title>JB/T 10281-2001 Technical requirements for fire smoke exhaust fans - JB/T 10281-2001 - Chinese standardNet - bzxz.net
Home > JB > JB/T 10281-2001 Technical requirements for fire smoke exhaust fans
JB/T 10281-2001 Technical requirements for fire smoke exhaust fans

Basic Information

Standard ID: JB/T 10281-2001

Standard Name: Technical requirements for fire smoke exhaust fans

Chinese Name: 消防排烟通风机 技术条件

Standard category:Machinery Industry Standard (JB)

state:in force

Date of Release2001-06-04

Date of Implementation:2001-10-01

standard classification number

Standard ICS number:Fluid systems and general parts >> 23.120 Ventilators, fans, air conditioners

Standard Classification Number:Machinery>>General Machinery and Equipment>>J72 Compressor, Fan

associated standards

Publication information

publishing house:Mechanical Industry Press

Publication date:2004-04-23

other information

Focal point unit:National Technical Committee for Fan Standardization

Publishing department:National Technical Committee for Fan Standardization

Introduction to standards:

JB/T 10281-2001 This standard is based on the requirements for mechanical smoke exhaust in GB 50045-1995 "Code for Fire Protection Design of High-Rise Civil Buildings" and GB 50067-1997 "Code for Fire Protection Design of Garages, Repair Garages and Parking Lots". This standard specifies the definition, technical requirements, test methods, inspection rules, marking, packaging and transportation of fire smoke exhaust fans. This standard applies to mechanical smoke exhaust systems installed in various buildings, axial flow and centrifugal fans that exhaust smoke in the event of a fire. This standard was first issued in June 2001. JB/T 10281-2001 Technical conditions for fire smoke exhaust fans JB/T10281-2001 Standard download decompression password: www.bzxz.net

Some standard content:

