JB/T 5860-1991 Rated parameters of relays and relay protection devices
Basic Information
Standard ID:
JB/T 5860-1991
Standard Name: Rated parameters of relays and relay protection devices
Chinese Name:
继电器及继电保护装置 额定参数
Standard category:Machinery Industry Standard (JB)
state:in force
Date of Release1991-10-17
Date of Implementation:1992-10-01
Some standard content:
Mechanical Industry Standard of the People's Republic of China
Rated parameters of relays and relay protection devices 1 Subject content and scope of application
5860-91
This standard specifies the rated parameters of relays and relay protection devices such as input excitation quantity, auxiliary excitation quantity and frequency. This standard applies to the rated parameters applied externally to relays and relay protection devices for secondary circuits of power systems. This standard does not apply to other parameters specified internally by relays and relay protection devices due to circuit requirements. Reference standards
Electrical terminology
Basic terminology
GB2900.17 Electrical terminology
3 Terms
Relays and relay protection devices
In addition to the terms of GB2900.1 and GB2900.17, this standard also uses the following terms. 3.1
Rated parameters
Parameters specified for relays and relay protection devices under given working conditions. Input excitation disk
Rated voltage
The rated values of AC voltage (effective value) are: 12, 24, 36, 100/√3, 100, 110, 220, 380V, and the rated values of DC voltage are: 5, 6, 12, 15, 24, 36, 48, 110, 220V. Rated current
The rated values of AC current (effective value) are: 0.5, 1, 2, 5A and these values multiplied by 10\; the rated values of DC current are: 0.15, 0.25, 0.5, 1, 2, 4, 8A and these values multiplied by 10\. Note: n is an integer.
Working range
When the rated voltage is 100V and above, the working range of input excitation is: AC voltage is 85% to 110% of the rated (effective) value; DC voltage is 80% to 110% of the rated (average) value. When the rated voltage is 60V or less, the working range of input excitation is: AC voltage is 90%-110% of the rated (effective) value; DC voltage is 85%-110% of the rated (average) value. b.
Note: The rated parameters of input excitation other than those in Articles 4.1 to 4.3 shall be specified in the product standard. 5
Auxiliary excitation disk
Rated voltage
The rated values of AC voltage (effective value) are: 24, 48, 100, 110, 220, 380V; the rated values of DC voltage are: 12, 24, 48, 60, 110, 125, 220, 250V. Approved by the Ministry of Machinery and Electronics Industry on October 24, 1991 and implemented on October 1, 1992
Rated current
The rated current value is not recommended at the moment.
5.3 Working range
The working range of auxiliary excitation voltage is:
JB586091wwW.bzxz.Net
a, 80%~110% of the rated value when 100V and above, b, 90%~110% of the rated value when 60V and below. 6
The rated value of frequency is 50, 60Hz.
Additional remarks:
This standard is proposed and managed by Xuchang Relay Research Institute of the Ministry of Machinery and Electronics Industry. This standard is drafted by Acheng Relay Factory of the Ministry of Machinery and Electronics Industry. The drafters of this standard are Zhou Shixian and Li Dianfa. 144
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.