GB 19510.11-2004 Lamp controlgear Part 11: Special requirements for electronic inverters and frequency converters for high-frequency cold-start tubular discharge lamps (neon lamps)
Some standard content:
TC5 29. 140. 99
National Standard of the People's Republic of China
GB 19510,11—2004/IEC 61347-2-10:2000 Lamp controlgear-Purt11: Particulnr requirements for clcctronic invcrtors andconverters for high-frequency operation of cold start tubular discharge lamps(neontubes)
(IEC 61347-2-10.20m0.T:
2004-05-10 Issued
General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China Standardization Administration of the People's Republic of China
2005-02-01 Implementation
Normative referencesbZxz.net
General requirements
Test instructions
Terminals
Earthing devices
Prevention and insulation of accidental contact with live parts
Prevention and insulation Practice
Dielectric strength,
Thermal test of the group
Normal state·
Abnormal state·
Fault condition
Distance and electrical interruption
Protection circuit
Narrow nails, installed components and reverse connection
Consideration of fire prevention and front leakage current initiation
Corrosion
23 No-load rated shaft platform electrical point and rated shaft output certificate
B1951D.11—2004/IEC 61347-2-10;2000 Appendix A (Existing Normative Screening) Tests for Determining Whether Pregnant Electrical Components Are Potentially Causing Electric Shock Appendix B (Normative Parts Screening)
General Requirements for Control Devices of Thermally Protected Lamps Appendix C (Normative Appendix)
Appendix (Normative Appendix)
Appendix E (Normative Appendix)
Appendix F (Normative Instructions)
Appendix G (Normative Appendix)
Appendix H (Normative Appendix) Appendix 1 (normative appendix)
Special requirements for electronic control of lamps with thermal protection
Test requirements for heating of thermally protected lamps
Application of test chamber in test chamber
Derivation of pulse current value
Appendix 1 (normative appendix)
Measurement method for voltage and current of output circuit of electronic converter and frequency converter for dense rainbow lamp |.9 All technical contents of this part are mandatory. Preface
G19510 lamp control device 3 is divided into 1 part: Part 1: General requirements and safety requirements, GR19510.11-2Q04/1EC61347-2-10:20Q0--Part 2: Special requirements for automatic start-up (except glow actuators)-Part 3: Special requirements for DC-AC electronic step-down converters for high-efficiency lamps; Part 4: Special requirements for hybrid electronic ballasts for fluorescent lamps; Part 5: Special requirements for direct current electronic ballasts for Menton lighting Particular requirements for ballasts: Part 6: Particular requirements for ballasts for public lighting; Part 11: Particular requirements for inverters and converters for cold-start discharge lamps (except fluorescent lamps); Part 12: Particular requirements for ballasts for lighting; Part 13: Particular requirements for ballasts for electric lamps (except fluorescent lamps); Part 14: Particular requirements for inverters and converters for cold-start discharge lamps (radio lamps); Part 15: Particular requirements for ballasts for electric lamps (except fluorescent lamps); Part 16: Particular requirements for ballasts for electric lamps (except fluorescent lamps); Part 17: Particular requirements for ballasts and converters for electric lamps (radio lamps) Part 12: Particular requirements for miscellaneous electronic devices for lamps: This part is the first part of the control devices of the plan. This part should be used together with GB19510.1. It is formulated after supplementing or amending the corresponding clauses of GB19511. This part is equivalent to the English version of IFC.61317-2-10: Control devices for 200G lamps Part 2-10: Particular requirements for converters and receivers for high-frequency cold-start high-efficiency electric lamps (needle lamps). This part is equivalent to the English version of IFC.61317-2-10: Part 2-10: Particular requirements for converters and receivers for high-frequency cold-start high-efficiency electric lamps (needle lamps) ,)\F7317-210\Change\Part "EC513471 Standard" to G"10.11\Delete the front of 61347-2-0, change 617-2-0 c) Replace the "Note:\ The symbols in the form can be used as decimal points\,\) For some international standards cited in 151347-1:20 that are adopted as Chinese standards, this part uses these international standards as Chinese industry standards instead of the corresponding international standards. Most of the international standards that are not equivalent to those adopted as Chinese standards are introduced in this part (see Chapter 2 of this part). B19510.11 is one of the national standards for control devices of tungsten lamps. It lists the design structures of these national standards and their corresponding international standards, as well as the representative national standards: B1951.1 Control devices for tungsten lamps Part 3: General requirements and safety requirements IEC51310-1; Control devices for tungsten lamps Part 3: Special requirements for starting devices (except super-light actuators) (IEC61347-2-1); G19510.3 Control devices for tungsten lamps Part 3: Special requirements for DC/AC step-down conversion terminals for tungsten filament lamps (IEC61347-2-1); 2).