ICS23.120
Machinery Industry Standard of the People's Republic of China
JB/T10281-2001
Technical conditions for fire smoke exhaust fans
Exhaust fume fan for fire fighting specifications2001-06-04Promulgated
China Machinery Industry Federation
Implementation on 2001-10-01
JB/T10281-2001
This standard is compiled based on the requirements for mechanical smoke exhaust in GB500451995 "Code for Fire Protection Design of High-rise Civil Buildings" and GB50067-1997 "Code for Fire Protection Design of Garages, Repair Garages and Parking Lots". This standard is proposed and managed by the National Technical Committee for Fan Standardization. The responsible drafting units of this standard are: Beijing Tiandicheng Ventilation Equipment Co., Ltd., Zhejiang Shangfeng Group Industrial Co., Ltd., Shenzhen Liantongda Air Conditioning Equipment Co., Ltd., Shenyang Blower Research Institute, Beijing Century Jingye Noise and Vibration Control Technology Co., Ltd. The main drafters of this standard are: Wang Dongguo, Dong Hanxiang, Zhuang Yongan, Zheng Hua, Chen Mingliang, Shao Bin. This standard is published for the first time.
1 Scope
Machinery Industry Standard of the People's Republic of China
Technical Conditions for Fire Smoke Exhaust Fans
ExhaustfumefanforfirefightingspecificationsJB/T10281—2001
This standard specifies the definition, technical requirements, test methods, inspection rules, marking, packaging and transportation of fire smoke exhaust fans. This standard applies to mechanical smoke exhaust systems installed in various types of buildings, and axial and centrifugal fans that play a role in smoke exhaust in the event of a fire.
2 Referenced Standards
The provisions contained in the following standards constitute the provisions of this standard through reference in this standard. When this standard is published, the versions shown are valid. All standards will be revised, and parties using this standard should explore the possibility of using the latest versions of the following standards: GA211—1999
GB/T12362000
GB/T2888—1991
GB/T32351999
GB/T13274—1991
GB/T 13275—1991
GB/T133061991
JB/T6445—1992
JB/T68861993
JB/T86891998
JB/T8690—1998
JB/T91011999
JB/T10213—2000
JB/T102142000
3 Definitions
This standard adopts the following definitions.
3.1 Fire smoke exhaust fans
Test method for high temperature resistance of fire smoke exhaust fans
Performance test of industrial fans using standardized air ducts (idtISO5801:1997)Noise measurement method for fans and Roots blowersBasic types, dimensional parameters and performance curves of fansTechnical conditions for general-purpose axial flow fans
Technical conditions for general-purpose centrifugal fans
Overspeed test of fan impellers
Technical conditions for painting of fans
Vibration detection and limit values ​​of fans
Noise limit values ​​of industrial fans
Rotor balancing of fans
Technical conditions for welding quality inspection of fans
Technical conditions for riveted and welded parts
Ventilators
Ventilators are installed in the mechanical smoke exhaust system of a building. When a fire occurs in the building, it is a ventilation equipment used to remove smoke (the equipment can also be used for ventilation at other times).
3.2 Motor air cooling system
When the motor is working at a high ambient temperature, a forced ventilation system is set up to protect the motor. Approved by China Machinery Industry Federation on June 4, 2001 and implemented on October 1, 2001
4 Technical requirements
4.1 Design requirements
JB/T10281—2001
4.1.1 Fire smoke exhaust fans shall comply with the provisions of this standard and be designed and manufactured according to the drawings and technical documents approved by the prescribed procedures or according to the requirements of the agreement between the supply and demand parties
4.1.2 The type, size parameters and performance curve of fire smoke exhaust fans shall comply with the provisions of GB/T3235. 4.1.3 Under the condition that the medium temperature is not higher than 85℃, the fan shall be designed for at least 10 years of use, and the safe operation time before the first overhaul shall be no less than 18,000 hours (including non-operation time). 4.1.4 The material used to manufacture the impeller of the fire smoke exhaust fan should be able to ensure that: when the temperature of the conveying medium is 280℃ and it runs continuously for 30 minutes, the impeller has sufficient mechanical properties.
4.2 Product performance of fire smoke exhaust fans
4.2.1 The fire smoke exhaust fan should be able to operate normally for a long time under the condition that the medium temperature is not higher than 85℃. 4.2.2 The fire smoke exhaust fan should ensure that: when the temperature of the conveying medium is 280℃, it can work continuously for 30 minutes, and can continue to operate normally when the medium temperature cools to the ambient temperature. 4.2.3 At the rated speed, in the working area, the measured pressure curve of the fan and the curve given in the manual should meet the following requirements a) The corresponding pressure value deviation of the axial flow fire smoke exhaust fan at the specified flow rate is 5% b) The corresponding pressure value deviation of the centrifugal fire smoke exhaust fan at the specified flow rate is 5%. 4.2.4 The noise limit of the A-level sound level of the fire smoke exhaust fan at the working point given in the manual shall comply with the provisions of JB/T8690. 4.3 The impeller of the fire smoke exhaust fan shall be statically and dynamically balanced. The balance quality level shall not be lower than G5.6. The material of the impeller balance weight block shall be the same as that of the impeller, and connected to the impeller by welding or riveting. 4.4 The impeller of the fire smoke exhaust fan shall be subjected to overspeed test according to the requirements of JB/T6445, and the overspeed speed shall be 110% of the maximum working speed, and the overspeed time shall not be less than 2min.
