9, 12
CJX3-9, 12
CJX1-16.22
CJX3-16.22
CJX1-32.38
CJX3-32.38
CJX1-45.63
CJX3-45.63
CJX1-75, 85
CJX3-75.85| |tt||CJX1.110, 140
CJX3-110.140
CJX1-170
CJX3-170
Type of control power supply
JB/T743594
CJX5-120, 150 type AC contactor overall dimensions and installation dimensions Table 6
Auxiliary contact combination
CJX1-9, 12
CJX3-9.12
CJX1-16.22
CJX3-16.22
CJX3-32.38
CJX1-32, 38
60± 0. 60
See table?
100±0.70
110±0.70
100±0.70
110±0.70
130±0.80
160±0.80
4. 8 +0.48
5. 5 +n. 48
Contactor model
CJX2-9, 12
CJX4-9, 12
CJX2-16
CJX4-16
CJX2-25
CJX4-25
CJX2-32
CJX4-32
CJX2-40~63
CJX4-40~63
CJX2-80.95
CJX4-80, 95
JB/T 7435-94
82(116)
87(122)
96(131)
101(138)
116(172)
127(183)
Note: The data in brackets are for DC operated contactors. Type
CJX5-9, 12
CJX5-16
CJX5-22
CJX5-30, 40
CJX5-50.62
CJX5-85, 105
CJX5-120
CJX5-150
68(76)
90(92)
108(112)
126(136)
Note: The data in brackets are for DC-operated contactors. Technical requirements
5.1 Normal working conditions and installation conditions
1 Normal working conditions
1 Ambient air temperature
5. 1. 1. 1
(40±0.50/50±0.50)
80(114)
98(126)
104(132)
108(135)
129(160)
138(164)
147(172)
50±0.50/60±0.60
50±0.50/60±0.60
100±0.70/110±0.70
100±0.70
The upper limit of ambient air temperature is +40°C, and its average value within 24 hours shall not exceed +35°C; the lower limit of ambient air temperature is
-5°C.
2Altitude
5.1. 1. 2
The altitude of the installation site shall not exceed 2000m.
5. 1. 1. 3
Atmospheric conditions
(60±0.60)
110±0.70
125±0.80
125±0.80
4 5+0. 48
4: 5 +0.48Figure 3: Dimensions and installation dimensions of CJX2-9~32, CJX4-9~32 type AC contactors Figure 4: Dimensions and installation dimensions of CJX2-40~95, CJX4-40~95 type AC contactors Figure 5: Dimensions and installation dimensions of CJX5-9-
JB/T 7435 94
~16 type AC contactor size and installation size Figure 6CJX5-22~40 type AC contactor size and installation size Figure 7CJX5-50~105 type AC contactor size and installation size 8
CJX1-9, 12
CJX3-9, 12
CJX1-16.22
CJX3-16.22
CJX1-32.38
CJX3-32.38
CJX1-45.63
CJX3-45.63
CJX1-75, 85
CJX3-75.85| |tt||CJX1.110, 140
CJX3-110.140
CJX1-170
CJX3-170
Type of control power supply
JB/T743594
CJX5-120, 150 type AC contactor overall dimensions and installation dimensions Table 6
Auxiliary contact combination
CJX1-9, 12
CJX3-9.12
CJX1-16.22
CJX3-16.22
CJX3-32.38
CJX1-32, 38
60± 0. 60
See table?
100±0.70
110±0.70
100±0.70
110±0.70
130±0.80
160±0.80
4. 8 +0.48
5. 5 +n. 48
Contactor model
CJX2-9, 12
CJX4-9, 12
CJX2-16
CJX4-16
CJX2-25
CJX4-25
CJX2-32
CJX4-32
CJX2-40~63
CJX4-40~63
CJX2-80.95
CJX4-80, 95
JB/T 7435-94
82(116)
87(122)
96(131)
101(138)
116(172)
127(183)
Note: The data in brackets are for DC operated contactors. Type
CJX5-9, 12
CJX5-16
CJX5-22
CJX5-30, 40
CJX5-50.62
CJX5-85, 105
CJX5-120
CJX5-150
68(76)
90(92)
108(112)
126(136)
Note: The data in brackets are for DC-operated contactors. Technical requirements
5.1 Normal working conditions and installation conditions
1 Normal working conditions
1 Ambient air temperature
5. 1. 1. 1
(40±0.50/50±0.50)
80(114)
98(126)
104(132)
108(135)
129(160)
138(164)
147(172)
50±0.50/60±0.60
50±0.50/60±0.60
100±0.70/110±0.70
100±0.70
The upper limit of ambient air temperature is +40°C, and its average value within 24 hours shall not exceed +35°C; the lower limit of ambient air temperature is
-5°C.
