Machinery Industry Standard of the People's Republic of China
JB/T 10161-1999
Electromagnets for Flow-Through Dry Valves
1999-10-08 Issued
National Bureau of Machinery Industry
2000-03-01 Implementation
JB/T10161-1999
Technical standard specifies the relevant contents of electromagnets for DC parallel-flow valves, and the product structure, technical requirements, test methods, verification rules, marking, packaging, transportation and storage are in line with the current national standards and industry standards, and are more specific and operable. This standard is proposed and managed by the Nengdu Machine Tool Electromagnetic Research Institute. This standard is issued by: Anyang Hangchuang Electric Machinery Factory, this standard is issued by: Yan Shuxin, Bangfeng, scope
Machinery Industry Standard of the People's Republic of China
Solenoid for DC Dry Valve
JB/T 10161-[999
This standard specifies the type, parameters, technical requirements, test methods and inspection regulations of electromagnets for DC dry valves. This standard is applicable to single-phase bridge type full micro-rectifier without filter, with a voltage up to 22V, used as a control circuit for electric valves and magnets [hereinafter referred to as electromagnetics] Z Reference Standards
The following standards contain provisions that can be cited in this standard and constitute non-standard provisions. When this standard is revised, the versions shown are valid. All standards will be reviewed, and all parties using this standard should explore the possibility of using the latest versions of the following standards. GH:T 2423.4—1V93
GU:T 2828-:987
GB/T 29U0.181992
GEB/T 42U7—:984
GR/T4942.3—[993
GR/T1404B[—]993
IR.T5244—1991
3 Terms and symbols
Basic environmental test specifications for electronic products Membrane test Db: Alternating damp heat test method Batch inspection plan Teaching drag sampling procedure and sampling table (applicable to continuous batch inspection) Good electrical T terminology Low voltage electrical appliances
Solid insulating materials in moisture Determination method of leakage tracking index and leakage surge resistance index under wet conditions
General provisions for low-voltage switchgear and controlgear
Electromagnet for hydraulic smoke
The terms and symbols of this standard conform to the provisions of GB/T2900.18 and JB/T5244 4 types, basic parameters and dimensions
4.1 Structural type
The electromagnet is armored screw type push type, with right protective casing and no reset device. 4.2 Model and its meaning
Yangshenghua number
With borrowed light, no signal mark if no X
With plug socket, no C means self-H line
Specification code
Design serial number
Electric iron
Approved by the same machine bottle industry bureau on 1999-10-08 and implemented on 2000-03-01
4.3 Line network voltage equal reduction
DC:12V24V.11oV,220V.
4. 4 Basic varieties and parameters
JB/T·1016t—1990
The varieties and basic age of electromagnets shall conform to the requirements of Table 1.
MFZI1-0.7C:
MFZ115C
MFZ1-2C
MF21-25C
MJZ1-3.8C
MF71-1.5C:
MF21-10C
Frequency
4.5 External dimensions and installation dimensions
Frequency fixed stroke
Residual stroke
The external dimensions and installation dimensions of the electromagnet shall conform to the requirements of Figure 1 and Table 2. To the overall dimensions and installation dimensionsbZxz.net
Power-on continuous rate when the standard operating rate
MI-ZL-D.7C
MFZ1--.3.