4.5 The vibration limit of the fire smoke exhaust fan in operation shall comply with the relevant provisions of JB/T8689. 4.6 Structural requirements
a) Axial flow fire smoke exhaust fans shall be equipped with motor thermal insulation protection and air cooling system in the fan (fans using motors with H insulation grade may not be equipped with forced air cooling system). The insulation grade of the motor shall not be lower than F grade. b) The power lead wire of the motor of the axial flow fire smoke exhaust fan shall be contained by a heat-resistant insulation sleeve or a high-temperature resistant cable. c) When the centrifugal fire smoke exhaust fan adopts A-type transmission, a heat insulation structure between the casing and the motor shall be provided. 4.7 Manufacturing requirements
4.7.1 The position tolerance of the inlet and outlet flange connection holes of the fire smoke exhaust fan shall be less than or equal to Φ1.5mm. The runout tolerance of the impeller of the axial flow fire smoke exhaust fan shall not exceed the provisions of Table 1. 4.7.2
Table 1 Fan impeller runout tolerance
Hub radial and end face circular runout
Impeller outer diameter radial circular runout
Impeller outer diameter end face circular runout
≤630
>630-800
>800-1250
>1250-2000
JB/T10281—2001
4.7.3 For an axial flow fire smoke exhaust fan with unequal pitch impeller, the difference in pitch (chord length) between the two corresponding end points of the corresponding blades at the outer circle shall not exceed the provisions of Table 2. Table 2 Blade pitch difference
Number of blades
≤630
>630-800
>800~1250
The geometric tolerance shall not exceed the provisions of Table 3.
Axial flow fire smoke exhaust fan casing size limit deviation, Table 3 casing size deviation and shape and position tolerance
Unprocessed cylinder inner diameter limit deviation
Parallelism tolerance of flange rings at both ends
Inner diameter roundness tolerance
≤630
>630-800
>800-1250
>1250-2000
>1250-2000
4.7.5 The blade shape of the axial flow fire smoke exhaust fan is airfoil or twisted plate, and the line profile tolerance of the blade camber profile shall comply with the provisions of JB/T10214.
4.7.6 The circular run-out tolerance of the inner diameter of the impeller cover of the centrifugal fire smoke exhaust fan shall be less than 1/2 of the minimum radial clearance between the impeller and the air inlet; the circular run-out tolerance of the impeller end face shall not exceed the provisions of Table 4; the flatness tolerance of the impeller disk shall not exceed the provisions of Table 5; the perpendicularity tolerance of the impeller blade outlet edge to the disk shall be less than or equal to 1% of the blade outlet width; the deviation of the blade outlet installation angle is +°. Table 4 Impeller end face circular runout tolerance
Disk end face circular runout
Wheel cover end face circular runout
Disk flatness
200-400
>120-400
>400-1000
Disk flatness tolerance
>1000~1600
>400-1000
>1600-2000
>1000~2000
The difference k between the two chord lengths at the outlet ends of any three adjacent blades of the centrifugal fire smoke exhaust fan impeller shall be in accordance with the provisions of Table 6. Table 6 Chord length difference k
Machine No.
0.45×(impeller diameter/100)
>10-20wwW.bzxz.Net
0.43×(impeller diameter/100)
JB/T10281—2001
4.7.8 The air inlet of centrifugal fire smoke exhaust fan shall be flat and smooth, and the shape and position tolerance of the casing side panel shall not exceed the requirements of Table 7. Table 7 Flatness of casing side panel
Flatness of casing side panel
>120-400
>400-1000
>1000~2000
4.7.9 The technical conditions of fire smoke exhaust fan welded parts shall comply with the provisions of JB/T10214, and the welding quality shall comply with the provisions of JB/T10213. 4.7.10 The gap of riveted parts shall not be greater than 0.1mm within the range of twice the rivet diameter, and shall not be greater than 0.3mm in other parts. The rivet head shall be smooth and flat, and any loose rivet, skewed rivet head, cracks and unriveted rivets are not allowed. 4.8 Assembly requirements
4.8.1 The radial clearance between the casing and the impeller of the axial flow fire smoke exhaust fan should be uniform, and the minimum radial single-side clearance value is: when the machine number is ≤No.10, the clearance is ≥3.5mm; when the machine number is >No.10, the clearance is ≥4.5mm. 4.82 The radial single-side clearance between the air inlet and the inlet of the impeller cover of the centrifugal fire smoke exhaust fan should be uniform, and the radial single-side clearance value should be within the range of 0.15%~0.4% of the impeller diameter, and the axial overlap length between the air inlet and the impeller cover should be 0.8%~1.2% of the impeller diameter. 4.9 The technical requirements for painting the inner and outer surfaces of the fire smoke exhaust fan shall comply with the provisions of JB/T6886. The paint selected for the fan will basically not change color after the fan conveys a medium at 280℃. 4.10 The rotating parts of the fire smoke exhaust fan and all parts that may become loose must be firm and reliable, and have anti-loosening measures. 4.11 Transmission group, pulley, coupling and other rotating transmission parts should be equipped with protective covers. 5 Test method