2Altitude
5.1. 1. 2
The altitude of the installation site shall not exceed 2000m.
5. 1. 1. 3
Atmospheric conditions
(60±0.60)
110±0.70
125±0.80
125±0.80
4 5+0. 48
4: 5 +0.48Figure 3: Dimensions and installation dimensions of CJX2-9~32, CJX4-9~32 type AC contactors Figure 4: Dimensions and installation dimensions of CJX2-40~95, CJX4-40~95 type AC contactors Figure 5: Dimensions and installation dimensions of CJX5-9-
JB/T 7435 94
~16 type AC contactor dimensions and installation dimensions Figure 6CJX5-22~40 type AC contactor dimensions and installation dimensions Figure 7CJX5-50~105 type AC contactor dimensions and installation dimensions 8
CJX1-9, 12
CJX3-9, 12
CJX1-16.22
CJX3-16.22
CJX1-32.38
CJX3-32.38
CJX1-45.63
CJX3-45.63
CJX1-75, 85
CJX3-75.85| |tt||CJX1.110, 140
CJX3-110.140
CJX1-170
CJX3-170
Type of control power supply
JB/T743594
CJX5-120, 150 type AC contactor overall dimensions and installation dimensions Table 6
Auxiliary contact combination
CJX1-9, 12
CJX3-9.12
CJX1-16.22
CJX3-16.22
CJX3-32.38
CJX1-32, 38
60± 0. 60
See table?
100±0.70
110±0.70
100±0.70
110±0.70
130±0.80
160±0.80
4. 8 +0.48
5. 5 +n. 48
Contactor model
CJX2-9, 12
CJX4-9, 12
CJX2-16
CJX4-16
CJX2-25
CJX4-25
CJX2-32
CJX4-32
CJX2-40~63
CJX4-40~63
CJX2-80.95
CJX4-80, 95
JB/T 7435-94
82(116)
87(122)
96(131)
101(138)
116(172)
127(183)
Note: The data in brackets are for DC operated contactors. Type
CJX5-9, 12
CJX5-16
CJX5-22
CJX5-30, 40
CJX5-50.62
CJX5-85, 105
CJX5-120
CJX5-150
68(76)
90(92)
108(112)
126(136)
Note: The data in brackets are for DC-operated contactors. Technical requirements
5.1 Normal working conditions and installation conditions
1 Normal working conditions
1 Ambient air temperature
5. 1. 1. 1
(40±0.50/50±0.50)
80(114)
98(126)
104(132)
108(135)
129(160)
138(164)
147(172)
50±0.50/60±0.60
50±0.50/60±0.60
100±0.70/110±0.70
100±0.70
The upper limit of ambient air temperature is +40°C, and its average value within 24 hours shall not exceed +35°C; the lower limit of ambient air temperature is
-5°C.
2Altitude
5.1. 1. 2
The altitude of the installation site shall not exceed 2000m.
5. 1. 1. 3
Atmospheric conditions
(60±0.60)
110±0.70
125±0.80
125±0.80
4 5+0. 48
4: 5 +0.481 Normal working conditions and installation conditions
1 Normal working conditions
1 Surrounding air temperature
5. 1. 1. 1
(40±0.50/50±0.50)
80(114)
98(126)
104(132)
108(135)
129(160)
138(164)
147(172)
50±0.50/60±0.60
50±0.50/60±0.60
100±0.70/110±0.70
100±0.70
The upper limit of ambient air temperature is +40°C, and its average value within 24 hours shall not exceed +35°C; the lower limit of ambient air temperature is
-5°C.
2Altitude
5.1. 1. 2
The altitude of the installation site shall not exceed 2000m.
5. 1. 1. 3
Atmospheric conditions
(60±0.60)
110±0.70
125±0.80
125±0.80
4 5+0. 48
4: 5 +0.481 Normal working conditions and installation conditions
1 Normal working conditions
1 Surrounding air temperature
5. 1. 1. 1
(40±0.50/50±0.50)
80(114)
98(126)
104(132)
108(135)
129(160)
138(164)
147(172)
50±0.50/60±0.60
50±0.50/60±0.60
100±0.70/110±0.70
100±0.70
The upper limit of ambient air temperature is +40°C, and its average value within 24 hours shall not exceed +35°C; the lower limit of ambient air temperature is
-5°C.
2Altitude
5.1. 1. 2
The altitude of the installation site shall not exceed 2000m.
5. 1. 1. 3
Atmospheric conditions
(60±0.60)
110±0.70
125±0.80
125±0.80
4 5+0. 48
4: 5 +0.48
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.