MR21 2C
MFZ1-2.5C
MI21-3.8C
MFZ.I4 SC:
M21-10
5 Requirements
External color and
5.1 Normal working conditions and installation conditions
5. 1. 1 Weekly air penetration temperature
JB/T 19161-1999
Table 2 Overall dimensions and installation dimensions
Installation scale
45 ± 0.2
60 ± 0.2
, the weekly air temperature limit shall not exceed %:
5! The 24h average value of the solid air temperature shall not exceed +35℃:) The lower limit of the solid air temperature shall not be lower than -5℃. 5.1.2 Sea carbon
The sea depth of the installation site shall not exceed 2000m
5. 1. 3 Atmospheric residual parts
Fixed diameter of installation hole
Minimum size of upward hole
2: 013
Hole operation piece
T3.3 -0.25
21 ± 0.25
26.510.25
The relative humidity shall not exceed 50% when the air temperature is -40C. Higher relative humidity can be achieved at lower temperatures. The monthly average relative humidity in the measurement month will be 90%, and the monthly average minimum humidity is +25°C. And take into account the condensation on the surface of the product due to humidity changes: 5.1.4 The pollution level of the short-term pollution is pollution level 2. 5.1.5 Safety test conditions a) It can be installed in a small direction (when the armature moves upward, the electromagnetic continuous suction should include the armature's change b) It should be installed in an environment free from light and shock vibration: ) In a medium without desiccant, and the medium does not contain gases and dust (including conductive dust) that are sufficient to corrode and destroy the metal. d) In a section with no network attack ability: The installation category of the electromagnetic titanium is "installation industry". 5.1.6 1. Construction a) Long-term "construction: ||b) Interruption period:
5.1.? The permissible range of magnetic charge is 85%-110%. 5.1 General requirements
5.2.1 Clearance
The minimum clearance value of the electromagnet is 1.5mm. 5.2.2 Creepage distance
J810161-1999
The minimum creepage distance of the electromagnet shall comply with the provisions of Table 3. Table 3 Creepage distance
Required creepage distance
> 63-125
>125-24
About the classification of insulating material groups, they can be divided into the following four groups according to their full charge tracking index CTI: Insulating material group I: CTT 600
Insulating material group: 60CTI 400
Insulating material group Ma: 400CT1=175
Insulating material group MB: 175>CT1=100
5.2.3 External protection level
The protection level of the electromagnet shell is IP55, 5.2.4# 5.2.54 Requirements for parts: All ferrous metal parts of electromagnets, except for the working pole and the connecting parts of the magnetic system, must have protective measures. The working pole of the magnetic winding should be clean and free of grease: Plastic parts should be bright and free of cracks. 5.3 Performance requirements: 5.3.1 Dielectric performance: The electromagnet can withstand the 1min1 frequency withstand voltage test without flashing: Table 4: Withstand voltage requirements, F> 60 -363
5.3.2 Residual magnetism
The impact force of the residual magnetism is not greater than 18% of the rated suction force. 5.3.3 Before
1Pre-voltage test voltage standard converter effect micro
JB/T10161-1999
When the insulator is working under the condition of an annual average temperature of the surrounding air of +20℃, the rated voltage is applied to the excitation line of the insulator, and its stable temperature rise value shall not exceed the temperature rise limit listed in Table 5. Table "5 Temperature rise limit
Insulating material grade
The temperature rise limit obtained by the resistance method
53. 3. 4 Suction force
When the ambient air temperature at the test site is the upper limit, after the ambient temperature rise reaches the set value, within the set stroke, when the power supply voltage is 8% of the rated value, the suction force of the electromagnet shall not be less than the rated suction force value specified in Table 1. 5.3.5 Moisture resistance performance
The insulation resistance of the insulation material should be able to adapt to the damp and hot environment. According to the method specified in GB/T2423.4, the alternating heat test is carried out. The severity level of the test is the highest salinity value + 4% and the test period is 6 days. After the test, the insulation resistance is not less than the specified value in Table 6. Then carry out a 1min frequency endurance test. The test voltage is 80% of the value specified in Table 4. The insulation resistance in Table 6 is the minimum insulation resistance||tt| ... After the test, the plastic parts shall not have bulges and cracks. 5.3. The machine shall be capable of performing not less than 6 to 10 times of attraction and discharge under the specified output voltage and the working and installation conditions specified in 5.1. 5.3.8 The reverse connection dimensions of the electromagnetic head shall comply with the provisions of Figure 1 of JBT5244-1991. The protective grounding plate shall have a clear grounding mark:
6 Test method
6.1 Basic requirements
6.1.1 The electromagnet under test shall comply with the requirements of the drawings and technical documents approved by the prescribed procedures. 6.1.2 Each test or each completed sequence test shall be carried out on a new and clean product. Replacement of parts or repairs are not allowed during the test (indicator lights and heart-shaped coils are allowed to be replaced). 6.1.3 The test power supply is a single-phase bridge full-wave rectifier (without filtering equipment) DC power supply. 6.2 General inspection
6.2.1 Check the electromagnet nameplate, protective grounding plate, oil waist, anti-removal measures, packaging, plastic parts and other surface quality plates. Check the flexibility of the armature action when the sensitive magnetic coil is not energized. 6.2.2 Electromagnet assembly pre-test, external dimensions and installation dimensions, electrical distance between the membrane and the plug socket, plug connection windage, grade caliper, micrometer or special tools, equipment and receiver inspection, 6.2.3 Insulation material comparison tracking index CTI error determination, according to GB.T4207. 5
6.3 Dielectric property test
JB/T-10161-1999
6.3.1: The basic conditions of the electromagnetic frequency endurance test shall be in accordance with the provisions of 8.23.4.1 in GB/T14048.11993. 6.3.2 The waveform of the test power supply shall be in accordance with the provisions of B.2.3.4.3 of GB/14048.1-1993. 6.3.3 The T-type withstand voltage test is applied between the protective earthing piece and the contact piece (or 2) of the plug socket. 6.3.4 The micro leakage current shall not be greater than 100mA. 6.3.5 If there is no breakdown or flashover during the 1min high-frequency withstand voltage test, it is considered qualified. 6.3.6 In the factory test, the test time is allowed to be shortened to 1ss6.4 Magnetic field test