5.1 Impeller dynamic balance correction shall be carried out on a dynamic balancing machine in accordance with the provisions of JB/T9101. 5.2 Impeller overspeed test shall be carried out in accordance with the provisions of JB/T6445. 5.3 Mechanical operation test of fire smoke exhaust fan shall be carried out continuously at the working speed, and after the bearing temperature is stable for 20 minutes, the bearing temperature rise and vibration shall be measured. The temperature rise shall not be higher than 40℃ of the ambient temperature, and the vibration detection and its limit value shall comply with the relevant provisions of JB/T8689. 5.4 Aerodynamic performance test
The aerodynamic performance test of fire smoke exhaust fan shall be carried out in accordance with the provisions of GB/T1236. 5.5 Noise test
The noise measurement method shall be carried out in accordance with the provisions of GB/T2888. The noise limit value shall comply with the provisions of JB/T8690. 5.6 High temperature resistance test
Carry out in accordance with the provisions of GA211. High temperature performance requirements must meet the requirements of 4.4.2. 6 Inspection rules
6.1 Inspection classification
Fire smoke exhaust fans are divided into factory inspection and type inspection. 6.2 Factory inspection
Mass-produced fire smoke exhaust fans should be subject to factory inspection upon delivery. Axial flow fire smoke exhaust fans shall comply with the provisions of GB/T13274: centrifugal fire smoke exhaust fans shall comply with the provisions of GB/T13275. 4
6.3 Type inspection
JB/T10281—2001
6.3.1 Type inspection shall be carried out in any of the following situations: a) The first product of each type of fan;
b) The first product of the converted production;
c) When there are major modifications to the design structure, materials and processes that may affect product performance; d) When production resumes after 3 years of suspension.
6.3.2 The type inspection items of axial flow fire smoke exhaust fans shall be implemented in accordance with GB/T13274: the type inspection items of centrifugal fire smoke exhaust fans shall be implemented in accordance with GB/T13275. The two types of fans shall also be subjected to high temperature resistance test according to GA211. 6.4 Judgment rules
6.4.1 Each fan must be inspected and qualified by the quality inspection department of the manufacturer and can only be shipped after the certificate of conformity is issued. 6.4.2 If the fan sampled is out of tolerance, it shall be doubled for sampling. Those that meet the requirements are still qualified. If they are still out of tolerance, the batch of products shall be unqualified and shall be repaired and inspected one by one before they can be shipped. 6.5 User requirements
When the user makes special inspection requirements, they should be stipulated in the contract between the supply and demand parties. 6.6 Warranty period
If the user complies with the installation and use rules of the fan, within 18 months after delivery (calculated from the date of shipment), if the fan is damaged or cannot work normally due to manufacturing quality problems, the manufacturer should repair or replace parts for the user free of charge. 7 Marking, packaging, transportation
7.1 Marking
7.1.1 A turning arrow and product label should be installed in a conspicuous position on the fan casing. The label content should at least include: a) Model and name:
b) Main technical parameters: fan total pressure (or static pressure), flow, motor power, speed, maximum temperature of the medium: c) Product number:
d) Manufacturing date;
e) Manufacturer name and trademark.
7.1.2 The size and technical requirements of the product label should comply with the provisions of GB/T13306. 7.2 Packaging and transportation
7.2.1 The ventilator should be packed in a box as a whole as far as possible. If it is inconvenient to pack the whole, it can be packed in parts, but measures must be taken to ensure that the installation clearance and coaxiality of the product after on-site installation meet the product technical requirements. 7.22 The ventilator should be leveled, clamped and bolted in the box. Disassembly tools and other parts should also be fastened and fixed in the gaps in the box to prevent movement and displacement during transportation. 7.2.3 The documents accompanying the ventilator are:
a) Product certificate;
b) Product manual or sample;
c) Packing list (complete set supply list); d) Photocopy of the registration certificate for the fire smoke exhaust ventilator. 5
JB/T10281—2001
7.2.4 The dimensions and weight of the packaging box shall comply with the regulations of the transportation department. 7.2. 5
The structure of the packaging box shall take into account the convenience of lifting, handling, long-distance transportation, multiple loading and unloading, and climatic conditions, and shall be suitable for water and land transportation, so as to avoid product damage, quality reduction or loss of parts due to poor packaging. 6
Mechanical Industry Standard
Technical Conditions for Fire Smoke Exhaust Fans
JB/T10281-2001
Published and issued by the China Academy of Mechanical Science
Printed by the China Academy of Mechanical Science
(No. 2 Shouti South Road, Beijing: Postal Code 100044)*
Format 880×12301/16 Printing Sheet 3/4
4Number of Words 14,000
