Chemical industry standard of the People's Republic of China
HG/T 3132-1998
L type cooling tower fan
L type cooling tower fan
1998 --03 -23 Issued
1999-01-01 Implementation
Ministry of Chemical Industry of the People's Republic of China Issued
WHG/T3132-1998
This standard is a revision of ZBJ72001-86 (L-type cooling tower fan) based on the continuous improvement of the design and manufacturing level of cooling tower fans. The measurement and evaluation of vibration and noise specified in this standard are equivalent to the mechanical vibration of machines with speeds ranging from 10 to 2001ev/s in ISO2372 (Basis of Estimated Vibration Standards): The aerodynamic performance of the fan complies with GB123588 "Test Methods for Aerial Performance of Ventilators"; The measurement and evaluation of fan noise complies with GB/T2888-91 "Methods for Measuring Noise of Fans and Roots Blowers". Compared with ZBJ72001-86 "L-type cooling tower fan", this standard has the following main differences: The standard is named "Type Cooling tower fan》:
This standard fan series is extended to nine models; the basic parameters for vibration measurement and evaluation of fans in this standard are selected from vibration intensity: This standard proposes technical specifications for the design of fans, and specifically proposes clear design regulations for fan couplings: This standard proposes electrical and instrumentation complete set configuration requirements for products. Appendix A and Appendix B of this standard are the appendices of the standard. From the date of implementation, this standard will be in line with ZBJ72001-86. This standard was proposed by China Chemical Equipment Corporation. This standard was approved by the Chemical Machinery and Standardization Technical Committee of the Ministry of Chemical Industry, and the drafting unit of this standard is Shanghai Chemical Machinery No. 2. The main drafters of this standard: Zhang Huanwu, Hu Shenmin, Weng Yinghao, Yang Baishun, Xu Jianying, www.category standard industry data free download 1 Scope
Chemical Industry Standards of the People's Republic of China
L-type cooling tower fan
L type cooling tower tan
HG/T 3132--1998
Replaces ZRJ 72001-86
This standard specifies the naming and basic parameters, requirements, test methods and inspection rules, marking, packaging and storage and transportation of L-type cooling tower fans (hereinafter referred to as fans).
This standard applies to mechanical ventilation cooling tower fans in circulating water cooling systems with working environment temperature not exceeding 70℃ and relative air humidity less than 100%. bzxZ.net
2 Referenced standards
The provisions contained in the following standards constitute the provisions of this standard before being cited in this standard. When this standard is published, the versions shown are valid. All standards will be revised, and parties using this standard should explore the possibility of using the latest versions of the following standards. GB 19190
GB 997-81
GB/T 1031—95
GB 1220—92
GB 1236—85
GB/T 1804—92
GB/T 2888—91
GB 3077—88
GB 3452. 1--92
GE9239—88
GB 9877. 188
GB 10095-88
GB 11352-89
GB11365--89
Packaging, storage and transportation pictorial symbols
Motor structure and installation form, code
Surface roughness parameters and values
Stainless steel bars
Test methods for aerodynamic performance of fans
Tolerances and fits Limit deviations of dimensions without tolerances Test methods for noise of fans and Roots blowers
Technical conditions for alloy structural steels
Type 0 rubber seals for hydraulic and pneumatic applications Dimension series and tolerances Mechanical vibrations-balance mass of rotating rigid bodies Lip seals for rotating shafts Structural dimension series Precision of involute cylindrical gears
Classification and technical conditions of carbon steel castings
Precision of bevel and hypoid gears
GB/TI3306--91 Labels
GB/T13384-92 General technical conditions for packaging of electromechanical products JB/T 1472-94
JC/T 281—94
Mechanical seals for pumps
Alkali-free and non-ferrous glass fiber cloth
YB/T 036.7—92 General technical conditions for forgings Approved by the Ministry of Chemical Industry of the People's Republic of China on 1998-03-23 and implemented on 1999-01-01
W3 Nomenclature and basic parameters
3.1 Type
HG/T3132-1998
The fan is an axial flow fan of the exhaust type. Its basic type is shown in Appendix A (Appendix to the standard). 3.2 Model
3.2.1 Model indication method:
(in alphabetical order of A, B, C)
Major modification bed
Nominal diameter im
3.2.2 Model example
Indicates impeller diameter of 8 meters, after the first improvement L80A160
3.3 Basic parameters
3.3.1 Series spectrum of fans According to impeller name
Series L42L
The basic parameters of the fan are specified in Table 2
Impeller diameter
Impeller speed range
Number of blades
Blade installation angle adjustment range
Air volume range
Total pressure range
Supporting electrical Machine power
4 Technical requirements
4.1 Design
4.1.1 Aerodynamic performance
35~5
The Chinese phonetic letter of the word "冷" for cooling tower fans is a few 160 kW cooling tower fans.
