This standard replaces JB 1376-74 and JB 3772-84. This standard specifies the types and basic parameters of steam-type lithium bromide absorption chillers. This standard is applicable to single-effect and double-effect lithium bromide absorption chillers (hereinafter referred to as "units" or "single-effect units", "double-effect units") that use saturated water vapor as heat source, lithium bromide aqueous solution as absorbent, and water as refrigerant to produce cold water for air conditioning or production processes. JB/T 5443-1991 Types and basic parameters of steam-type lithium bromide absorption chillers JB/T5443-1991 Standard download decompression password: www.bzxz.net
Some standard content:
Machinery Industry Standard of the People's Republic of China JB/T5443—91 Steam-type lithium bromide absorption chiller Types and basic parameters Issued on July 22, 1991 Issued by the Ministry of Machinery and Electronics Industry of the People's Republic of China Implementation on July 1, 1992 Mechanical Industry Standard of the People's Republic of China Steam-type lithium bromide absorption chiller Types and basic parameters Subject content and scope of application JB/T5443—91 Replaces JB137674 JB3772—84 This standard specifies the types and basic parameters of steam-type lithium bromide absorption chillers. This standard applies to single-effect and double-effect lithium bromide absorption chillers (hereinafter referred to as "units" or "single-effect units" and "double-effect units") that use saturated water vapor as a heat source, lithium bromide aqueous solution as an absorbent, and water as a refrigerant to produce cold water for air conditioning or production processes. 2 Reference standards ZBJ73025 3 Type Refrigerator model compilation method The unit is divided into single-effect and double-effect types. The single-effect unit uses 0.1MPa (gauge pressure, the same below) saturated water vapor as a heat source to produce 7C cold water. 3.1.1 The double-effect unit uses the following four different pressures of saturated water vapor as a heat source to produce cold water of different temperatures. That is: for a 0.8MPa unit, the cold water outlet temperature is 7°C; for a 0.6MPa unit, the cold water outlet temperature is 7 or 10°C; for a 0.4MPa unit, the cold water outlet temperature is 7 or 10°C; for a 0.25MPa unit, the cold water outlet temperature is 13°C. d. 3.2 The compilation method of the unit model shall comply with the following provisions in addition to the provisions of ZBJ73025: Port Remodel number: indicated by Latin letters A, B... in sequence, the first design is omitted Cold water outlet temperature: 7℃ is indicated by D, 10℃ is indicated by Z, 13℃ is indicated by G; single-effect type is not indicated Nominal cooling capacity (×10kW) Heating saturated water vapor pressure (×10-\MPa), single-effect type is not indicatedType: single-effect type is indicated by XZ; double-effect type is indicated by SXZApproved by the Ministry of Machinery and Electronics Industry on July 22, 1991 and implemented on July 1, 1992 3.3 Model example JB/T5443-—91 Cooling capacity 1150W Steam single-effect lithium bromide absorption chiller: XZ-115 Cooling capacity 1750kW, the first modified steam single-effect lithium bromide absorption chiller: b. XZ-175A Cooling capacity 1150kW, heating saturated steam pressure 0.6MPa, cold water outlet temperature 10C steam double-effect lithium bromide absorption chiller c.bzxz.net Chiller: SXZ6-115Z Cooling capacity 1750kW, heating saturated steam pressure 0.4MPa, cold water outlet temperature 7C, the second modified steam double-effect lithium bromide absorption chiller d. SXZ4-175DB Basic parameters The basic parameters of the single-effect unit should comply with the provisions of Table! Table 1 Nominal cooling capacity Cold water outlet Inlet temperature Cold water inlet and outlet Inlet temperature difference Cooling water Inlet temperature Unit cooling capacity Cooling water consumption Saturated steam Gauge pressure Unit cooling capacity Steam consumption JB/T5443-91 4.2 The basic parameters of the double-effect unit with 0.8MPa saturated steam as the heat source shall comply with the provisions of Table 2. Table 2 Nominal cooling capacity Cold water outlet Inlet temperature Cold water inlet and outlet Inlet temperature difference Cold water Inlet temperature Unit cooling capacity Cooling water consumption 4.3 The basic parameters of the double-effect unit with 0.6MPa saturated steam as heat source shall comply with the provisions of Table 3. 4.4 The basic parameters of the double-effect unit with 0.4MPa saturated steam as heat source shall comply with the provisions of Table 4. Saturated steam Gauge pressure Unit cooling capacity Steam consumption Nominal cooling capacity Cold water outlet Temperature difference between cold water inlet and outlet Cooling water Inlet temperature Unit cooling capacity Cooling water consumption Saturated steam Gauge pressure Unit cooling capacity Steam consumption When the cold water outlet temperature is 7℃, When the cold water outlet temperature is 10℃, Nominal cooling capacity Cold water outlet Temperature difference between cold water inlet and outlet JB/T 544391 Cold water inlet and outlet Temperature difference Cooling water Inlet temperature Unit cooling capacity Cooling water consumption Cold water outlet temperature When 7℃, Cold water outlet temperature When 10℃, Saturated steam Gage pressure Unit cooling capacity Steam consumption Cold water outlet temperature When 7℃, Cold water outlet temperature When 10℃, JB/T5443—91 5The basic parameters of the double-effect unit with 0.25MPa saturated steam as the heat source shall comply with the provisions of Table 5. 4.5 Nominal cooling capacity Additional notes: Cold water outlet Temperature difference between cold water inlet and outlet Cooling water Inlet temperature This standard is proposed and managed by the Hefei General Machinery Research Institute of the Ministry of Machinery and Electronics Industry. This standard was drafted by the Hefei General Machinery Research Institute of the Ministry of Machinery and Electronics Industry, and the main drafter of this standard is Wang Dekui. Unit cooling capacity Cooling water consumption Saturated steam Gauge pressure Unit cooling capacity Steam consumption People's Republic of China Mechanical industry standard Steam type lithium bromide absorption chiller Type and basic parameters JB/T5443-91 Published and issued by the Mechanical Standardization Research Institute of the Ministry of Machinery and Electronics Industry (Beijing 8144 Xin Box Postal code 100081) Copyright reserved. No reproduction allowed Printed by Hebei Qinghe Printing Factory Format 880×1230 First edition in October 1991 Printing sheet 5/8 Word count 12000 First printing in October 1991 Print run 00.001-1000 Price 1.00 yuan No. 0257 Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.