First Edition September 2001First Printing September 2001Print Quantity 1-500
Price RMB 1,200
2001-098
Mechanical Industry Standard Service Network: http://www.jb.ac.cn1cn1cn110 The gap of the riveted parts should not be greater than 0.1mm within the range of two times the rivet diameter, and the rest should not be greater than 0.3mm. The rivet head should be smooth and flat, and any loose rivets, skewed rivet heads, cracks and un-riveted phenomena are not allowed. 4.8 Assembly requirements
4.8.1 The radial clearance value between the casing and the impeller of the axial flow fire smoke exhaust fan should be uniform, and the minimum radial single-side clearance value: when the machine number is ≤No.10, the clearance is ≥3.5mm; when the machine number is >No.10, the clearance is ≥4.5mm. 4.82 The radial single-side clearance between the air inlet and the impeller cover of the centrifugal fire smoke exhaust fan should be uniform, and the radial single-side clearance value should be within the range of 0.15%~0.4% of the impeller diameter. The axial overlap length between the air inlet and the impeller cover should be 0.8%~1.2% of the impeller diameter. 4.9 The technical requirements for painting the inner and outer surfaces of fire smoke exhaust fans shall comply with the provisions of JB/T6886. The paint selected for the fan basically does not change color after the fan conveys the medium at 280℃. 4.10 The rotating parts of the fire smoke exhaust fan and all parts that may loosen must be firm and reliable, and have anti-loosening measures. 4.11 The rotating transmission parts such as the transmission group, pulley, coupling, etc. should be equipped with protective covers. 5 Test method
5.1 The dynamic balance correction of the impeller is carried out on the dynamic balancing machine in accordance with the provisions of JB/T9101. 5.2 The overspeed test of the impeller is carried out in accordance with the provisions of JB/T6445. 5.3 The mechanical operation test of the fire smoke exhaust fan is carried out continuously at the working speed. After the bearing temperature stabilizes for 20 minutes, the bearing temperature rise and vibration are measured. The temperature rise shall not be higher than 40℃ of the ambient temperature, and the vibration detection and its limit value shall comply with the relevant provisions of JB/T8689. 5.4 Aerodynamic performance test
The aerodynamic performance test of the fire smoke exhaust fan is carried out in accordance with the provisions of GB/T1236. 5.5 Noise test
The noise measurement method shall be carried out in accordance with the provisions of GB/T2888. The noise limit value shall comply with the provisions of JB/T8690. 5.6 High temperature resistance test
It shall be carried out in accordance with the provisions of GA211. The high temperature performance requirements shall meet the requirements of 4.4.2. 6 Inspection rules
6.1 Inspection classification
Fire smoke exhaust fans are divided into factory inspection and type inspection. 6.2 Factory inspection
Mass-produced fire smoke exhaust fans shall be subject to factory inspection upon delivery. Axial flow fire smoke exhaust fans shall be subject to the provisions of GB/T13274: centrifugal fire smoke exhaust fans shall be subject to the provisions of GB/T13275. 4
6.3 Type inspection
JB/T10281—2001
6.3.1 Type inspection shall be carried out in any of the following cases: a) the first product of each type of ventilator;
b) the first product of the converted production;
c) when the design structure, materials and process have been significantly modified and may affect the product performance; d) when the production is resumed after 3 years of suspension.
6.3.2 The type inspection items of axial flow fire smoke exhaust ventilator shall be implemented in accordance with GB/T13274: the type inspection items of centrifugal fire smoke exhaust ventilator shall be implemented in accordance with GB/T13275. The two types of ventilators shall also be subjected to high temperature resistance test according to GA211. 6.4 Judgment rules
6.4.1 Each ventilator shall be inspected and qualified by the quality inspection department of the manufacturer and can only be shipped after the certificate of conformity is issued. 6.4.2 If the fan sampled is out of tolerance, it shall be doubled for testing. If it meets the requirements, it is still qualified. If it is still out of tolerance, the batch of products is unqualified and shall be repaired and inspected one by one before it can be shipped. 6.5 User requirements
When the user makes special inspection requirements, it shall be stipulated in the contract between the supply and demand parties. 6.6 Warranty period
If the user complies with the installation and use rules of the fan, within 18 months after delivery (calculated from the date of delivery), if the fan is damaged or cannot work normally due to manufacturing quality problems, the manufacturer shall repair or replace parts for the user free of charge. 7 Marking, packaging, and transportation
7.1 Marking
7.1.1 A turning arrow and product label should be installed in a conspicuous position on the fan housing. The label content should at least include: a) Model and name:
b) Main technical parameters: fan total pressure (or static pressure), flow, motor power, speed, maximum temperature of the medium: c) Product number:
d) Manufacturing date;
e) Manufacturer name and trademark.
7.1.2 The size and technical requirements of the product label should comply with the provisions of GB/T13306. 7.2 Packaging and transportation