6.4.1 It is carried out on the suction test bench.
6.4.2 The K is checked to be the set voltage value.
6.4. The type test is carried out for no less than six times, and the polarity is changed after every two tests: the factory test is carried out for no less than two times, and the polarity is changed each time. 6.5 Temperature rise test
6.5.1 The test is carried out in accordance with 8.2.3.3.1 and 8.2.3.3.6 of GR/T140M8.11993. The temperature rise test should be carried out within the range of 10-40°C of ambient air temperature. The ambient air temperature change during the test should not exceed +10°C. 6.5.2 The test voltage is the rated voltage value.
5.3 The electromagnetic titanium is installed on the corresponding two-position return reading (carrying an iron block with the same outer dimensions as the reading body) and placed on a medium with poor thermal conductivity.
6.6 Suction test
6.6.1> The hot resistance R of the wire is calculated according to the formula (!): R,-ea -ar,+y
Where: The resistance temperature coefficient of the wire at -0℃ (1/234.5 for copper and 1245 for aluminum): - the maximum allowable ambient air temperature,
T,: The temperature rise of the exciting coil when the ambient temperature is converted to the allowable ambient air temperature, K; The cold environmental leakage during the test, ?; The cold electric value of the exciting coil during the R test.
6.6.2 Adjust the measured electric current to the rated voltage, and then adjust the loop current value to, and calculate it according to the formula (2): o.85U.
6.6.3 Use the repetition method to test, and change the input after every two tests. 6.6.4 The type test shall be carried out for at least sixteen times, with the polarity changed after every two tests; the factory test shall be carried out for at least twelve times, with the polarity changed each time. 6.6.5 The force at any point within the specified path shall not be less than the rated strength. 6.7 Test for heat resistance
According to the alternating heat filter test method specified in GB/T2423.4, verify the heat resistance specified in 5.3.5: check the flexibility of the armature action after the test.
6.8 Low temperature storage test
6.8.1 The electromagnet test piece is placed in a low temperature mixing box for cooling, and the cooling rate is not more than 1℃/min. After the internal temperature reaches -25℃ (the difference between the temperature of the test piece and the specified low temperature value is within ±3), continue the low temperature test for 16h, and then restore the test piece under normal fire conditions (temperature 15-35, relative humidity 45%75%, air pressure 86~106kFa). The recovery time must be sufficient to reach the stable temperature under high temperature.
6.8.2 Inspection of bending materials. Painted parts should meet the requirements of 5.2.5. 6.8.3 Check the flexibility of electromagnet action. 6. Mechanical life test. 6..1 The test voltage is a constant voltage value. The electromagnet is installed on the corresponding two-way four-way body and is carried out under the condition of oil flow. The continuous rate of operation is 60%. The operating frequency is not more than 12000 times/. The electromagnet is tested in a simulation test. The reaction force spring end is selected according to the table: MF21-0.7C MF2.1-1 SC: MFZ1-2C MFZI-3.SC MIZ1-3.BC MFZ1-1.5C MF21 :