GBIS Slu.4 Lamp controlgear
Part 4 Special requirements for variable current for flame retardant use (IEC 61347-23, GB 111514-19941
GB19510.55 Lamp controlgear Part 5, Connection requirements for inter-current devices for general lighting 8CB19510.11-2004/[FC61347-2-10, 2000 (IEC 61347-2-4)
R19510,6 Lamp controlgear
Part 1: Special requirements for high-frequency current storage for public transportation (IEC 6.347-2-5)
CB:9510.7 Lamp controlgear
(IEC 6.347-3-6);
Part 7: Particular requirements for DC electronic ballasts for aircraft use (IEC 61347-2-8, GB 8313-993; GB 19510.5 Lamp controlgear Part 1: Particular requirements for ballasts for high-efficiency lamps (excluding fluorescent lamps) (IEC 61347-2-S, GB 19510.5 Lamp controlgear Part 2: Particular requirements for ballasts for high-efficiency lamps (excluding fluorescent lamps) (IEC 61347-2-S, GB 19510.5 Lamp controlgear Part 3: Particular requirements for ballasts for high-efficiency lamps (excluding fluorescent lamps) (IEC 61347-2-8, GB 19510.5 Lamp controlgear Part 1: Particular requirements for ballasts for high-efficiency lamps (excluding fluorescent lamps) (IEC 61347-2-S, GB 19510.5 1434515933: CB1J510.11 & Lamp control devices 11: Part 11: Particular requirements for high-frequency cold-shoulder-driven tube-shaped lamps (driving lights) electronic inverters 3 ([IEC6 34?-2-10); 19510.12 Lamp control devices Part 2: Part 2: Particular requirements for lamps and lanterns (IEC51347-2-17. Part A, B, Appendix C, Appendix Appendix D, Appendix E, Appendix F, Appendix G, Appendix II and Appendix I are normative appendices. This part was proposed by the China National Lighting Industry Federation. This part is under the jurisdiction of the National Lighting Appliance Standardization Technical Committee (CSB-S/TC224). The drafting units of this part are the National Electric Light Source Quality Supervision and Inspection Center, Beijing Electric Light Source Research Institute, and the drafting persons of this part are Tu Yuli. Anzuodian, Yu Anhong, Lu Rongshu, Hang Nian, Wu Guoming, Qiu Hui, Fan Xiaoping, R. B19510.11—2004/1EC61347-2-102000 This part and the various subsections of B195:0112 in the applicable clauses of GH19510.1 specify the applicable scope of this clause and the implementation sequence of various tests, and also specify necessary supplementary requirements. The parts of GB19510.2 to GB19510.12 are separate texts and do not correspond to each other. If this part refers to the basic requirements of GB19510.1 by saying "according to the first requirement of GB19510.5", then this sentence means to follow all the requirements of that clause, but it is obviously not applicable to GB19510.2 to GB19510.10.1 Scope
GB 19510,11-2004/1FC: 61347-2-10:2000 Lamp control gear
Part 11: Particular requirements for electronic inverters and converters for high frequency start tubular discharge lamps (pencil lamps) This part specifies the special requirements for electronic inverters and converters for commercial frequency cold cathode discharge lamps. Such inverters and converters are used in signal equipment using discharge tubes and are directly connected to a power supply voltage of 1000V or 50Hz below 1000V AC or 1000V self-driving. The output voltage is 1V~1CV. The value of 1i is not specified in the input, and the value can be 15cx The following two types of converters and frequency converters are specified, Class A and Class B requirements: A converter or frequency converter: The frequency range is 0-5kHz, the output and peak value of the final return shall not exceed 5000V, the input current is 25mA (effective value) and the output current is 50mA (sample value). The power supply voltage does not exceed 250V or 250V at 0Hz or 60Hz. Due to the limitation of the power supply and power rating, the output power of the A converter or frequency converter shall not cause electric shock hazard. In Japan, the output voltage can reach 5V.
Class B inverter or frequency converter: refers to the inverter or frequency converter that operates with a negative output voltage of no more than 5CV, a negative output voltage of no more than 100V between the terminals within the frequency range of Hz100kHz, and a maximum output current of 200A (effective value) and 400mA (peak value). 1: The output inductor of Class B inverter or frequency converter needs protection. Note: In Japan, the output voltage of Class B inverter should not exceed 5V. The secondary output group should not be grounded. In order to verify the safety of the inverter or frequency converter, their performance must be checked: However, due to the current characteristics of the neon lamp, this part specifies the reference voltage to ensure repeatable test results. The maximum rated operating temperature of the group is not applicable to this part. 2 Normative reference documents
The clauses in the following documents become the clauses of this part through the reference of this part of GB1916. For referenced documents with a date not specified, all subsequent revisions (excluding errata) or static versions are not applicable to this part. However, parties that have reached agreement on this part are encouraged to study whether the updated versions of these documents can be used. For any referenced documents without a date specified, their latest versions are applicable to this part.