7.2.1 The fan should be packed in a box as a whole as much as possible. For those that are inconvenient to pack as a whole, separate packaging can be used, but measures must be taken to ensure that the installation clearance and coaxiality of the product after on-site installation meet the product technical requirements. 7.22 The fan should be leveled, clamped, and fixed in the box with bolts. Disassembly tools and other parts should also be fastened and fixed in the gaps in the box to prevent movement and displacement during transportation. 7.2.3 The documents accompanying the fan are:
a) Product certificate;
b) Product manual or sample;
c) Packing list (complete set supply list); d) Photocopy of the registration certificate of the fire smoke exhaust fan. 5
JB/T10281—2001
7.2.4 The dimensions and weight of the packaging box should comply with the regulations of the transportation department 7.2. 5
The structure of the packaging box should take into account the convenience of lifting, handling, long-distance transportation, multiple loading and unloading, and climatic conditions, and be suitable for water and land transportation, so as not to cause product damage, quality reduction or parts loss due to poor packaging. 6
Mechanical Industry Standard
Technical Conditions for Fire Smoke Exhaust Fans
JB/T10281-2001
Published and issued by the China Academy of Mechanical Science
Printed by the China Academy of Mechanical Science
(No. 2 Shouti South Road, Beijing: Postal Code 100044)*
Format 880×12301/16 Printing Sheet 3/4
4Number of Words 14,000
First Edition September 2001First Printing September 2001Print Quantity 1-500
Price RMB 1,200
2001-098
Mechanical Industry Standard Service Network: http://www.jb.ac.cn110 The gap of the riveted parts should not be greater than 0.1mm within the range of two times the rivet diameter, and the rest should not be greater than 0.3mm. The rivet head should be smooth and flat, and any loose rivets, skewed rivet heads, cracks and un-riveted phenomena are not allowed. 4.8 Assembly requirements
4.8.1 The radial clearance value between the casing and the impeller of the axial flow fire smoke exhaust fan should be uniform, and the minimum radial single-side clearance value: when the machine number is ≤No.10, the clearance is ≥3.5mm; when the machine number is >No.10, the clearance is ≥4.5mm. 4.82 The radial single-side clearance between the air inlet and the impeller cover of the centrifugal fire smoke exhaust fan should be uniform, and the radial single-side clearance value should be within the range of 0.15%~0.4% of the impeller diameter. The axial overlap length between the air inlet and the impeller cover should be 0.8%~1.2% of the impeller diameter. 4.9 The technical requirements for painting the inner and outer surfaces of fire smoke exhaust fans shall comply with the provisions of JB/T6886. The paint selected for the fan basically does not change color after the fan conveys the medium at 280℃. 4.10 The rotating parts of the fire smoke exhaust fan and all parts that may loosen must be firm and reliable, and have anti-loosening measures. 4.11 The rotating transmission parts such as the transmission group, pulley, coupling, etc. should be equipped with protective covers. 5 Test method
5.1 The dynamic balance correction of the impeller is carried out on the dynamic balancing machine in accordance with the provisions of JB/T9101. 5.2 The overspeed test of the impeller is carried out in accordance with the provisions of JB/T6445. 5.3 The mechanical operation test of the fire smoke exhaust fan is carried out continuously at the working speed. After the bearing temperature stabilizes for 20 minutes, the bearing temperature rise and vibration are measured. The temperature rise shall not be higher than 40℃ of the ambient temperature, and the vibration detection and its limit value shall comply with the relevant provisions of JB/T8689. 5.4 Aerodynamic performance test
The aerodynamic performance test of the fire smoke exhaust fan is carried out in accordance with the provisions of GB/T1236. 5.5 Noise test
The noise measurement method shall be carried out in accordance with the provisions of GB/T2888. The noise limit value shall comply with the provisions of JB/T8690. 5.6 High temperature resistance test
It shall be carried out in accordance with the provisions of GA211. The high temperature performance requirements shall meet the requirements of 4.4.2. 6 Inspection rules
6.1 Inspection classification
Fire smoke exhaust fans are divided into factory inspection and type inspection. 6.2 Factory inspection
Mass-produced fire smoke exhaust fans shall be subject to factory inspection upon delivery. Axial flow fire smoke exhaust fans shall be subject to the provisions of GB/T13274: centrifugal fire smoke exhaust fans shall be subject to the provisions of GB/T13275. 4
6.3 Type inspection
JB/T10281—2001
6.3.1 Type inspection shall be carried out in any of the following cases: a) the first product of each type of ventilator;
b) the first product of the converted production;
c) when the design structure, materials and process have been significantly modified and may affect the product performance; d) when the production is resumed after 3 years of suspension.
6.3.2 The type inspection items of axial flow fire smoke exhaust ventilator shall be implemented in accordance with GB/T13274: the type inspection items of centrifugal fire smoke exhaust ventilator shall be implemented in accordance with GB/T13275. The two types of ventilators shall also be subjected to high temperature resistance test according to GA211. 6.4 Judgment rules