MEZI-I0C
Company: Reflection degree +[0%
6.10 External light protection level test
6.10.1 The test method is qualified according to the provisions of GB/T4942.2.
6.10.2 During the test, the electromagnet is placed vertically and placed on the corresponding body or mold. The head and seat are tested at the same time. Inspection rules
7.1 Classification of inspection and test
The inspection and test of electromagnets are divided into the following categories: a) Type test:
b) Period test:
c) Factory test: Routine test, factory sampling test. 7.2 Type test
The purpose of type test is to verify whether the design and performance of the electromagnet meet the strict requirements of this standard. Type test is a test that must be carried out by new product development units or re-trial production units. Normally type test is only carried out once, but when the changes in product design, process, material and structure may affect its working performance, it is necessary to carry out type test of all or related items again. Table 8 stipulates the items and sequence of type test: Table 8 stipulates the items and sequence of periodic test, that is, the content of general production inspection, 3. Determination of CTI value of insulating material, marking, packaging, plug size and size. External shadow size and installation size
About assembly members
Hand parts requirements
Dielectric performance test
Limit opening test
Pre-humidity potential energy test
War benefits will exist or research
Machine connection
Special protection level test
Note: External protection level test is only for replacement specifications. 7.2.2 Flat test rules
5.2.1. 5.2.2
Test method
Test sequence
Type test
The electromagnetic device to be tested by the acid test or the test must be a formal trial sample. Each test item (or test sequence) should be no less than three sets. All the specified type test items should be qualified before the electromagnetic device can be considered to have passed the type test. Products that have passed the type test can be adjusted. .2.3 Test results and evaluation
In the type test, for items that do not pose a threat to safety or seriously reduce performance indicators, except for temperature rise and shell protection items, if there are errors, the manufacturer must provide sufficient information to explain that the error is not an inherent defect in the design, but is caused by the defects of individual test products. In this case, the original test product is allowed to be tested. If the test is qualified, it is still considered to be qualified for the type test. 7.3 Periodic test
. 3.1 When the product passes the type test and enters the stage of fixed production, a periodic test is carried out to check the stability of the product. Periodic tests should be carried out every 5 years. 3.1.2 The periodic test items and sequence shall be in accordance with the provisions of Table 8. 7.3.2 Periodic test rules
JB/T10161-1999
The electromagnetic equipment for periodic test must be randomly selected from the batch of products that have passed the factory test. Each test item (or test sequence) shall be selected at least two units. All the specified test items must be qualified. If one unit fails in the test, it is allowed to retest the item according to the original state. If the retest results are all normal, it can be considered that the periodic test is qualified. If another unit fails in the test, it is considered that the periodic test is unqualified.
7.4 Exit test
7.4.1 Regular test
Routine test is the test and inspection conducted by the manufacturer before the electromagnetic equipment is shipped. The purpose is to check for defects in materials, processes and assembly.
7.4.1.! See Table 9 for routine test items and test methods. Table 9 Routine test items
Routine test items
8 Mark
5. Dielectric energy
e. Test plan
e. Parts
7.4.1.2 Routine test method
Routine or unqualified products must be repaired one by one until they are completely qualified. If they cannot be repaired, they should be scrapped. 7.4.2 Selection test
Electromagnets must be inspected according to the second sampling plan of GB2828 before they are tested. 7.4.2.! Test! The test results are divided into dimensions, title sequence, inspection level and qualified quality level AQ1. Values shall be determined according to Table 10. Table 10 Factory sampling test items date
Production qualification certificate
Test items month. Requirements
Appearance 45
Random sitting and comic heart small 5.3.8
Version 52.4
.4,2.2 Factory holding test and retest specifications
Test method
Before each batch of electric iron leaves the factory, randomly select 100 samples as specified in Table 11 for inspection. If the number of unqualified units is equal to or less than A: the batch is qualified; if the number of unqualified units is equal to or more than R:, it is judged as unqualified: if the number of unqualified units is greater than A and less than R, then re-select 100 (, 100) units for inspection. If the total number of unqualified units after release is equal to or less than 4, the product is still good; if the total number of unqualified units is equal to ten, the batch is judged to be unqualified. Batch specification
51-150
051-2801
281--5
501-1200
120:1-3200
Transfer rules
JB/T10161190
Output inspection sampling table
Output: Sampling inspection shall follow the provisions of 4.6.3 of GB/T2828-1987 and implement the transfer rules, 8 Marking, packaging, transportation and storage
&1 Name
