This standard storage tank is suitable for storing volatile petroleum, petroleum products and chemical products. HG 21502.2-1992 Steel Vertical Cylindrical Internal Floating Roof Storage Tank Series HG21502.2-1992 Standard download decompression password: www.bzxz.net
Some standard content:
Industry Standard of the People's Republic of China Steel Vertical Cylindrical Internal Floating Roof Storage Tank Series HG 21502. 2-92 Editor: The Sixth Design Institute of the Ministry of Chemical Industry Approval Department: Ministry of Chemical Industry Engineering Construction Standard Editing Center of the Ministry of Chemical Industry 1992 Beijing Specifications to be followed in design and manufacturing SH3046-92 "Design Specifications for Vertical Circular Simple Steel Welded Storage Tanks"; GBI128-90 "Construction and Acceptance Specifications for Vertical Cylindrical Steel Welded Oil Tanks"; GBI236-82 "Construction and Acceptance Specifications for Field Equipment and Industrial Pipeline Welding Projects"; SHJ26-90. "Standard for Seismic Assessment of Atmospheric Pressure Vertical Storage Tanks". 33 General Provisions Applicable Scope This standard storage tank is suitable for storing volatile petroleum, petroleum products and chemical products. Working Conditions Pressure: okPa; Temperature: +80℃. Storage Liquid Density: 01000kg/m2 Structural Type This standard storage tank is a steel vertical circular simple internal floating storage tank. 2.3 Specifications and Dimensions Nominal Volume: 100m2~30000m2; Nominal Diameter: DN4500mm~DN44000mm. Design pressure: Design temperature: Corrosion margin: Design load Design temperature -1980℃ Basic wind pressure: 0.5kPa. Snow load: 0.45kPa. Additional load on tank item: Seismic fortification intensity: 7 degrees. 2.4.5 Material selection The material selection should be based on the lowest daily average temperature of the tank construction area plus 13℃ to determine the tank wall material (Q235-AF: Q235-A20R: 16Mn16MnR). The specific selection principle is based on Table 2.4.5. Q235-A Application range of steel plate GB3274 GB6654 GB1591 GB3274 GB6654 Application range Metal allowable Minimum temperature Maximum allowable Thickness Mechanical properties Inspection items ObvOs,os ObDgvOg AkyCold bending OnOs,05 OhCsos AkvCold bending Note: ①16MnR steel plate with thickness greater than 30mm should be delivered in normalized state. Note ② 20R with a thickness greater than 30mm and 16MnR with a thickness greater than 30mm shall be subjected to ultrasonic flaw detection one by one to meet the requirements of ZBI74003-88 "Ultrasonic flaw detection of pressure vessel steel plates" and comply with the grade requirements of "Ultrasonic flaw detection of pressure vessel steel plates". 36 2.4.6 Allowable stress The allowable stress of steel plates shall be based on Table 2.4.6. Allowable stress value of steel plate Q235-A 6~16 17~25 Strength index at room temperature (MPa)/o, (MPa) Allowable stress at the following temperature (℃) (MPa) Atmospheric temperature The number, specifications and uses of the nozzles set in this standard are recommended and can be changed according to process requirements and indicated in the selection table. The specifications of the tank pipe and the pipe extension length are shown in Figure 2.5 and Table 2.5.37 Figure 2.5 Schematic diagram of storage misconnection Storage pipe length dimension table Pipe specifications Φ18×3 Φ32×5 @45×5 @57×5 $89×6 Weight108×6 @159×7 Φ219×8 Φ273×9 @325X10 Φ377×11 Pipe extension length The pipe flange adopts a raised plate type flat welding flange with a nominal pressure of PN0.6MPa. The flange standard is HGI44-91 (except for the instrument interface). The foam fire fighting and water sprinkler system adopts a raised plate type flat welded steel pipe flange, with a nominal pressure of PN-1MPa, and the flange standard is GB9119.7-88. 2.7 Liquid level indication This standard storage tank is equipped with two sets of liquid level indication devices, one is a float type steel belt level gauge, and the other is a differential pressure level gauge. 2.8 Ladder, platform This standard stipulates that 100m2~300m2 storage tanks use straight ladders, and 400m2~30000m storage tanks use spiral ladders, with a spiral rise angle of 45°. 39 2.9.1 Foam fire fighting Fire fighting facilities This standard adopts foam fire fighting for storage tanks. Different numbers of air foam generators are set according to different volumes. 2.9.2 Fire sprinkler For storage tanks that need to be equipped with water sprinklers, this standard stipulates that storage tanks of 100m2 to 800m2 are only equipped with tank top sprinklers, and storage tanks of 1000m2 to 30000m2 are equipped with water sprinklers on the tank top and tank wall. See Table 2.9.2 for details.2.10 2.10.1 Floating plate structure Internal floating roof structure This standard adopts two structural types: shallow plate type and cabin type. Storage tanks with a nominal volume less than 10000m2 adopt shallow plate type, and storage tanks with a nominal volume equal to or greater than 10000m2 adopt cabin type. Sealing structure type This standard adopts two structural types: packing seal and tongue seal. Storage tanks with a nominal volume less than 10,000m2 use packing seals, and storage tanks with a nominal volume equal to and greater than 10,000m2 use tongue seals. For the rubber element of the sealing device, this standard recommends the use of nitrile rubber. In addition, fluororubber and glass cloth impregnated with polytetrafluoroethylene can also be used according to the storage medium, and it should be noted in the selection table. tank wall spray tank top spray feeding port, discharging port water inlet water inlet steel strip liquid 10m~30000m internal floating roof storage tank series pipe orifice specifications and uses air foam fire foam light hole, air hole, oil measuring hole level meter port ei/ez3 foam population| |tt||Tank top Wall manhole Pressure differential liquid Surface gauge port Pressure differential liquid Sewage outlet temperature gauge port Surface gauge port Standard serial number 21502.2-92-101www.bzxz.net 2-92-102 2-92-103 21502.2-92-104 21502. 2-92-105 21502.2-92-106 21502.2-92-107 21502. 2-92-108 | | tt | | 21502.2-92-109 | tt||21502.2-92-115 21502.2-92-116 .2-92-117 21502.2-92-118 2.2- 92-119 21502.2-92 21502:2-92-121 .2-92-126 21502.2-92 -2-92- 2-92-129 21502.2-92-130 21502.2-92- 2.10.3 Support height of internal floating roof The internal floating roof of this standard has two support heights: operation and maintenance. The operation height is 900mm and the maintenance height is 1800mm. 2.10.4 Guide mechanism (anti-rotation device) The guide device of the floating plate of this standard adopts a sliding guide device. 2.11. Wall reinforcement ring This standard stipulates that the tank with a nominal volume less than 1000m2 shall not be equipped with reinforcement ring, and the tank with a nominal volume equal to or greater than 1000m2 shall be equipped with reinforcement ring. Tank bottom plate structure This standard recommends that the tank bottom plate adopts two types of butt joint and overlap, and it shall be selected according to the actual situation of the foundation and indicated in the selection table. 2.13 Drainage outlet This standard recommends that the tank adopts two drainage structure types: tank bottom drainage and cleaning hole. And it shall be selected according to the characteristics of the storage medium and indicated in the selection table (drainage hole S1, cleaning hole Sz). Additional requirements 2.14.1 The fire sprinkler device set in this standard can be selected or modified according to the process requirements. 2.14.2 According to the characteristics of the storage medium, if there is a requirement for anti-corrosion treatment of the tank bottom plate, it can be proposed in the selection table and clarified. Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.