title>HG 20559.6-1993 Codes for thermal insulation, heat preservation, fire protection and sound insulation of pipeline instrument flow charts - HG 20559.6-1993 - Chinese standardNet - bzxz.net
Home > HG > HG 20559.6-1993 Codes for thermal insulation, heat preservation, fire protection and sound insulation of pipeline instrument flow charts
HG 20559.6-1993 Codes for thermal insulation, heat preservation, fire protection and sound insulation of pipeline instrument flow charts

Basic Information

Standard ID: HG 20559.6-1993

Standard Name: Codes for thermal insulation, heat preservation, fire protection and sound insulation of pipeline instrument flow charts

Chinese Name: 管道仪表流程图隔热、保温、防火和隔声代号

Standard category:Chemical industry standards (HG)

state:in force

standard classification number

Standard ICS number:71.010

Standard Classification Number:>>>>P7 Chemical Industry>>Comprehensive Chemical Industry>>G04 Basic Standards and General Methods

associated standards

Publication information

other information

Introduction to standards:

HG 20559.6-1993 Pipeline Instrument Flow Diagram Insulation, Heat Preservation, Fire Prevention and Sound Insulation Code HG20559.6-1993 Standard Download Decompression Password: www.bzxz.net

Some standard content:

Pipeline instrument flow chart heat insulation, thermal insulation, fire prevention and sound insulation code HG20559.6-93 Compiled by: Process System Design Technology Center of the Ministry of Chemical Industry Ministry of Industry Approved by: Chemical Industry Implementation date: November 1, 1994 1 Definition and scope 1.0.1. Heat insulation (thermal insulation) refers to the use of thermal insulation materials to isolate the heat (cold) source from the environment. It is divided into heat isolation (thermal insulation) and cold isolation (cold insulation). 1.0.2 Heat insulation (cold insulation) is to keep the material at a certain temperature by means of heat (cold) transfer of hot (cold) medium. According to the existence of hot (cold) medium outside the material (pipe), it is divided into accompanying pipe, jacket pipe, electric heating, etc. 1.0.3 Fire prevention refers to the fire prevention treatment of steel materials such as pipelines, steel brackets, steel structures, equipment legs, skirts, etc. Sound insulation refers to the use of measures to isolate or reduce the transmission of sound sources. 1.0.4
2 Purpose
Codes are used to mark pipeline numbers in engineering design materials such as pipeline instrument flow charts. 2.0.1
3 Codes
3.0.1 Insulation, heat preservation, fire prevention and sound insulation codes are represented by one or two capital English printed letters, and the two English letters must be the same size.
3.0.2 Codes are divided into two categories: general codes and special codes. 3.0.2.1 General codes refer to insulation and heat preservation characteristics in general, without specifying specific categories, and are preferably used in version A of process flow charts (PF diagrams) and pipeline instrument flow charts (PI diagrams). 3.0.2.2 Special codes refer to specific categories. With the progress and deepening of engineering design, special codes should be used in version B (internal audit version) of the pipeline instrument flow chart (PI diagram) and subsequent versions. 3.0.3 Function type code, see Table 3.0.3. Class
Function type code
General code
Personal protection (anti-scalding)
Anti-surface condensation
Steam tracing pipebzxz.net
Hot (cold) water tracing pipe
Hot (cold) oil tracing pipe
Special medium tracing (cold) pipe
Electric tracing (electric belt)
Steam jacket
Hot (cold) water jacket
Hot (cold) oil jacket
Special medium jacket
Special code
Using insulation materials
Using cold insulation materials
Using insulation materials
Using insulation materials
Using insulation materials
Using insulation materials
Using insulation materials
Tracing pipes and using insulation materials
Tracing pipes and using heat insulation materials
Tracing pipes and using heat insulation materials
Tracing pipes and using heat insulation materials
Electric heating tapes and using heat insulation materials
Jacketed pipes and using heat insulation materials
Jacketed pipes and using heat insulation materials
Jacketed pipes and using heat insulation materials
Jacketed pipes and using heat insulation materials
Using refractory materials and coatings
Using sound insulation materials
Note: ① For the composite type that requires both thermal isolation (insulation) and cold isolation (cold insulation), the general code "I" is used to mark. When using heat-conducting glue to lay heating pipes and heating plates, the functional category code is marked according to the tracing pipe type, but the specifications and models of the heat-conducting glue need to be marked on the relevant materials and drawings.
For the composite situation that requires both heat insulation and sound insulation, the type code of the main function is used for marking. ?
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.