The price shall be negotiated by the supply and demand parties.
55602070
245165~
80~-17090~-160
185136~
115~155
110~150
155127~
-155117~136
170130~240170~280200~320
155~205
145~245
55~11090~13290-16011016016022537~55
4.1.1.1 The performance parameters of the fan such as air volume and total pressure shall comply with the provisions of Table 2. 4.1.1.2 The aerodynamic performance of the fan shall be optimized according to the parameters such as air volume, total pressure, power and speed. 4.1.1.3 The aerodynamic performance of the fan shall comply with the provisions of GB1236. And draw the waiting curves of air volume, total pressure and power. 4.1.2 Mechanical properties
HG/T3132-1998
4.1.2.1 The first-order critical speed of the fan coupling shaft system shall be at least higher than 20% of the working speed. 4.1.2.2 The connection between the coupling and the shaft end shall adopt an elastic coupling with automatic centering and error compensation functions. 4.1.2.3 The fan coupling components shall be subjected to dynamic balance correction test, and the balance accuracy level shall be in accordance with the provisions of Table 3. Table 3
Series code
Balance accuracy level
The fan impeller components shall be subjected to overall static balance correction test, and the balance accuracy level shall not be lower than G6.3 level specified in GB9239. 4.1.2.4
4.1.2.5 When the fan is running under normal load, the fan shall be 4.1.2.6 When the fan is installed on a reinforced concrete bag king cold unloading tower without vibration elimination foundation, the maximum vibration intensity of the gear box shall be in accordance with the provisions of Table 4 at full load.
Series code
L42, L47, L55
L60, L70, L77.L80
L85, L92
Gearbox high shaft centerline
Bearing seat housing
4.1.2.7 Gears of reduction box shall be designed according to high speed and heavy load gears. The gear tolerance shall not be less than 4.1.2.8 The transmission tolerance of the gear pair with matching teeth of spiral bevel gear and helical cylindrical gear shall comply with
The contact spots of gear pair meshing shall be in accordance with the provisions of Table 5. Gear category
Spiral bevel gear
Helical cylindrical gear
Mechanical seals for reduction box shall comply with 4.1.2.11 of JB/T1472
2 Skeleton oil seals shall comply with JB
4.1,2.13O-type rubber seals shall comply with
4.1,3Reliability
4.1.3.1The reliability design of the fan shall be based on the service life4.1.3.2The maintenance cycle of the fan and continuous operation of 8000 hours. 4.1.4Oil temperature and lubrication
Maximum vibration intensity
Along the tooth length direction
4.1.4.1When the fan is running under load, the maximum oil temperature in the gearbox shall not exceed 86℃. 4.1.4.2The gears shall be well lubricated, and the gearbox lubricating oil shall be N150 heavy-duty extreme pressure industrial gear oil, or other gear oils with equivalent performance.
4.1.5Electronic control device
4.1.5.1The electronic control device of the fan shall have good and reliable grounding. The electric control device shall be equipped with an on-site operating switch so that when the operator enters the fan for maintenance work, the electric power can be reliably cut off and controlled. 4.1.5.2
Electrical instrument matching
According to the needs, the user can match all or part of the following electrical instruments and equipment: HG/T 3132—1998
a) Use Y series outdoor motors, and the motors should comply with GB 997; b) The motor should be equipped with a bag protection device or a temperature rise control instrument; c) The reducer should be equipped with a monitoring instrument to control its oil temperature, oil level, machine vibration and other operating parameters; d) The monitoring instrument should have online monitoring and remote line control functions. 4.3 Manufacturing
4.3.1 In addition to complying with the requirements of this standard, the manufacture of fans shall also comply with the requirements of product drawings and technical documents approved through prescribed procedures.
4.3.2 Materials and purchased parts
4.3.2.1 All types of materials used in the manufacture of fans shall comply with the relevant national standards or industry standards. 4.3.2.2, The material grades used for the main parts of the fan shall comply with the provisions of Table 6. Other materials with performance not lower than that of the above materials may also be used. Table 6
Part Name
Half Coupling
Coupling Tube
Helical Gear Pair
Bevel Gear Pair
icr18Ni9r1
20CrMnTY
20crMnTI
Vinyl Ester Resin
Standard Code
GB1220
GB1220
GB 3077
GB 3077
Alkali-free Unshielded Glass Fiber Cloth
Steel castings shall comply with the provisions of GB11352.