This part adopts the normative references given in Chapter 2 of H19510.1 to modify the following normative references. GH19510.T lamp control concentration Part: - Sensitivity requirements (GB1951U.1-2004IEC61S47-1:2050
1sUSE4:1984Safety colors and safety-y signs (Satetypolursandsafe-ysigns) 3: Definitions
This part adopts the definitions in Chapter 8 of GB1S515.1 (except for definitions in 4.11, 5.1G.3.17) and the following definitions 3.1
Tube-shaped cold-electrode discharge lamp (cold-electrode discharge lamp) ubilurcoldlhudedischarlamp (aeunLube) is a tube that may have an electric discharge in addition to the material of the electric discharge lamp, and does not require external heat during the starting process, that is, it emits electrons through field effect emission. This lamp is filled with inert gas (or a mixture of inert gases), and may also be filled with vapor. The lamp may be coated with reverse-
GB 195FD. 11—2004/IEC 61347-2-10,2D00 optical material rating.
No-load rated output voltage Unar-lnadratedantpntvoltagef. The maximum rated voltage between the output terminals or between the entire connected circuit of a converter or frequency converter connected to a rated power supply at rated frequency when the transmission line is not loaded. The voltage is 1/2 of the effective value or peak value, whichever is greater. 3.3
Converter
An electronic converter that can convert alternating current into alternating current. 3.4
An electronic converter that can convert an alternating current power supply of one frequency into an alternating current power supply of another frequency. 3.5
Frurth-leakage protective devce ground current protector
When a ground fault occurs between any component of the high-voltage output circuit and the ground wire, the output power of the converter or transformer can be cut off.
Open circuit protector5
Furth-leakage protective device
When a ground fault occurs between any component of the high-voltage output circuit and the ground wire, the output power of the converter or transformer can be cut off.
Open circuit protector5
Furth-leakage protective device
When a ground fault occurs between any component of the high-voltage output circuit and the ground wire, the output power of the converter or transformer can be cut off.
Open circuit protector10.1 Section 6 Performance requirements and the following requirements: Converters and inverters shall be classified according to their no-load output voltage, rated operating power and output current range as follows: 1) Class A converter or inverter,
b) Class B converter or inverter,
Class B converter or inverter may have more than one output current. In this case, each terminal shall comply with the above provisions. 7 Marking
7.1 Marking content
G19510.11—2004761347-2-10, 2000 Electronic converters for cold-start tubular discharge lamps operating at high temperatures shall comply with the requirements of B195.1.2 and be marked with the following mark:
B195 10.1.1 a6) cd and the contents of clause 1. According to the requirements of GH/T5465.2 and Figure 1 of [ISO3864], the high voltage warning instructions shall be marked on the independent electronic inverters and transformers. For example, the words "high voltage" and a power symbol shall be used. This mark shall be marked on the outer surface of the inverter or frequency converter to make it clear. It is not necessary to mark the whole type of inverter, because its mark is the same as the marked inner part, and the applicable Class A or B flame symbol shall be used.
7.2 Supplementary markings
In addition to the above mandatory markings, the following applicable markings shall also be marked on the inverter or frequency converter, or in the manufacturer's product catalog or manual;
G1S5 13.171), k>, m>, m>, etc. If the inverter or frequency converter is composed of more than one independent component, the necessary information of other related components (especially DC power supply or inductor) should be marked on the output component: - the range and efficiency, diameter and length of the lamp applicable to the inverter or frequency converter; - if the inverter or frequency converter has integral leads, the recommended lead type and the maximum lead length should be marked in detail:
- instructions on applicable installation tables and installation methods; instructions on applicable grounding methods (including connectors of the inverter or frequency converter): the following notes should be marked according to the protection circuit in the inverter or frequency converter: ||tt ||1) If the output terminal is not connected to the ground terminal, the mark is: ".kV". If one output terminal is connected to the ground, the mark is "ground-.kV". For example: 4kV! If the middle point of the output terminal is connected to the ground terminal, the mark is "…-ground-.kV". For example: 3-ground-3V). This marking form is not used in Japan.
