Engineering Construction Standard Full-text Information System
National Standard of the People's Republic of China
Civil Building Lighting Design Standard
133-90
1991Beijing
Engineering Construction Standard Full-text Information System
W Engineering Construction Standard Full-text Information System
National Standard of the People's Republic of China
Civil Building Lighting Design Standard
133-90
Editor Department: Former Ministry of Urban and Rural Construction and Environmental Protection of the People's Republic of China Approval Department: Ministry of Construction of the People's Republic of China Date of implementation: March 1, 1991
Engineering Construction Standards Full Text Information System
Engineering Construction Standards Full Text Information System
Notice on the release of the national standard "Lighting Design Standard for Civil Buildings"
(90)Jianbiaozi No. 248
According to the requirements of the State Planning Commission's Document No. Jizong [1984] 305, the "Lighting Design Standard for Civil Buildings" jointly formulated by the China Academy of Building Research and relevant units has been reviewed by relevant departments. The "Lighting Design Standard for Civil Buildings" GBJ133-90 is now approved as a national standard and will be implemented on March 1, 1991. The Ministry of Construction is responsible for the management of this standard. The China Academy of Building Research is responsible for specific interpretation and other work. The Ministry of Construction's Standards and Norms Research Institute is responsible for organizing its publication and distribution. Ministry of Construction of the People's Republic of China
May 18, 1990
Engineering Construction Standards Full Text Information System
Engineering Construction Standards Full Text Information System
Preparation Instructions
This standard is compiled by the China Academy of Building Research in accordance with the requirements of the State Planning Commission [1984] Jizong No. 305, and is jointly compiled with relevant design, scientific research and colleges and universities.
During the preparation of this standard, the preparation team conducted extensive investigations and studies, carefully summarized the practical experience of civil building lighting design in my country, referred to relevant international standards and foreign advanced standards, carried out scientific research and experimental verification work on major technical issues, and widely solicited opinions from relevant units across the country. Finally, the Ministry of Construction reviewed and finalized the draft together with relevant departments.
Since this standard is compiled for the first time, during the implementation process, we hope that all units will combine engineering practice and scientific research, carefully summarize experience, and pay attention to accumulating information. If you find that there is a need for modification and supplementation, please send your opinions and relevant information to the National Standard Management Group of "Civil Building Lighting Design Standard" of the Institute of Building Physics, China Academy of Building Research (No. 19 Chegongzhuang Street, Beijing, Postal Code 100044) for reference in future revisions. Ministry of Construction of the People's Republic of China
May 1990
Engineering Construction Standards Full Text Information System
W.bzsoso.cOmEngineering Construction Standards Full Text Information System
Chapter 1 General
Chapter 2 Illumination Standards
Section 1
General Provisions
Industry News
Section 2 Illumination Standard Values
Chapter 3 Lighting Quality
Section 1 Illumination Uniformity
Section 2 Glare Limitation
Section 3
Section 4
Chapter 4||t t||Light source color
Reflectance ratio and illuminance ratio…
Lighting design
Section 1
Section 2
Section 3
Appendix—
Appendix 2
Appendix 3
Lighting methods and types of lighting
Light sources and lamps
Lighting design requirements
Glossary
Lamp brightness limit curve and its application method Explanation of terms used in this standard
Additional notes
Engineering Construction Standard Full Text Information System
(15)
... (18)
Engineering Construction Standard Full Text Information System
Chapter 1 General
Article 1.0.1 This standard is formulated to make the lighting design of civil buildings meet the requirements of building functions and protecting people's eyesight health, and to achieve energy conservation, advanced technology, economic rationality, safe use and convenient maintenance. Article 1.0.2 This standard applies to the lighting design of newly built, rebuilt and expanded public buildings and residences.
Article 1.0.3 In addition to complying with this standard, the lighting design of civil buildings shall also comply with the provisions of the relevant current national standards and specifications. Engineering Construction Standard Full-text Information System
Engineering Construction Standard Full-text Information System
Chapter II
Illumination Standard
Section I
General Provisions
Article 2.1.1 The standard value of illumination for civil building lighting shall be classified according to the following series: 0.5, 1, 2, 3, 5, 10, 15, 20, 30, 50, 75, 100, 150, 200, 300, 500, 750, 1000, 1500 and 20001x. Article 2.1.2 The standard value of illumination refers to the average illumination value on the reference plane of the work or living place.