Forgings shall comply with the provisions of YB/T036.7.
JC/T 281
or medium alkali glass fiber cloth
All accessories and purchased parts shall meet the requirements of the corresponding product standards and shall have product certificates. 4.3.2.5
4.3. 3 Processing
4.3.3.1 The surface of the casting shall be smooth and flat, and the attached molding sand, oxide scale, bubbles, gates, stomachs, burrs, etc. shall be cleaned up. The casting shall not have shrinkage cavities, cracks, sand holes, non-metallic inclusions and looseness that affect the strength. Repair welding is allowed. Before repair welding, the defects must be removed. The strength of the casting shall not be reduced after repair welding. The casting shall be aged before machining to eliminate the internal stress generated during casting. 4. 3, 3, 3
The surface of forgings shall be smooth and free of defects such as forging scars and cracks. 4. 3. 3. 4
After rough machining, the bad parts formed by casting or forging shall be subjected to corresponding heat treatment according to the material requirements. 4. 3. 3. 5
4.3.3.6The machining of gears shall comply with the provisions of 4.1.2.7 and 4.1.2.8, and the surface roughness of the tooth surface shall comply with the provisions of GB/T1031 and shall not exceed Ral. 6.
The limit deviation of the final tolerance size of the machined surface and the non-machined surface shall comply with the accuracy of IT14 and IT164. 3. 3. 7
of GB/T1804 respectively.
4.3.3.8The inner surface of the oil-containing surface such as the bearing seat of the gearbox shall be painted with vinegar oil paint, and the outer surface and other parts shall be painted according to the requirements of the drawings. 4.4 Installation
4.4.1 The blades and hubs must be assembled according to the numbers. 4.4.2 The assembly dimension deviation of the blades shall comply with the provisions of Table 7. wW. Series code of various US standard industry data free download
L42, L47, L55
L60.L70., L77.L80
L85, L92
HG/T 3132-1998
Maximum deviation of blade installation angle
Axial motion of blade outer edge
Maximum chord length difference of adjacent blades
4.4.3 The clearance between the outer edge of the impeller and the wind cylinder shall comply with the provisions of Table 8 and shall be uniform and consistent, and no sudden changes are allowed. Table 8
Series code
L42, L47, L55
L60, L70, L77, L80
L85, L92
4.4.4 The horizontal error of the reduction box base installation shall not exceed 0.1/1000mm. 4.4.5 The parallelism of the two coupling flange end faces shall not exceed 0.12mm. 4.4.6 After the fan is installed, the coupling should be rotated evenly by hand. 5 Tests and test methods
The distance between the blade and the wind pipe wall
15~-25
5.1 Material test
Material test shall comply with the provisions of relevant material standards. The material supplier shall provide all or part of the material test certificate according to the requirements of the fan manufacturer, including:
a) chemical composition;
b) mechanical properties.
5.2 Component test
5.2.1 According to the provisions of 4.1.2.4, the impeller component shall be subjected to the overall static balance correction test. 5.2.2 According to the provisions of 4.1.2.3, the coupling component shall be subjected to the dynamic balance correction test. 5.2.3 The conversion formula of balancing accuracy and the mass center offset of the rotating part is: e
Where: G balancing accuracy grade mm/s
mass center offset um
-rotating part working angular velocity, rad/s
allowable unbalance is in accordance with the provisions of Appendix B (Standard Appendix), 5.2.4
5.2.5 There shall be no more than two balancing weights in the same balancing weight plane, and the phase difference between the two balancing weights shall be less than 90°5.2.6 The appearance of the dynamic and static balancing weights shall be smooth and free of burrs, and they must be firmly fixed on the balancing workpiece. 5.2.7 No-load and load test of reduction gearbox
5.2.7. Every fan reduction gearbox shall be subjected to no-load running test. The no-load test shall be carried out by continuous operation at rated speed. After the pool temperature stabilizes, the running time shall be at least 20 minutes and shall meet the following requirements: a) No loosening of connectors and fasteners; b) No oil leakage or oil rush at sealing points and joint surfaces; e) The reduction gearbox shall run smoothly and normally without any shock or abnormal noise; d) The reduction gearbox oil shall not exceed 70℃ and the temperature rise shall not exceed 40℃. HG/T3132-1998
5.2.7.2 When necessary, the load test of the gearbox shall be carried out according to the following steps: a) The gearbox for the load operation test must first complete the no-load operation test specified in 5.2.7.1; b) Load 25% of the rated load and operate for 4 hours c) Load 50% of the rated load and operate for 2 hours; d) Load 75% of the rated load and operate for 1 hour; e) The loading test requirements shall comply with the provisions of a), b) and c) in 5.2.7.1. 5.3 Machine test
5.3.1 The aerodynamic performance test of the fan shall be carried out in accordance with the provisions of GB1236. 5.3.2 The test of the noise performance of the fan is generally carried out on the construction site, and the determination and limitation of the noise value shall be carried out in accordance with GB/T2888. 5.3.3 The mechanical operation test shall be carried out on the simulated tower according to the technical agreement of the two parties. 6 Inspection rules
6.1=The fan is inspected by the quality inspection department of the manufacturer
6.2 The inspection of the fan is divided into factory inspection and heavy inspection. 6.2.1 Factory inspection
6.2.1.1 Factory inspection items and requirements shall be in accordance with 4.3, 4.4, 5.1 and 56.2.1.2 Factory inspection shall be carried out for each fan.