For Class 4 converters or transformers, the reading is the actual value. For Class B converters or transformers: the value is 0.5% of the effective value or the peak value. The larger value is used. 2) Output voltage when installed with a certain load:
The independent output line of the converter or transformer should be marked with the applicable mark in the above 1) and 2). 8 Wiring terminals
According to the requirements of Chapter 8 of GB1U510. "And the following requirements: The converter or transformer equipped with lead wires shall comply with the corresponding requirements of GB7HU1. 9 Grounding equipment
According to the requirements of Chapter 5 of GB9510.1 with the following requirements: For Class B converters or transformers, the grounding terminal is connected to the common components of the output line:, except for the following circumstances, the grounding terminal is connected to a component of the output line or any component of the output line through a device that can detect the fault current. The grounding terminal is not directly connected to the sensing terminal, and the output component can reach the ground potential through the internal circuit.
Compliance is checked by visual inspection.
GB 1951D.11—2004/IEC: 61347-2-10;200C Note: In Japan, this requirement is not applied.
10 Measures to prevent accidental contact with live parts shall comply with the requirements of Chapter 10 of GB1SE1C.1 and the following requirements: 101 After a severe circuit breaker condition occurs, the residual charge between the terminals of the inverter and the frequency converter shall not exceed 45u.
Compliance is checked by measurement
10.2 If the output load circuit components of the converter or processor are grounded, or are suitable for grounding through their internal circuits, the insulation barrier between the input line and the output line should be composed of double insulation or strong insulation (see Chapter 12 Safety requirements: Test voltage). Compliance is checked by the test described in Chapter 12 (test voltage). 11 Moisture-proof and insulation
According to the requirements of GB19510.1 Section 11 and the following requirements: The electrical penetration between the A-type converter or inverter and the metal box with an area of not less than 31001m\ placed on any part of the outer surface of the converter or inverter shall not exceed 50PF: During the test, the converter shall not be operated, 12 uniform electric strength
According to the requirements of GR19510,1 Section 12 and the following requirements: Test voltage:
The test voltage of the converter and inverter is as follows: When the output load circuit is connected to an external metal part, the input test voltage is twice the rated input voltage plus 1V. - When the input line is connected to an external metal part, the test voltage of the output terminal is twice the rated output voltage without load: In Japan, a 1.5-screen test voltage should be used. The heat-resistant test device or transformer and the supporting frame of group 13 shall not have excessively high pressure under normal or abnormal conditions, which will impair its safety. Its compliance is checked by the tests specified in Chapters 14, 15 and 16. 14 Normal Condition
14.1 Install the converter or inverter in its normal operating position according to the manufacturer's instructions and GB19510.1 (manufacturer's instructions). After heating, test it in the long convection wind test box specified in Appendix F of GB19510.1. 14.2 Use the specified load voltage R (see Appendix I) and connect the standard power supply voltage to operate the converter or frequency converter. For converters or frequency converters that can provide an approximately stable output current, the power supply voltage should be maintained at the nominal value until the stable state is reached.
For converters or frequency converters that cannot provide an approximately stable output current, stop the power supply until the output current reaches the standard value specified by the converter or frequency converter's mark. Then, maintain the voltage at the nominal value. The output current is obtained until it reaches a steady state. 14.3 If the converter or frequency converter has more than one output terminal, a suitable load resistor (R,) shall be connected to each pair of output terminals. 14.4 During the test, the temperature on the relevant components shall not exceed that specified in Table 12.1 and Table 12.2 of GB70CC, but 15 Abnormal band rate
15.1 Place the converter or frequency converter under the test record specified in Section 15.2, and follow the instructions on the manufacturing surface (if specified, including the use of heat plates and partitions) to increase the voltage to the most unfavorable voltage between %~110 of the rated power supply voltage, and operate the converter or frequency converter for 1 hour. The test shall be carried out in a large convection wind box specified in Appendix F of GB19510.1. CB19510,11—2004/1E 61347-2-10.200015.2 The tests shall be carried out under the following conditions to reveal the most unfavourable situation. The time between the tests shall not exceed 15 days. 1) Carry out the conditions 1) to 3) in sequence. b) Carry out the conditions 2) and 3) simultaneously. 3) Short-circuit the auxiliary line.
If there is more than one output circuit, short-circuit all the output circuits at the same time. 1) If the transformer or the equipment has a device to cut off the main power supply in case of a fault in the output circuit, this test can be omitted. 2) Connect the load socket R (see attached) to the output terminal. If the converter is a frequency converter and it has more than one input terminal, connect the electrical resistor K to each pair of output terminals. 3) Install the converter on a metal plate with a uniform length of 1m. The material of the metal plate shall be specified by the manufacturer. If the manufacturer does not specify, it shall be made of steel or aluminum (select the one that provides the most favorable condition). 2: In addition, other materials may be required.
15.3 During the test period specified in 15.2 and at the end of the test, no faults that may endanger the safety of the converter or transformer are allowed.
The loss of any external transformer on the external transformer of the converter shall not exceed double. In addition, the output current shall not exceed the value specified in Chapter 23 of the standard.
