JB/T 10434.2-2004 Plugs and sockets for household and similar purposes Part 2: Special requirements for fixed non-interlocking switched sockets

Basic Information

Standard ID: JB/T 10434.2-2004

Standard Name: Plugs and sockets for household and similar purposes Part 2: Special requirements for fixed non-interlocking switched sockets

Chinese Name: 家用和类似用途插头插座 第2部分:固定式无联锁带开关插座的特殊要求

Standard category:Machinery Industry Standard (JB)

state:in force

Date of Release2004-03-12

Date of Implementation:2004-08-01

standard classification number

Standard ICS number:Electrical Engineering>>Electrical Devices>>29.120.30 Plugs, sockets and connectors

Standard Classification Number:Electrical Engineering>>Electrical Equipment and Apparatus>>K65 Other Electrical Apparatus

associated standards

Procurement status:MOD IEC 60884-2-3:1989,E1

Publication information

publishing house:Mechanical Industry Press

ISBN:15111.7343

Publication date:2004-07-31

other information

Drafting unit:Guangzhou Electric Science Research Institute

Focal point unit:National Electrical Accessories Standardization Committee

Publishing department:National Electrical Accessories Standardization Committee

Introduction to standards:

This standard applies to AC fixed switched sockets for household and similar purposes, with or without grounding contacts, with a rated voltage not exceeding 440V and a rated current not exceeding 32A, for indoor and outdoor use. JB/T 10434.2-2004 Plugs and sockets for household and similar purposes Part 2: Special requirements for fixed non-interlocking switched sockets JB/T10434.2-2004 Standard download decompression password: www.bzxz.net

Some standard content:

IS 22.120.3
Machinery Industry Standard of the People's Republic of China
JB/T10434.2—2004
Part 2:
Plugs and sockel-outlets for household and similar purposcsPart 2:Particular requirements for switched socket-outlets witloutinterlockfurfixed insiallalionsf1EC60884-2-3;1989,E1,M0D
2004-03-12 Issued
2004-08-01 Implementation
National Development and Reform Commission of the People's Republic of China Issued Foreword
Normative reference documents
Tai Pei Zong Yi
·General requirements.…
General instructions for the ten tests
Dimensional inspection.
Anti-electrostatic protection||t t||The structure of the same type of socket
The structure of the plug and mobile socket
Interlocking socket
Chemical resistance, protection against harmful water ingress and protection against two
Insulation resistance and electrical
According to the working of other contacts
Breaking capacity
The force caused by removing the head...
The flexible cable is connected
The city test degree
The ladder order is relatively large with the components and their connections.
Slowly! This standard modifies and adopts IFC608842-3:1989 "Household and similar purpose plug sockets Part 2: Special requirements for plugs with switches" (First Edition). This standard should be used in conjunction with GB2D99.1 "Household and similar purpose plug sockets Part 1: General requirements" and is only applicable to household and similar purpose sockets with non-interconnected switches (with mechanical switches as the main body and controlled by switches). It does not apply to products that may be used alone. my country's multi-position non-interconnected socket products allow one switch to control both positions. In order to match the versions, the standard chapter number and structure are adjusted appropriately in the compilation, so as to facilitate the use with GR299.1. This standard is compared with E60884-2-3:1939 as follows: The structure of Chapter 1 is adjusted to correspond to GB2099.1-1996: Chapter 2 "Normative Reference Documents" is added to facilitate the use with GB2099.1-1996, and the chapter number of the whole text is also adjusted accordingly: For Chinese products, add a note under 3.102 to explain that my country allows one switch to control multiple positions at the same time: Chapter 6, add the specified rated value to indicate the numerical value of the entire product (see 6.101). 1) In correspondence with 8.2, the relevant content of 7.2.10.3 "Classification according to contact disconnection situation" is added, and the content of the standard is reported: the last line of 10.101 "Chapters 16 and 20" is changed to "Chapters 17 and 27"; According to the internal proposal of the standard, the last line of 10.103 "Chapters 16 and 19" is changed to "Chapters 10 and 17"; In Chapter 21, "c0-0.6±0.05" is changed to 00=0.8-0.05; The delay rate of normal operation (15 operations per minute) in Chapter 21 is changed to "according to the determination of Chapter 20", which is consistent with 1915.1: This standard is a recommended standard:
This standard is approved by the China Association of Primary Industry. This standard is under the jurisdiction of the National Electrical Equipment Standardization Technical Committee. The originators of this standard are: Guangzhou Instrument Science Research Institute, Qifeng Electric (Gaozhou) Co., Ltd., TC Hui International Engineering Co., Ltd., Hangzhou Hongli Automatic Equipment Co., Ltd., and Luo Mingge (Beijing) Electric Co., Ltd. The main drafters of this standard are: Yao Huaiping, Wang Keshi, Kong Jun, Chang Guozi, and Liu Xing. Introduction
Plugs and sockets for household and similar purposes
JB/T10434.2-2004
Part 2: Special requirements for fixed non-interlocking sockets with switches (%20991 contains the contents related to the sockets for release, which are applicable according to the parties. 1 Standard
C2099.1-16 This chapter is modified as follows: The first paragraph is changed to
This standard applies to AC fixed sockets with switches for indoor and outdoor use, with or without grounding contacts, rated and not exceeding 140V, and rated current not exceeding 32A. 1: The socket with a switch is used for a relatively large socket, 2: The value of the socket with a switch can also be made of the switch specified in UH294.1 and the switch specified in 169151, but the two.7 Series No. 2 paragraphs and column 2 .
The total is Note 3
23. The letter, Note 1 is changed to Note 4. Toe 5+6
? Normative references
This chapter of GB2099.1-1996 is applicable after the amendment, and the following terms and definitions are applicable to this standard. 3.1
A switched socket-outlet is a component composed of a socket and a control socket. 3.2
Multiple socket-outlets with switches ultlpleswilchedscicket-oullel refers to an accessory with a switch socket, and the socket is controlled by its own independent data: I learn product price auction - a switch control position folding socket, also allows the switch to control multiple positions 3.3
switch swilel
is a device used in one or more circuits to connect and disconnect current. 3.4
onceprraion
refers to the conversion of the switch moving contact from one working position to another working position. 4 General requirements
G month 2099.11996 This chapter applies.
JB/F10434.2——2004
5 About the test a note
GB2Uyy. 1-1VV6 shall apply with the following modifications. 5.5 Addition:
Addition: If flashing continues on the switch sample during any test in the 20th month, the plug of the switch shall be deemed not to comply with this standard.
6 Ratings
GH2099.[-1996]4 shall be modified as follows. 6.2 shall be changed to:
The rated current and voltage ratings of the switch in the plug socket shall not be less than the rated values ​​of the controlled outlet. Addition:
6.101 The rated current of the switch socket shall be the lower of the following two: Rated current of the switch part:
The rated current of a socket controlled by a switch or the rated current of all the outlets controlled by a switch. 7 Classification
This chapter of G20S5.1-1996 shall apply with the following modifications. 7.2 Addition:
7.2.101 Classification of sockets with switches:
7.2.101.1 Classification of side-operated switch methods. - Rotary lift switch
Push-pull switch:
A cross-board switch:
A button switch.
7.2.101.2 Classification by neutral line conversion
Neutral line controlled by switch:
Neutral line controlled by small gap
7.2.101.3 Classification by contact disconnection: Normal gap structure switch:
Small gap structure switch.
Note 1: When the small gap is in the listening position, the head gap is 3nm~12n. 8 Marking
This version of GB2099.1-1996 is applicable after the following modification. 1st - the first stroke of the damaged core
rated current (A) (with switch pre-seat product total rated current after the seventh effect:
small gap structure symbol (when this structure: 8.2 after the first stroke add:
small gap structure.
"break position o....-..
..." road position)
additional training:
JB/I10494.2-2C04
8.The terminals of the power conductors shall be marked with identification marks, unless the connection method itself is not important, is self-evident or is marked on the wiring board. Such terminals shall be marked with the letter "I". If there are multiple such terminals, they shall be marked with the letters "11", "L2", "3", etc., and these terminals may each have a box to indicate their associated terminals. Alternatively, the surface of the terminal shall be made of yellow or purple material: other commonly used metal layers of different colors are used to connect the two-pole, one-pole and two-pole switches. Unless the connection of the terminal itself is self-evident, otherwise, the terminal corresponding to any "pole" shall also be marked with similar identification marks to distinguish the terminal corresponding to the other pole. The terminal after the neutral conductor is indicated by the letter "N". These markings are not Marking on screw pins or other easily removable parts. 8.102 Two-pole, three-pole switches and switches with a rated voltage exceeding 250V or a rated current exceeding 16A should be marked to clearly indicate the direction of movement of the starter or the actual position of the switch. For multi-stage switch sockets, the marking indicates the result caused by the movement of the starter element. The marking should be clearly visible on the front of the socket after the cover or cover is installed. If these markings are on the cover or removable element, it should be ensured that it is impossible for these parts to be installed in a position that will cause the marking to be incorrect. The symbols "" and "" can be used to indicate the marking. Note 1: Class-1 must have such a marking.
9 Size list Li
GB209 9.1 This chapter of 1996 applies.
10 Protection against electric shock
(R2099.] This specification shall be amended and added as follows:
10.101 The rotary knob, operating lever, button, springboard, etc. used to operate the switch in the socket of the switch shall be made of high-grade materials. Otherwise, their products and metal parts shall be separated from the metal parts of the switch mechanism by insulation or insulation, or their fusible parts shall be sealed with a battery.
Whether it is satisfactory or not shall be checked by observing the specification and conducting 17 and 27 tests. 10.102 The metal parts of the mechanism that are not isolated from the live parts, such as the core or pivot of the wheel or springboard, shall not protrude from the casing. Whether it is satisfactory or not shall be determined by observing the whole process and, if necessary, the starting element shall be removed from the casing. Components removed or destroyed. If the operating components must be destroyed: Compliance shall be checked after the tests of clause 28: 1D.103 Switch mechanism with dial in the normal state After installation, metal parts of the switch mechanism, such as wheels or hinges, shall be insulated from easily accessible metal parts.
In addition, these metal parts shall be insulated from easily accessible metal parts, including metal plates supporting the base of the switch, which may be installed in the metal mounting box, and from the screws fixing the base to its bracket. If the creepage distance and electrical distance between the two parts of the switch mechanism and the insulated parts are at least twice the values ​​specified in clause 27.1, or these metal parts are firmly earthed, the above additional requirements do not need to be met and the components are qualified. If necessary, the test and inspection of Chapters 10 and 17 shall be carried out. 11 Grounding faults
This chapter of GR2099.1-1996 shall apply.
12 Terminals
This chapter of GB2099.1-1906 shall apply.
JB/T10434.2-20C4
13 Structure of fixed sockets wwW.bzxz.Net
This chapter of 2099.1-1996 shall apply with the following modifications:
13.101 The switch structure shall be in close contact with the neutral line of the switch holder. The grounding head shall not be used as a pole: The position of the switch operating element shall not be affected by the incorrect insertion of the corresponding terminal. The correct operation of the core component shall not be hindered by the corresponding positive distance.
Compliance is checked by the following test: When the operating element of the switch is properly inserted into the seat with the stop gauge specified in B102, the seat shall not be disturbed by the normal operation of the operating element.
13.102 The knob of the rotary switch shall be securely coupled to the axis of rotation or to a component of the switch structure. A force of [N min] in the positive direction shall be applied to the knob. If the switch can be turned in the opposite direction without force, the knob shall not come loose during this test.
13.103 The operating element of the switch shall automatically be in the position corresponding to the moving contact when it is released. Except for single-press switches, the operating element of such switches may be in a single static position. 13.104 The switch is constructed so that the moving contact can be static in the "" or "" position. If the position corresponds to the position of the actuating element and there is sufficient insulation between the fixed contact and the moving contact, an intermediate position is allowed. If necessary, the insulation between the fixed contact and the moving contact in the intermediate position can be checked by applying a 5012 or 12 Hz basic sine wave voltage for 1 min across the switch. For switch sockets with a rated voltage of 13V or less, the test voltage is 1250V. For output accessories with a rated voltage exceeding 130V, the test voltage is 2000V. Compliance with the requirements of 13.103 and 13.104 may be checked by observation and by a functional test. 13.105 The switch shall be constructed so that no excessive arcing occurs when the switch is operated slowly. Compliance is checked by causing the switch to interrupt the circuit for a second time at the end of the test, the actuating element to move more than 25° and stop the actuating element in the middle position, and then the actuating element is tripped. During the test, a continuous arc is present. 13.106 A socket-outlet with a switch operating on one pole shall be capable of making and disconnecting all the poles simultaneously, except that the neutral conductor shall not be connected before the other poles and after the other poles. Compliance is checked by observation and by a functional test. 13.107 If the cover and the plate are removed for installation, the action of the mechanism shall be independent of the plate and the plate. Whether it is qualified, the following method is used to check: without cover and differential plate, it is not allowed to be connected in series, and the starting element is normally pressed without excessive force. During the test period, the lamp should flash. 14 Structure of plugs and mobile sockets This chapter of GB2099.1-1996 is not applicable. 15 Chain sockets This chapter of GB2099.1-1996: small applicable 15 Ageing resistance, protection against harmful water ingress and moisture resistance This chapter of GB2099.1-1990 is applicable. 17 Insulation resistance and electrical strength This chapter of GB2099.1-1996 is applicable after the following amendments. 17.1 Replace the last sentence: Except? 17.1.1) and h) the insulation resistance is less than 2M2, and the insulation resistance shall not be less than 5M2. 17.1.1 Add after the first note:
For switches with sockets, the insulation resistance shall be measured in the following order: between all poles connected together and the body, and between each other pole connected to the body in turn: when the switch is in the "+" position: h When the switch is in the "+" position, the switch shall be in the "it" position. This: The "body" includes the product and the metal parts, the metal parts of the concealed type with the switch, the metal wires that make short contact with the external parts and the external surface of the insulated material, the fixed points of the silicon seeds, the fixed screws of the base or the strike plate, the external installation lights, the grounding constants, and any metal parts that need to be insulated from the electrical parts: see 1I102) 1 day grounding head work
GB2099.1-1995 is applicable
19 temperature rise
GH2099.1-1 is applicable to this chapter.
20 will break capacity
GB2099.1-199HG is applicable after the modification
The switch with switch socket should have sufficient connection and disconnection capacity. The principle of the test device used in the four-item test is shown in Figure 13 of G16915.1. The test device is also used for normal operation test. The switch is connected to the conductor specified in the test in Chapter 19. The switch is usually tested at 1.1 times the rated voltage and 1.25 times the rated current. The operation is performed 200 times at the following uniform rate: 30 operations per minute for switches with a rated current not greater than 10A; 15 operations per minute for switches with a rated current greater than 10A but less than 25A; 7 operations per minute for switches with a rated current of 25A or less than 25A.5 operations. For the full-rotation switch with two-way operation, the operating element shall be operated half of the total number of times in one direction and the remaining number of times in the other direction:
This test is carried out by adding a dense current (c0590.6 ± 0.05). During the test, there shall be no continuous flashing of the specification. After the test, the sample shall not be damaged by the use of the instrument. The following modifications shall apply to the normal operation of the switch socket:
The switch of the switch socket shall be able to withstand the voltage, electricity and heat generated in normal use without excessive loss and other harmful effects.
Whether the system meets the following test is checked
The switch is tested with rated voltage and rated voltage (c99=0.8m/s 0.05m/s). The test device is as specified in Chapter 20. The test operation frequency is shown in Table 01.
JB/T10434.2-2004
Rated voltage
2. c. 250V
1A -32A
The operation rate shall be calculated as specified in Chapter 20,
Normal connection test operation times
Operation change number
LUKHKO
Special double operation shall be carried out at the same time, 3/4 of the total operation times shall be operated in the clockwise direction, and the remaining operation times shall be operated in the counterclockwise direction:
During the test, the sample shall be operated accurately, and after the test, the sample shall be able to perform the electrical strength test specified in Section 17 And the temperature rise test specified in Chapter 19, but the test current is reduced by the rated current, the sample does not appear: the impact of continuous use of the damage, such as the position of the action element, the position of the element and the direction of the action head are inconsistent, the insulation front partition is scratched: the connection cannot continue to work, the change has not been abandoned, the requirements of the 0th happiness: the electrical connection is changed, the sealing rate is passed: the relative position of the internal organs is rotated. The test of the air-filled plastic test in Chapter 6.3 is not repeated. The test question: the sample is not lubricated, the force required to press the plug is not suitable. GB20951-1206 is applicable.
23 Flexible cable and its connection
GB2099.1-19 internal car chapter applies
24 Mechanical slope strength
G2099.1-1996 19% of the operating history
25 Heat resistance
GB2049.1-1996 This chapter applies
26 Screws, current parts and their connections
GB2099.1-1996 This chapter applies,
27 Creepage distance, electrical space and distance through window sealant R20.1-1996 This chapter is modified and created. Added:
27.101 For switches installed in the middle of switch rooms, creepage distance, electrical space through the specified distance should not be less than the value shown in Table 12.
Required electrical residence:
1. When the head is open, the narrow gap between each independent live part: 2: between the electrical parts and:
table 102
metal parts of the machine groove, if required to be insulated from the live parts (see [0.12]): 3. Machine gear parts: if required to be insulated from the fusible and metal parts [see 10113)! Medical seat, age and benefit board frequency setting and standard: support mourning clear switch bottom plate of the enterprise constant frame: fusible and metal parts:
electric 4 distribution:
4, when the head is separated, each independent live part is the same, 5. between the electrical parts and the metal parts of the machine, if required to be insulated from the live parts (see 10.102):. The metal parts of the mechanism, the requirements for the insulation of the surrounding parts and the insulation requirements of the brackets are as follows: 10.10: Check the screws and the installation of the base, cover and the metal push-on of the bottom of the spray-type switch, and the new parts.
JB/T10434.22Q04
, for the electrical parts of the switch with small structure, when the head is separated, this value can be reduced to 1.2mmL. Whether it is qualified or not, it can be checked by visual inspection.
? The resistance to abnormal heat, flame retardancy and end electric tracking of the insulation material GB2499.[—1996] is applicable.
29 Anti-rust performance
GB2099.1—19 is applicable.
Additional test for plugs with extended sheath
Do not go to this chapter.