Article 2.1.3 The illumination standard value is set at three values: high, medium and low according to the different activities or operation categories of various buildings. Designers should select the appropriate standard value according to the building grade, functional requirements and usage conditions. Generally, the middle value should be selected. Article 2.1.4 When designing lighting, the degree of illumination reduction caused by the attenuation of the light source, dust accumulation of lamps and pollution on the surface of the room should be divided by the maintenance factor in Table 2.1.4.
Maintenance factor
Characteristics of environmental pollution
Serious pollution
Workrooms or places
Residential bedrooms, offices, restaurants, reading rooms, drawing rooms, etc.
Store business halls, waiting rooms, boat rooms, cinemas
Theater auditoriums, etc.
Engineering Construction Standards Full-text Information System
Incandescent lamps, fluorescent lamps,
High-intensity gas discharge lamps
Halogen tungsten lamps
W Engineering Construction Standards Full-text Information System
Section 2 Standard values of illumination
Article 2.2.1
Provisions.
The standard illumination value of library building lighting shall comply with the provisions of Table 2.2.1 Standard illumination value of library building lighting
Reference plane and its height
General reading room, children's reading room,
study room, mounting and repair room, art room
Old readers' reading room, rare book and map reading room
showroom, catalog hall (room), cashier's hall
(room), audio-visual room, microfilm reading room
Readers' lounge
Open transport and transmission equipment
Article 2.2.2
.
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.25m vertical plane
0.75m horizontal plane
Standard illumination value (lx)
The standard illumination value of office building lighting shall comply with Table 2.2.2 Standard illumination value of office building lighting
Reference plane and its height
Office, lecture hall, conference room, reception room, display room Office, business hall
Work with visual display screen
Design room, drawing room, typing room
Binding, copying, printing, archive room
Duty room
0.75m horizontal plane
Workbench horizontal plane
Actual working surface
0.75m horizontal plane
0.75m horizontal plane
Standard value of illumination (ix)
Note: For work with visual display screen, the vertical illumination on the screen should not be greater than 1501x. Engineering Construction Standard Full Text Information System
Engineering Construction Standard Full Text Information System
Article 2.2.3
Regulations.
The standard illumination value of store building lighting shall comply with the standard illumination value of store building lighting in Table 2.2.3
One area
General store
Business hall
Display cabinet, window
Indoor vegetable market business hall
Self-service shopping mall business hall
Fitting room
Cashier
Reference plane and its height
0.75m horizontal Surface
Counter surface
1.5m vertical surface
Plane where goods are located
0.75m horizontal surface
0.75m horizontal surface
Standard illumination value (Ix)
Vertical surface at 1.5m height of fitting position
Cash counter surface
0.75m horizontal surface
Note: Display cabinets and display windows refer to those that display key and new products. Section 2.2.4
2.2.4.
The lobby corridor
The audience lounge
The standard illumination value of the theater building lighting shall comply with the standard illumination value of the theater building lighting in Table 4
Engineering 4 Construction Standard Full Text Information System
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
The standard illumination value ( x)
Engineering Construction Standard Full-text Information System
VIP room, costume room, prop room
Make-up room
Projection room
Actor's lounge
Rehearsal hall
General area
Make-up table
General area
Sound, light, and electricity control room
Art room, scenery painting room
Box office
Article 2.2.5Www.bzxZ.net
Regulations.
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
Vertical plane at 1.1m height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Control panel
0.75m horizontal plane
Ticket counter
Continued Table 2.2.4
Standard illumination value (Ix)
The standard illumination value of hotel building lighting shall comply with the hotel building lighting in Table 2.2.5. Standard value of illumination
Dressing table
Reference plane and its height
General activity area
Desk
Bathroom
Reception room
Main restaurant, room service desk, bar counterWestern restaurant, bar, coffee shop, dance hallEngineering construction standard full text information system
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
1.5m high vertical plane
0.75m Horizontal plane
0.75m horizontal plane
Standard value of illumination (Ix)
Full-text information system of engineering construction standards
Grand banquet hall, general service desk, main restaurant counter, foreign currency exchange
Foyer, lounge
Gym, equipment room, steam room, swimming pool
Amusement hall
Bowling
Kitchen, laundry, canteen
Food preparation, cooking, catering
Small items storage
Note: @
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.5
Standard value of illumination (Ix)
When there is no local lighting such as desk lamps in the guest room, the illumination of the general activity area can be increased by one level②The illumination value of the barber bar is applicable to the barber shops of ordinary guest houses and hotels. Article 2.2.6
Regulations.