16 Fault conditions
According to the requirements of Chapter 4 of B19510.1, the following requirements shall be set: 16.1 In the reverse state, the output current shall not exceed the nominal value specified by the manufacturer. 1.5: a. Connect the output terminal to the circuit or, if the converter or inverter is equipped with a drop protection device, connect the output terminal to the resistor R described in Appendix 1.:
6) The grounding support with a slightly impermissible impedance is cut on both ends of the output. Method: If the slow ground loss is connected to the temporary output line, the user can change the output according to the requirements of the first week. If the converter is replaced according to the requirements of the first week, the converter does not need to be tested as described in 16.16) in the output environment. The test should be carried out according to the requirements of GB195:0.1 Chapter 15. The following requirements are required: 17.1 The converter group or converter should be equipped with an insulator material and pass the Japanese standard.
17.2 The lead wire between the output terminal of the controller or inverter and the discharge tube shall be of the type suitable for the inverter or frequency converter, and shall meet the following requirements:
) Suitable for working under high voltage
b) Suitable for working under the output voltage of the inverter or frequency converter: 18 Distance and electrical spacing
shall comply with the requirements of GB19510.1 Section 1 and the following requirements: 1 Regardless of whether the inverter or frequency converter is installed in a high-voltage environment or a low-voltage environment, the distance and electrical spacing of its output line shall not be less than the following values (unit: mm): -- Minimum electrical spacing: 4 = 12-1
-- Minimum electrical spacing = + 50
In the formula, The inverter provides the no-load rated output medium voltage (unit: V, t8.2) of the insulation material used and the working voltage: 15V (effective value), or 71V (effective value) or DC phase-to-phase (5). The insulation distance should be consistent with the insulation material used and the working voltage: GB19510.11-2004/EC61347-2-10:3000, and meet the following requirements: The minimum thickness of the supplementary insulation is .4m and the minimum thickness of the reinforced insulation is 5.4m. However, the reinforced insulation shall not be subjected to mechanical stress that may cause deformation or aging of the insulation material at the nominal working temperature. Note that under certain conditions, this degree must be increased. The qualification shall be checked by measurement and the specified dielectric strength test. 19 Protection Circuits
B The protection circuits of converters and inverters shall comply with the requirements of 19.1, 19.2 and 19.3. 19.1B The optical converter or inverter shall be equipped with an earth leakage protector to disconnect the output power supply in the event of an earth fault in the output line. The protector shall comply with the requirements of 19.5. 19.2 If the inverter or inverter is required to be equipped with an open circuit protection device, such a protection device shall be able to disconnect the power supply in the event of an interruption in the transmission line or a light failure or discharge. The high-speed protector shall be in accordance with the requirements of 19.6. 19.3 After the protector in the converter or inverter starts to operate due to an earth fault or line trip, the protector shall remain in operation until the power supply is also disconnected. When the power supply is connected again, the protector that disconnected the output power supply shall automatically reset. If there is a grounding fault or open circuit fault when the protection is in place, the protection should be noted in the requirements of 15.5.3 and 19.6.3. In order to ensure that the protection alarm will not be reinstalled, special inspection of the entire screen is required. 19.4 Compliance control shall be carried out in accordance with the relevant tests described in 19.5 and 19.6: 19.5 Grounding protection
If the converter transformer is equipped with a grounding protector, the protection should be retained in accordance with the requirements of 19, 5.1~195. 19.5.1 Answer the phone
The grounding discharge shall be tested according to the requirements of Appendix 1. 19.5.2 External contact
In the event of accidental contact between the high-voltage circuit and the ground, the ground leakage protector shall be able to disconnect the power output of the converter or frequency converter.
19.5.3 Ground-change power regulation protector
The ground-change power regulation protector shall meet the following requirements: a) If the sensor device or protection switch capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; b) If the sensor device or protection device capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; *65% of the rated current of the protection terminal should be lower than the rated output current of the converter terminal or inverter group it protects, and should not exceed 25IA
: The actual current during the fault period is determined by the fault effect of the fault device or inverter, nor is it determined by the working current of the protector. d) The working time of the protector under the rated fault current should not exceed 200s. 19.6 Open circuit protection
If the protection device is equipped with open circuit protection, its performance should meet the requirements of 19.6.1~19,5.3. 19.6.1 The open circuit voltage shall be measured in accordance with the requirements of the test circuit. 19.6.2 When the upper limit of the circuit is broken, the open circuit protector shall be able to cut off the input power of the converter or inverter. The fault status shall be detected by a sensor or other suitable device connected to the output line. 19.6.3 Open circuit protector The open circuit protector shall meet the following requirements: GB19510.11-2004/1FT:61347-2-10:2000 (if the inductor and/or protective switch are installed in the casing of the inverter). b) If the inductive component and/or protector that can disconnect the power supply is installed in the inductive inverter, then this component should be able to operate normally within the temperature range of 25°C to 65°C. c) If the inverter or frequency converter is turned on in the open circuit state as described in I.3.1, the protector should start or work within 38°C to 55°C. d) If a fault occurs when the inverter or frequency converter is turned on, the protector should be put on within 200°C and then start to work again. If the power supply is disconnected and then connected again, and the open circuit state still exists, the protector should start to work within 39°C to 59°C. Note: The image protector will not be pressed again, and the exhaust needs to be special. 20 Welding, filtering components and connecting parts
According to the requirements of Chapter 17 of GB1951C.1.