6.4.1 Each ventilator shall be inspected and qualified by the quality inspection department of the manufacturer and can only be shipped after the certificate of conformity is issued. 6.4.2 If the fan sampled is out of tolerance, it shall be doubled for testing. If it meets the requirements, it is still qualified. If it is still out of tolerance, the batch of products is unqualified and shall be repaired and inspected one by one before it can be shipped. 6.5 User requirements
When the user makes special inspection requirements, it shall be stipulated in the contract between the supply and demand parties. 6.6 Warranty period
If the user complies with the installation and use rules of the fan, within 18 months after delivery (calculated from the date of delivery), if the fan is damaged or cannot work normally due to manufacturing quality problems, the manufacturer shall repair or replace parts for the user free of charge. 7 Marking, packaging, and transportation
7.1 Marking
7.1.1 A turning arrow and product label should be installed in a conspicuous position on the fan housing. The label content should at least include: a) Model and name:
b) Main technical parameters: fan total pressure (or static pressure), flow, motor power, speed, maximum temperature of the medium: c) Product number:
d) Manufacturing date;
e) Manufacturer name and trademark.
7.1.2 The size and technical requirements of the product label should comply with the provisions of GB/T13306. 7.2 Packaging and transportation
7.2.1 The fan should be packed in a box as a whole as much as possible. For those that are inconvenient to pack as a whole, separate packaging can be used, but measures must be taken to ensure that the installation clearance and coaxiality of the product after on-site installation meet the product technical requirements. 7.22 The fan should be leveled, clamped, and fixed in the box with bolts. Disassembly tools and other parts should also be fastened and fixed in the gaps in the box to prevent movement and displacement during transportation. 7.2.3 The documents accompanying the fan are:
a) Product certificate;
b) Product manual or sample;
c) Packing list (complete set supply list); d) Photocopy of the registration certificate of the fire smoke exhaust fan. 5
JB/T10281—2001
7.2.4 The dimensions and weight of the packaging box should comply with the regulations of the transportation department 7.2. 5
The structure of the packaging box should take into account the convenience of lifting, handling, long-distance transportation, multiple loading and unloading, and climatic conditions, and be suitable for water and land transportation, so as not to cause product damage, quality reduction or parts loss due to poor packaging. 6
Mechanical Industry Standard
Technical Conditions for Fire Smoke Exhaust Fans
JB/T10281-2001
Published and issued by the China Academy of Mechanical Science
Printed by the China Academy of Mechanical Science
(No. 2 Shouti South Road, Beijing: Postal Code 100044)*
Format 880×12301/16 Printing Sheet 3/4
4Number of Words 14,000
First Edition September 2001First Printing September 2001Print Quantity 1-500
Price RMB 1,200
2001-098
Mechanical Industry Standard Service Network: http://www.jb.ac.cn11 Type inspection shall be conducted in any of the following cases: a) the first product of each type of fan;
b) the first product of the conversion production;
c) when the design structure, materials and process have been significantly modified and may affect the product performance; d) when production is resumed after 3 years of suspension.
6.3.2 The type inspection items of axial flow fire smoke exhaust fan shall be implemented in accordance with GB/T13274: the type inspection items of centrifugal fire smoke exhaust fan shall be implemented in accordance with GB/T13275. The two types of fans shall also be subjected to high temperature resistance test according to GA211. 6.4 Judgment rules
6.4.1 Each fan shall be inspected and qualified by the quality inspection department of the manufacturer and issued with a certificate of conformity before it can leave the factory. 6.4.2 If the fan sampled is out of tolerance, it shall be doubled for sampling. If it meets the requirements, it is still qualified. If it is still out of tolerance, the batch of products is unqualified and should be repaired and inspected one by one before it can leave the factory. 6.5 User requirements
When the user makes special inspection requirements, they should be stipulated in the contract between the supply and demand parties. 6.6 Warranty period
If the user complies with the installation and use rules of the fan, within 18 months after delivery (calculated from the date of shipment), if the fan is damaged or cannot work normally due to manufacturing quality problems, the manufacturer should repair or replace parts for the user free of charge. 7 Marking, packaging, transportation
7.1 Marking
7.1.1 A turning arrow and product label should be installed in a conspicuous position on the fan casing. The label content should at least include: a) Model and name:
b) Main technical parameters: fan total pressure (or static pressure), flow, motor power, speed, maximum temperature of the medium: c) Product number:
d) Manufacturing date;
e) Manufacturer name and trademark.
7.1.2 The size and technical requirements of the product label should comply with the provisions of GB/T13306. 7.2 Packaging and transportation