Wind 1.! Each electromagnet shall be marked with the most visible, clear and durable mark, and shall not be placed on removable parts. The mark shall include a) manufacturer name or trademark h) product number (or) name: c) rated voltage: d) rated force: e) rated travel; f) year and month of manufacture or number g) enclosure protection grade, 8.1.2 The magnetizing date of the electromagnet shall have the following marks: a) product model: middle and upper rated plate 8.2 Packaging 2.1 Products must be inspected and qualified before they can be packaged. 8.2.2 The product packaging environment shall be clean, dry and free of harmful media. 8.2.3 The outside of the packaging box shall be marked with the manufacturer’s name or trademark, product model and name, etc. 8.2.4 The packaging box shall contain a packing list and a production manual. Each product (or each packaging box) shall be accompanied by a production certificate. 8.2.5 The gross weight of each box shall not exceed 40kg. 8.2.6 The outside of the packaging box shall have the following text and logos to indicate the product: a) Name and address of the receiving unit:
1) Model, name, specifications and number of products: c) Name and address of the lending unit:
2) Gross weight of the packaging box and net weight of the product:
3) The gross weight of the packaging box and the net weight of the product:
4) The gross weight of the packaging box and the net weight of the product:
5) The gross weight of the packaging box and the net weight of the product:
6) The gross weight of the packaging box and the net weight of the product:
7) The gross weight of the packaging box and the net weight of the product:
8) The gross weight of the packaging box and the net weight of the product:
9) The gross weight of the packaging box and the net weight of the product:
10) The gross weight of the packaging box and the net weight of the product:
11) The gross weight of the packaging box and the net weight of the product:
12) The gross weight of the packaging box and the net weight of the product:
13) The gross weight of the packaging box and the net weight of the product:
14) The gross weight of the packaging box and the net weight of the product:
15) The gross weight of the packaging box and the net weight of the product:
16) The gross weight of the packaging box and3. The outside of the packaging box shall be marked with the manufacturer’s name or trademark, product model and name, etc. 8.2.4 The packaging box shall contain a packing list and a production manual. Each product (or each packaging box) shall be accompanied by a production certificate. 8.2.5 The gross weight of each box shall not exceed 40kg. 8.2.6 The outside of the packaging box shall have the following text and logos to indicate the product: a) Name and address of the receiving unit:
1) Model, name, specifications and number of products: c) Name and address of the lending unit:
2) Gross weight of the packaging box and net weight of the product:
3) The outside of the packaging box shall be marked with the manufacturer’s name or trademark, product model and name, specifications and number, etc. 4) The inside of the packaging box shall contain a packing list and a production manual. Each product (or each packaging box) shall be accompanied by a production certificate. 5) The gross weight of the packaging box and the net weight of the product shall be
6) The outside of the packaging box shall have the following text and logo to indicate the product:
7) The outside of the packaging box shall have the following text and logo to indicate the product:
8) The outside of the packaging box shall have the following text and logo to indicate the product:
9) The outside of the packaging box shall have the following text and logo to indicate the product:
10) The outside of the packaging box shall have the following text and logo to indicate the product:
11) The outside of the packaging box shall have the following text and logo to indicate the product:
12) The outside of the packaging box shall have the following text and logo to indicate the product:
13) The outside of the packaging box shall have the following text and logo to indicate the product:
14) The outside of the packaging box shall have the following text and logo to indicate the3. The outside of the packaging box shall be marked with the manufacturer’s name or trademark, product model and name, etc. 8.2.4 The packaging box shall contain a packing list and a production manual. Each product (or each packaging box) shall be accompanied by a production certificate. 8.2.5 The gross weight of each box shall not exceed 40kg. 8.2.6 The outside of the packaging box shall have the following text and logos to indicate the product: a) Name and address of the receiving unit:
1) Model, name, specifications and number of products: c) Name and address of the lending unit:
2) Gross weight of the packaging box and net weight of the product:
3) The outside of the packaging box shall be marked with the manufacturer’s name or trademark, product model and name, specifications and number, etc. 4) The inside of the packaging box shall contain a packing list and a production manual. Each product (or each packaging box) shall be accompanied by a production certificate. 5) The gross weight of the packaging box and the net weight of the product shall be
6) The outside of the packaging box shall have the following text and logo to indicate the product:
7) The outside of the packaging box shall have the following text and logo to indicate the product:
8) The outside of the packaging box shall have the following text and logo to indicate the product:
9) The outside of the packaging box shall have the following text and logo to indicate the product:
10) The outside of the packaging box shall have the following text and logo to indicate the product:
11) The outside of the packaging box shall have the following text and logo to indicate the product:
12) The outside of the packaging box shall have the following text and logo to indicate the product:
13) The outside of the packaging box shall have the following text and logo to indicate the product:
14) The outside of the packaging box shall have the following text and logo to indicate the