21 Heat resistance, fire resistance and electrical tracking
According to the requirements of Chapter 1R of GT15519.1.
22 Corrosion resistance
According to the requirements of Chapter 19 of GH1S519.1,
23 No negative rated output voltage and rated output current 23.1 No negative rated output voltage
A The rated output voltage between the terminals of the converter or transformer and between them and the ground shall not exceed 50CU (peak value || tt||The rated no-load voltage between the B-type converter and the ground shall not exceed 50V, and the rated no-load voltage between the two shall not exceed: 10000V.
23.2 Rated output current
The rated output current of a Class A converter or transformer shall not exceed 35mA (effective value) or 50A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. The rated output current of a Class B converter or transformer shall not exceed 2mA (effective value) or 4n11A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. 23.3 Compliance
The test shall be carried out in accordance with the requirements of the appendix.4m
The minimum thickness of reinforced insulation is 5.4mT. However, the reinforced insulation is not subjected to mechanical stresses that may cause deformation or aging of the insulation material at the nominal operating temperature. Note that in the case of organic stress, the thickness must be increased. Compliance is checked by measurement and the specified dielectric strength test. 19 Protection circuits
B The protection circuits of converters and transformers shall comply with the requirements of 19.1, 19.2 and 19.3. 19.1B The optical converter or transformer shall be equipped with an earth leakage protector to disconnect the output power supply in the event of an earth fault at the output line. The protector shall comply with the requirements of 19.5. 19.2 If the inverter or transformer is required to be equipped with open circuit protection, this protection shall be able to disconnect the power supply in the event of an interruption in the transmission line or a light failure or discharge. The high-speed protector shall meet the requirements of 1S, 6. 19.3 After the protector in the converter or frequency converter starts to work due to a ground fault or line trip, the protector should remain in operation until the power is cut off. When the power is turned on again, the protector that cut off the output power should automatically reset. If there is a grounding fault or open circuit fault when the protection is in place, the protection should be noted in the requirements of 15.5.3 and 19.6.3. In order to ensure that the protection alarm will not be reinstalled, special inspection of the entire screen is required. 19.4 Compliance control shall be carried out in accordance with the relevant tests described in 19.5 and 19.6: 19.5 Grounding protection
If the converter transformer is equipped with a grounding protector, the protection should be retained in accordance with the requirements of 19, 5.1~195. 19.5.1 Answer the phone
The grounding discharge shall be tested according to the requirements of Appendix 1. 19.5.2 External contact
In the event of accidental contact between the high-voltage circuit and the ground, the ground leakage protector shall be able to disconnect the power output of the converter or frequency converter.
19.5.3 Ground-change power regulation protector
The ground-change power regulation protector shall meet the following requirements: a) If the sensor device or protection switch capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; b) If the sensor device or protection device capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; *65% of the rated current of the protection terminal should be lower than the rated output current of the converter terminal or inverter group it protects, and should not exceed 25IA
: The actual current during the fault period is determined by the fault effect of the fault device or inverter, nor is it determined by the working current of the protector. d) The working time of the protector under the rated fault current should not exceed 200s. 19.6 Open circuit protection
If the protection device is equipped with open circuit protection, its performance should meet the requirements of 19.6.1~19,5.3. 19.6.1 The open circuit voltage shall be measured in accordance with the requirements of the test circuit. 19.6.2 When the upper limit of the circuit is broken, the open circuit protector shall be able to cut off the input power of the converter or inverter. The fault status shall be detected by a sensor or other suitable device connected to the output line. 19.6.3 Open circuit protector The open circuit protector shall meet the following requirements: GB19510.11-2004/1FT:61347-2-10:2000 (if the inductor and/or protective switch are installed in the casing of the inverter). b) If the inductive component and/or protector that can disconnect the power supply is installed in the inductive inverter, then this component should be able to operate normally within the temperature range of 25°C to 65°C. c) If the inverter or frequency converter is turned on in the open circuit state as described in I.3.1, the protector should start or work within 38°C to 55°C. d) If a fault occurs when the inverter or frequency converter is turned on, the protector should be put on within 200°C and then start to work again. If the power supply is disconnected and then connected again, and the open circuit state still exists, the protector should start to work within 39°C to 59°C. Note: The image protector will not be pressed again, and the exhaust needs to be special. 20 Welding, filtering components and connecting parts
According to the requirements of Chapter 17 of GB1951C.1.