7.2.1 The ventilator should be packed in a box as a whole as far as possible. If it is inconvenient to pack the whole, it can be packed in parts, but measures must be taken to ensure that the installation clearance and coaxiality of the product after on-site installation meet the product technical requirements. 7.22 The ventilator should be leveled, clamped and bolted in the box. Disassembly tools and other parts should also be fastened and fixed in the gaps in the box to prevent movement and displacement during transportation. 7.2.3 The documents accompanying the ventilator are:
a) Product certificate;
b) Product manual or sample;
c) Packing list (complete set supply list); d) Photocopy of the registration certificate for the fire smoke exhaust ventilator. 5
JB/T10281—2001
7.2.4 The dimensions and weight of the packaging box shall comply with the regulations of the transportation department. 7.2. 5
The structure of the packaging box shall take into account the convenience of lifting, handling, long-distance transportation, multiple loading and unloading, and climatic conditions, and shall be suitable for water and land transportation, so as to avoid product damage, quality reduction or loss of parts due to poor packaging. 6
Mechanical Industry Standard
Technical Conditions for Fire Smoke Exhaust Fans
JB/T10281-2001
Published and issued by the China Academy of Mechanical Science
Printed by the China Academy of Mechanical Science
(No. 2 Shouti South Road, Beijing: Postal Code 100044)*
Format 880×12301/16 Printing Sheet 3/4
4Number of Words 14,000
First Edition September 2001First Printing September 2001Print Quantity 1-500
Price RMB 1,200
2001-098
Mechanical Industry Standard Service Network: http://www.jb.ac.cn11 Type inspection shall be conducted in any of the following cases: a) the first product of each type of fan;
b) the first product of the conversion production;
c) when the design structure, materials and process have been significantly modified and may affect the product performance; d) when production is resumed after 3 years of suspension.
6.3.2 The type inspection items of axial flow fire smoke exhaust fan shall be implemented in accordance with GB/T13274: the type inspection items of centrifugal fire smoke exhaust fan shall be implemented in accordance with GB/T13275. The two types of fans shall also be subjected to high temperature resistance test according to GA211. 6.4 Judgment rules
6.4.1 Each fan shall be inspected and qualified by the quality inspection department of the manufacturer and issued with a certificate of conformity before it can leave the factory. 6.4.2 If the fan sampled is out of tolerance, it shall be doubled for sampling. If it meets the requirements, it is still qualified. If it is still out of tolerance, the batch of products is unqualified and should be repaired and inspected one by one before it can leave the factory. 6.5 User requirements
When the user makes special inspection requirements, they should be stipulated in the contract between the supply and demand parties. 6.6 Warranty period
If the user complies with the installation and use rules of the fan, within 18 months after delivery (calculated from the date of shipment), if the fan is damaged or cannot work normally due to manufacturing quality problems, the manufacturer should repair or replace parts for the user free of charge. 7 Marking, packaging, transportation
7.1 Marking
7.1.1 A turning arrow and product label should be installed in a conspicuous position on the fan casing. The label content should at least include: a) Model and name:
b) Main technical parameters: fan total pressure (or static pressure), flow, motor power, speed, maximum temperature of the medium: c) Product number:
d) Manufacturing date;
e) Manufacturer name and trademark.
7.1.2 The size and technical requirements of the product label should comply with the provisions of GB/T13306. 7.2 Packaging and transportation
7.2.1 The ventilator should be packed in a box as a whole as far as possible. If it is inconvenient to pack the whole, it can be packed in parts, but measures must be taken to ensure that the installation clearance and coaxiality of the product after on-site installation meet the product technical requirements. 7.22 The ventilator should be leveled, clamped and bolted in the box. Disassembly tools and other parts should also be fastened and fixed in the gaps in the box to prevent movement and displacement during transportation. 7.2.3 The documents accompanying the ventilator are:
a) Product certificate;
b) Product manual or sample;
c) Packing list (complete set supply list); d) Photocopy of the registration certificate for the fire smoke exhaust ventilator. 5
JB/T10281—2001
7.2.4 The dimensions and weight of the packaging box shall comply with the regulations of the transportation department. 7.2. 5
The structure of the packaging box shall take into account the convenience of lifting, handling, long-distance transportation, multiple loading and unloading, and climatic conditions, and shall be suitable for water and land transportation, so as to avoid product damage, quality reduction or loss of parts due to poor packaging. 6
Mechanical Industry Standard
Technical Conditions for Fire Smoke Exhaust Fans
JB/T10281-2001
Published and issued by the China Academy of Mechanical Science
Printed by the China Academy of Mechanical Science
(No. 2 Shouti South Road, Beijing: Postal Code 100044)*
Format 880×12301/16 Printing Sheet 3/4
4Number of Words 14,000
First Edition September 2001First Printing September 2001Print Quantity 1-500
Price RMB 1,200
2001-098
Mechanical Industry Standard Service Network: http://www.jb.ac.cn1