Living room, bedroom
The standard illumination value of residential building lighting shall comply with Table 2.2.6
Standard illumination value of residential building lighting
Standard illumination value (Ix)
General activity area
Writing, reading
Engineering Construction Standard Full-text Information System
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
W Engineering Construction Standard Full-text Information System
Living room, bedroom
Bedside reading
Fine work
Dining room or square hall, kitchen
Bathroom
Stairwell
Article 2.2.7
2.2.7 provisions.
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.6
Illumination standard value (Ix)
The illumination standard value of railway passenger station building lighting shall comply with the illumination standard value of railway passenger station building lighting in Table 2.2.6
Reference plane and its height
Ordinary waiting room, mother-child waiting room, ticket office, VIP room, soft seat waiting room, ticket office, broadcasting room, dispatching room, driving plan room,
Customs office, public security verification office, information office, ticket supplement office||tt| |Entry hall, baggage check-in and claim
place, small luggage storage
ticket inspection office, ticket counter, ticket counter, check-out and handover counter, customs inspection bill
storage room (warehouse)
public security duty room
covered platform, entrance and exit tunnel, platform
uncovered platform, pedestrian bridge, station square Article 2.2.8
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
standard illumination value (Ix)
The standard illumination value of building lighting of port passenger stations shall comply with the table Engineering Construction Standard Full Text Information System75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.5
Standard value of illumination (Ix)
When there is no local lighting such as desk lamps in the guest room, the illumination of the general activity area can be increased by one level②The illumination value of the barber bar is applicable to the barber shops of ordinary guest houses and hotels. Article 2.2.6
Regulations.
Living room, bedroom
The standard illumination value of residential building lighting shall comply with Table 2.2.6
Standard illumination value of residential building lighting
Standard illumination value (Ix)
General activity area
Writing, reading
Engineering Construction Standard Full-text Information System
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
W Engineering Construction Standard Full-text Information System
Living room, bedroom
Bedside reading
Fine work
Dining room or square hall, kitchen
Bathroom
Stairwell
Article 2.2.7
2.2.7 provisions.
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.6
Illumination standard value (Ix)
The illumination standard value of railway passenger station building lighting shall comply with the illumination standard value of railway passenger station building lighting in Table 2.2.6
Reference plane and its height
Ordinary waiting room, mother-child waiting room, ticket office, VIP room, soft seat waiting room, ticket office, broadcasting room, dispatching room, driving plan room,
Customs office, public security verification office, information office, ticket supplement office||tt| |Entry hall, baggage check-in and claim
place, small luggage storage
ticket inspection office, ticket counter, ticket counter, check-out and handover counter, customs inspection bill
storage room (warehouse)
public security duty room
covered platform, entrance and exit tunnel, platform
uncovered platform, pedestrian bridge, station square Article 2.2.8
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
standard illumination value (Ix)
The standard illumination value of building lighting of port passenger stations shall comply with the table Engineering Construction Standard Full Text Information System75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.5
Standard value of illumination (Ix)
When there is no local lighting such as desk lamps in the guest room, the illumination of the general activity area can be increased by one level②The illumination value of the barber bar is applicable to the barber shops of ordinary guest houses and hotels. Article 2.2.6
Regulations.
Living room, bedroom
The standard illumination value of residential building lighting shall comply with Table 2.2.6
Standard illumination value of residential building lighting
Standard illumination value (Ix)
General activity area
Writing, reading
Engineering Construction Standard Full-text Information System
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
W Engineering Construction Standard Full-text Information System
Living room, bedroom
Bedside reading
Fine work
Dining room or square hall, kitchen
Bathroom
Stairwell
Article 2.2.7
2.2.7 provisions.
Reference plane and its height
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
Continued Table 2.2.6
Illumination standard value (Ix)
The illumination standard value of railway passenger station building lighting shall comply with the illumination standard value of railway passenger station building lighting in Table 2.2.6
Reference plane and its height
Ordinary waiting room, mother-child waiting room, ticket office, VIP room, soft seat waiting room, ticket office, broadcasting room, dispatching room, driving plan room,
Customs office, public security verification office, information office, ticket supplement office||tt| |Entry hall, baggage check-in and claim
place, small luggage storage
ticket inspection office, ticket counter, ticket counter, check-out and handover counter, customs inspection bill
storage room (warehouse)
public security duty room
covered platform, entrance and exit tunnel, platform
uncovered platform, pedestrian bridge, station square Article 2.2.8
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
0.75m horizontal plane
standard illumination value (Ix)
The standard illumination value of building lighting of port passenger stations shall comply with the table Engineering Construction Standard Full Text Information System