21 Heat resistance, fire resistance and electrical tracking
According to the requirements of Chapter 1R of GT15519.1.
22 Corrosion resistance
According to the requirements of Chapter 19 of GH1S519.1,
23 No negative rated output voltage and rated output current 23.1 No negative rated output voltage
A The rated output voltage between the terminals of the converter or transformer and between them and the ground shall not exceed 50CU (peak value || tt||The rated no-load voltage between the B-type converter and the ground shall not exceed 50V, and the rated no-load voltage between the two shall not exceed: 10000V.
23.2 Rated output current
The rated output current of a Class A converter or transformer shall not exceed 35mA (effective value) or 50A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. The rated output current of a Class B converter or transformer shall not exceed 2mA (effective value) or 4n11A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. 23.3 Compliance
The test shall be carried out in accordance with the requirements of the appendix.4m
The minimum thickness of reinforced insulation is 5.4mT. However, the reinforced insulation is not subjected to mechanical stresses that may cause deformation or aging of the insulation material at the nominal operating temperature. Note that in the case of organic stress, the thickness must be increased. Compliance is checked by measurement and the specified dielectric strength test. 19 Protection circuits
B The protection circuits of converters and transformers shall comply with the requirements of 19.1, 19.2 and 19.3. 19.1B The optical converter or transformer shall be equipped with an earth leakage protector to disconnect the output power supply in the event of an earth fault at the output line. The protector shall comply with the requirements of 19.5. 19.2 If the inverter or transformer is required to be equipped with open circuit protection, this protection shall be able to disconnect the power supply in the event of an interruption in the transmission line or a light failure or discharge. The high-speed protector shall meet the requirements of 1S, 6. 19.3 After the protector in the converter or frequency converter starts to work due to a ground fault or line trip, the protector should remain in operation until the power is cut off. When the power is turned on again, the protector that cut off the output power should automatically reset. If there is a grounding fault or open circuit fault when the protection is in place, the protection should be noted in the requirements of 15.5.3 and 19.6.3. In order to ensure that the protection alarm will not be reinstalled, special inspection of the entire screen is required. 19.4 Compliance control shall be carried out in accordance with the relevant tests described in 19.5 and 19.6: 19.5 Grounding protection
If the converter transformer is equipped with a grounding protector, the protection should be retained in accordance with the requirements of 19, 5.1~195. 19.5.1 Answer the phone
The grounding discharge shall be tested according to the requirements of Appendix 1. 19.5.2 External contact
In the event of accidental contact between the high-voltage circuit and the ground, the ground leakage protector shall be able to disconnect the power output of the converter or frequency converter.
19.5.3 Ground-change power regulation protector
The ground-change power regulation protector shall meet the following requirements: a) If the sensor device or protection switch capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; b) If the sensor device or protection device capable of cutting off the output power is installed inside the enclosure of the converter or inverter, such component shall be able to operate normally within the temperature range specified in the specification; *65% of the rated current of the protection terminal should be lower than the rated output current of the converter terminal or inverter group it protects, and should not exceed 25IA
: The actual current during the fault period is determined by the fault effect of the fault device or inverter, nor is it determined by the working current of the protector. d) The working time of the protector under the rated fault current should not exceed 200s. 19.6 Open circuit protection
If the protection device is equipped with open circuit protection, its performance should meet the requirements of 19.6.1~19,5.3. 19.6.1 The open circuit voltage shall be measured in accordance with the requirements of the test circuit. 19.6.2 When the upper limit of the circuit is broken, the open circuit protector shall be able to cut off the input power of the converter or inverter. The fault status shall be detected by a sensor or other suitable device connected to the output line. 19.6.3 Open circuit protector The open circuit protector shall meet the following requirements: GB19510.11-2004/1FT:61347-2-10:2000 (if the inductor and/or protective switch are installed in the casing of the inverter). b) If the inductive component and/or protector that can disconnect the power supply is installed in the inductive inverter, then this component should be able to operate normally within the temperature range of 25°C to 65°C. c) If the inverter or frequency converter is turned on in the open circuit state as described in I.3.1, the protector should start or work within 38°C to 55°C. d) If a fault occurs when the inverter or frequency converter is turned on, the protector should be put on within 200°C and then start to work again. If the power supply is disconnected and then connected again, and the open circuit state still exists, the protector should start to work within 39°C to 59°C. Note: The image protector will not be pressed again, and the exhaust needs to be special. 20 Welding, filtering components and connecting parts
According to the requirements of Chapter 17 of GB1951C.1.
