title>JB/T 6313.1-1992 General provisions for electrical copper braided wire - JB/T 6313.1-1992 - Chinese standardNet - bzxz.net
Home > JB > JB/T 6313.1-1992 General provisions for electrical copper braided wire
JB/T 6313.1-1992 General provisions for electrical copper braided wire

Basic Information

Standard ID: JB/T 6313.1-1992

Standard Name: General provisions for electrical copper braided wire

Chinese Name: 电工铜编织线 一般规定

Standard category:Machinery Industry Standard (JB)

state:in force

Date of Release1992-06-26

Date of Implementation:1993-01-01

standard classification number

Standard Classification Number:Electrical Engineering>>Electrical Materials and General Parts>>K11 Bare Wire

associated standards

alternative situation:JB 2572-1979

Procurement status:neq DIN 46443, DIN 46444

Publication information

Publication date:1993-01-01

other information

Focal point unit:Shanghai Cable Research Institute of the Ministry of Machinery and Electronics Industry

Publishing department:Ministry of Machinery and Electronics Industry of the People's Republic of China

Introduction to standards:

This standard specifies the product classification, general technical requirements, inspection rules, packaging, transportation and storage of electrical copper braided wire. JB/T 6313.1-1992 General provisions for electrical copper braided wire JB/T6313.1-1992 Standard download decompression password: www.bzxz.net

Some standard content:

Mechanical Industry Standard of the People's Republic of China
General Provisions for Electrical Copper Braided Wire
Subject Content and Scope of Application
JB 6313.1-92
This standard specifies the product classification, general technical requirements, inspection rules, packaging, transportation and storage of electrical copper braided wire. This standard should be used together with JB6313.2, JB6313.3, etc. 2 Reference standards
GB2900.10
GB3953
GB4910
Electrical terminology Wires and cables
Electrical round pot wire
Tinned round copper wire
Test method for DC resistance of conductive wire core of wire and cable Test method for bare wire General rules
Test method for bare wire
Wire and cable delivery tray
Dimension measurement
Type size
Wire and cable delivery tray. Technical requirements
3 Symbols, codes and product markings||tt| |3.1 Symbols and codes
3.1.1 Series codes
Electrical copper braided wire
3.1.2 Classification by product structure to be levied
3.1.3 Classification by material characteristics
Tin (plating)
3.1.4 Classification by nominal diameter of single wire
0.20mm.**
3.1.5 Classification by product use characteristics
For loudspeaker sound chart
For shielding protection
3.2 Product marking
3.2.1 Products are indicated by model, specification and number of this standard. TZ
x ​​(omitted)
T (omitted)
3.2.2 Specifications of twill braided wire include nominal cutting area and number of spindles (only when there are two different structures of the same model and nominal cross section). The specification of braided wire for speaker voice coil is the nominal cross section. The specification of tinned copper braided sleeve for shielding protection is sleeve diameter. The specification of straight copper braided wire is the nominal cross section. Note: The number of spindles refers to the number of strands of a single copper braided wire product. 3.2.3 Marking examples
JB 6313.1-92
Nominal cross section is 25mm, 36 spindles, 15-type twill copper braided wire, expressed as: a.Www.bzxZ.net
TZ-15(36)25JB6313.2-92
Nominal cross section is 35mm, 10-type straight copper braided wire, expressed as: b.
TZZ-1035
JB6313.3—92
c Copper braided wire for speaker voice coil with a nominal cross section of 0.2mm, expressed as: TZQ0.2
JB 6313.292
d. Tinned copper braided sleeves for shielding protection with a sleeve diameter range of 16 to 24 mm are expressed as: TZXP-16~24JB6313.2--92
4 Technical requirements
4.1 Materials
4.1.1 Copper braided wires shall be made of TR-type soft round copper wires in accordance with GB3953. For single wires with a diameter of 0.10 mm or less, TY-type hard round copper wires in accordance with GB3953 may also be used. 4.2 Tinned copper braided wires (sleeves) shall be made of TXR-type tinned soft round copper wires in accordance with GB4910. 4.1.2 Surface quality
The surface of the product shall be smooth and free of oil stains, and shall not have various defects that are inconsistent with good industrial products. 4.3 Strands and their joints
The braided layer of copper braided wire and tinned copper braided wire (sleeve) shall not be missing strands, skipping strands, missing strands or broken strands. The strand joints shall be trimmed neatly.
5 Inspection rules
5.1 Products shall be inspected and qualified by the quality inspection department of the manufacturer before leaving the factory. The products leaving the factory shall be accompanied by a quality inspection certificate. 5.2 Products shall be inspected according to the specified test items. The definitions of type test (T), sampling test (S) and routine test (R) shall be in accordance with the provisions of GB4909.1. 5.3 The sampling quantity of the test shall be agreed upon by the supply and demand parties. If the demand party cannot make any requirements, it shall be determined by the manufacturer. If the test results of the sampling items are unqualified, double sampling shall be carried out for the unqualified items for a second test. If there are still unqualified items, 100% inspection shall be carried out.
5.4 The appearance of the products shall be inspected piece by piece with eyesight (normal vision). 6 Packaging, transportation and storage
6.1 Packaging
6.1.1 Products should be delivered in reels or coils. Each package should be of the same model and specification. If two or more wire segments are contained in one package, the connection between the two wires should be clearly marked. If there are special requirements, the number of wire segments should be indicated. 6.1.2 The wire reels used for reel packaging should comply with the provisions of GB4005.1 and GB4005.2. 6.1.3 The weight of each coil of coiled wire shall not exceed 50kg, or it can be negotiated by both the supply and demand parties. Products packaged in coils should be added with moisture-proof materials and moisture-proof measures. 6.1.4 Each package should be attached with a label indicating: a.
Manufacturer name and trademark;
Model and specifications;
Length, m;
Gross weight and net weight, kg;
Date of manufacture
Standard number
The packaging of export products should comply with relevant regulations. 6.1.5
Transportation and storage
JB6313.1-92
Care should be taken to avoid damage to the product during loading, unloading, transportation and storage. The storage environment requires ventilation, dryness and no corrosive gases. Additional notes:
This standard was proposed and coordinated by the Shanghai Cable Research Institute of the Ministry of Machinery and Electronics Industry. This standard was drafted by the Shanghai Cable Research Institute of the Ministry of Machinery and Electronics Industry, Shanghai Copper Materials Factory, and Beijing Electric Wire Factory No. 7. The main drafter of this standard is Yuan Hesheng.
Drafted by Chongqing Electric Wire General Factory,
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.