6.2.2 Type inspection
6.2.2.1 Type inspection items and requirements
6.2.2.2 Sampling for type inspection shall be random
6.2.2.3 Type inspection shall be carried out in any of the following cases: a) product trial production, finalization and appraisal
b) when there are major changes in materials and processes
c) when the factory inspection results are different from the prototype inspection
d) when the national quality supervision agency proposes a type inspection
6.3 Inspection rules determination
6.3.1 Each fan shall be inspected in accordance with 6.2.1
6.3.2 Type inspection shall comply with 6.2.2. Requirements
Marking, packaging and storage
7.1 Marking
When the product is produced, any item
does not meet the requirements
and 5.3. The type inspection is determined to be qualified. If any one
does not meet the requirements, the factory inspection is determined to be unqualified. If it does not meet the requirements, the type inspection is determined to be unqualified. 7.1.1 The product label of the fan shall be set in a conspicuous position on the reduction box, and the label size and technical requirements shall comply with the provisions of GB/T13306. The label shall include the following contents:
a) Manufacturer's name;
b) Product model and name:
c) Main performance parameters:
d) Product number and manufacturing date.
7.1.2 The working rotation direction of the fan coupling should be indicated by a red arrow at a conspicuous position on the reduction box. 7.1.3 There should be a clear oil level limit line on the level gauge in the oil system. 7.2 Packaging
7.2.1 The exposed parts and unpainted machined surfaces of the fan parts should be coated with anti-rust grease and wrapped with waterproof materials before leaving the factory. 7.2.2 The fan is packaged according to the parts. The documents provided with the machine should be placed in a waterproof bag and packed into the packaging box together with the parts. The packaging should comply with the provisions of GB/T13384. The packaging, storage and transportation marks on the outside of the packaging box shall comply with the provisions of GBI9I. 7.2.3 The following contents shall be marked on the outer wall of the packaging box: a) Receiving unit, address;
b) Product name, model, factory number: c) External dimensions, gross weight;
d) Shipping unit, address,
7.2.4 Random documents include:
a) Packing list:
b) Product certificate;
c) Product instruction manual (including installation diagram). 7.3 Storage and transportation
7.3.1 The fan shall be stored in a clean, dry and ventilated warehouse according to the parts. When stored outdoors, protective measures shall be taken, and regular inspections and protective treatments shall be carried out according to the provisions of 7.2.1.
7. 3. 2 During transportation, measures shall be taken to prevent vibration or collision from causing damage to the product or packaging box. Appendix A (Appendix to the standard)
Schematic diagram of industrial series fans
Appendix B (Appendix to the standard)
100,000
50,000
2a,000
Various balanced sugar content orders per million revolutions allowable imbalance in mass 100
100g2000
100150
Maximum operating speed
Jco0oe
10001500
People's Republic of China
Chemical industry standard
L Cooling tower fan
HG/T3132—1998
Editor: China National Chemical Equipment Corporation
Political code: 100011
Printer: Beijing University of Chemical Technology Printing Factory
All rights reserved. No reproduction allowed
Format: 880×12301/16 Sheet 1 Number of words: 19.5 thousand words First edition: September 1998 First printing: September 1998 Number of copies: 1—100
Cost: 10 yuan
866120