21 Heat resistance, fire resistance and electrical tracking
According to the requirements of Chapter 1R of GT15519.1.
22 Corrosion resistance
According to the requirements of Chapter 19 of GH1S519.1,
23 No negative rated output voltage and rated output current 23.1 No negative rated output voltage
A The rated output voltage between the terminals of the converter or transformer and between them and the ground shall not exceed 50CU (peak value || tt||The rated no-load voltage between the B-type converter and the ground shall not exceed 50V, and the rated no-load voltage between the two shall not exceed: 10000V.
23.2 Rated output current
The rated output current of a Class A converter or transformer shall not exceed 35mA (effective value) or 50A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. The rated output current of a Class B converter or transformer shall not exceed 2mA (effective value) or 4n11A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. 23.3 Compliance
The test shall be carried out in accordance with the requirements of the appendix.61347-2-10:2000) If the inductor and/or protective switch that can disconnect the power supply is installed in the housing of the converter, the components shall operate normally within the temperature range specified by the manufacturer. If the inductor and/or protective switch that can disconnect the power supply is installed in the converter, the components shall operate normally within the temperature range specified by the manufacturer. b) If the inductor and/or protective switch that can disconnect the power supply is installed in the converter, the components shall operate normally within the temperature range of 25°C to 65°C. c) If the converter or inverter is turned on in the open circuit state as described in I.3.1, the protective switch shall start or operate within 38°C to 55°C. d) If the phenomenon occurs when the converter or inverter is turned on, the protective switch shall start or operate within 200°C. If the power supply is disconnected and then turned on again, and the open circuit state still exists, the protective switch shall start or operate within 39°C to 59°C. Note: To ensure that the image protector will not be repeated, it is necessary to pass special tests. 20 Welding, filtering components and connecting parts
According to the requirements of Chapter 17 of GB1951C.1.
21 Heat resistance, fire resistance and electrical tracking
According to the requirements of Chapter 1R of GT15519.1.
22 Corrosion resistance
According to the requirements of Chapter 19 of GH1S519.1,
23 No negative rated output voltage and rated output current 23.1 No negative rated output voltage
The positive rated output voltage between the terminals of the A-type converter or transformer and between them and the ground shall not exceed 50CU (peak value
The no-load rated voltage between the B-type converter and the ground shall not exceed 50V, and the no-load rated voltage between the terminals shall not exceed :0000V.
23.2 Rated output current
The rated output current of a class A converter or transformer shall not exceed 35mA (effective value) or 50mA (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. The rated output current of a class B converter or transformer shall not exceed 2mA (effective value) or 4n11A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. 23.3 Compliance
The test shall be carried out through the test.61347-2-10:2000) If the inductor and/or protective switch that can disconnect the power supply is installed in the housing of the converter, the components shall operate normally within the temperature range specified by the manufacturer. If the inductor and/or protective switch that can disconnect the power supply is installed in the converter, the components shall operate normally within the temperature range specified by the manufacturer. b) If the inductor and/or protective switch that can disconnect the power supply is installed in the converter, the components shall operate normally within the temperature range of 25°C to 65°C. c) If the converter or inverter is turned on in the open circuit state as described in I.3.1, the protective switch shall start or operate within 38°C to 55°C. d) If the phenomenon occurs when the converter or inverter is turned on, the protective switch shall start or operate within 200°C. If the power supply is disconnected and then turned on again, and the open circuit state still exists, the protective switch shall start or operate within 39°C to 59°C. Note: To ensure that the image protector will not be repeated, it is necessary to pass special tests. 20 Welding, filtering components and connecting parts
According to the requirements of Chapter 17 of GB1951C.1.
21 Heat resistance, fire resistance and electrical tracking
According to the requirements of Chapter 1R of GT15519.1.
22 Corrosion resistance
According to the requirements of Chapter 19 of GH1S519.1,
23 No negative rated output voltage and rated output current 23.1 No negative rated output voltage
The positive rated output voltage between the terminals of the A-type converter or transformer and between them and the ground shall not exceed 50CU (peak value
The no-load rated voltage between the B-type converter and the ground shall not exceed 50V, and the no-load rated voltage between the terminals shall not exceed :0000V.
23.2 Rated output current
The rated output current of a class A converter or transformer shall not exceed 35mA (effective value) or 50mA (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. The rated output current of a class B converter or transformer shall not exceed 2mA (effective value) or 4n11A (peak value), whichever is greater. The measurement shall be carried out in accordance with the requirements of the appendix. 23.3 Compliance
The test shall be carried out through the test.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.